TCV - Terminal unit

Circular terminal diffuser for installation without suspended ceiling

Circular and compact in design for free installation.

  • Horizontal air supply
  • Suitable for supply and exhaust
  • Integrated circular balancing plenum with measurement and adjustment functions
  • Effective sound attenuation
  • Circular duct connection with gasket
  • Deflector for direction of flow pattern
  • Detachable front plate enables cleaning of the terminal unit and ductwork

The diffuser and plenum shall be made of epoxy-painted steel with a white (RAL 9010) colour.
The diffuser shall diffuse the supply air into the space through the side slot and perforated front panel, ensuring a high mixing rate.
Flow pattern of the diffuser shall be adjustable in a 1, 2, 3 or 4-way direction by shaping the deflector.

The diffuser shall be integrated to a balancing plenum equipped with a measurement and adjustment module.
The diffuser shall have a detachable perforated front panel in order to provide access to the measurement and adjustment module in the plenum.
The balancing plenum shall have a spigot equipped with integral gasket for airtight duct connection.

Introduction

TCV

Round terminal unit
 


 

  • Horizontal air supply
  • Suitable for supply and exhaust
  • Integrated circular balancing plenum with measurement and adjustment functions
  • Effective sound attenuation
  • Circular duct connection with gasket
  • Deflector for direction of flow pattern
  • Detachable front plate enables cleaning of the terminal unit and ductwork


 

Dimensions


DIMENSIONS AND WEIGHT



NS  ØW  ØW1  H  H1  ØD 
100  300 289 258 93 99
125  300 289 258 103 124
160  450 439 294 121 159
200  450 439 318 138 199
250  600 589 377 174 249


Weight

TCV + MSM
NS  Weight(kg) 
100  3.90
125  3.86
160  7.49
200  7.72
250  12.39


Material and finishing

 

MATERIAL AND FINISHING

 

PART  MATERIAL  NOTE 
Upper plate Steel  
Front panel Perforated steel  
Deflection
panels
Steel  
Plenum Galvanised steel  
Attenuation
material
Polyester fibre Surfaces
protection layer
Spigot Galvanised steel  
Gasket Rubber compound  
Finishing Painted / White RAL 9010 Special colours available

 

Function


FUNCTION



Air is supplied into the space through the side slots and front panel of the diffuser and mixed with the room air outside the diffuser.
The throw pattern can be deflected in different (1, 2, 3 and 4) directions with the deflection panels.
Recommended maximum air temperature difference between supply and room air in cooling situations is 10 °C.

Installation


INSTALLATION




CODE  DESCRIPTION
1  FRONT PANEL
2  DEFLECTOR PANEL
3  DEFLECTOR PLATE
4  SPRING
5  PLENUM

The terminal unit is connected directly to the duct by screwing or riveting. The desired flow pattern is selected with the deflector panels during installation.

It is recommended that the minimum safety distance before the terminal unit is 3xD.

In an exhaust application neither deflector panels nor deflector plate are used.

Adjustment


ADJUSTMENT




CODE  DESCRIPTION
1  FRONT PANEL
2  MEASUREMENT AND ADJUSTMENT MODULE
3  PRESSURE TEST PLUG
4  EQUALISATION PLATE
5  PLENUM

The supply volume flow rate is determined using the measurement and adjustment module MSM.
Open the front panel and equalisation plate, pass the tubes and control spindle through the equalisation plate and side slot of the diffuser.
Replace the front panel.

Measure the differential pressure using a manometer. The airflow rate is calculated using the formula below.


Adjust the airflow rate by rotating the control spindle until the desired setting is achieved.
Lock the damper position with a screw.
Reassemble the tubes and spindle into the plenum and replace the diffuser front panel.

The exhaust flow rate is determined by using the separate measurement module located in the equalisation plate.

K- factor for installations with different safety distances (D= duct diameter)

SUPPLY AIR

TCV ØD  (>8xD)  min 3xD 
100 6.0 8.5
125 10.0 13.0
160 17.1 22.8
200 27.5 32.1
315 47.9 55.5

EXHAUST AIR

TCV ØD  k 
100 8.7
125 21.6
160 21.6
200 53.1
250 53.1


Servicing


SERVICING

Open the front panel of the diffuser and clean the parts by wiping with a damp cloth.
Remove the equalisation plate, and measurement and adjustment module by gently pulling the shaft (not the control spindle or measurement tubes!).
Wipe the parts with a damp cloth, instead of immersing in water.
Reassemble the equalisation plate, and measurement and adjustment module by pushing the shaft back into place until the unit meets the stopper.
Push the front panel back into place so that the springs lock.

Specification


SPECIFICATION


The diffuser and plenum shall be made of epoxy-painted steel with a white (RAL 9010) colour.
The diffuser shall diffuse the supply air into the space through the side slot and perforated front panel, ensuring a high mixing rate.
Flow pattern of the diffuser shall be adjustable in a 1, 2, 3 or 4-way direction by shaping the deflector.

The diffuser shall be integrated to a balancing plenum equipped with a measurement and adjustment module.
The diffuser shall have a detachable perforated front panel in order to provide access to the measurement and adjustment module in the plenum.
The balancing plenum shall have a spigot equipped with integral gasket for airtight duct connection.

Product Code


PRODUCT CODE


TCV/S-D

   S = Construction
    A  Supply with MSM module
    B  Exhaust with MEM module
   
   D = Connection size
    100, 125, 160, 200, 250


Specifics and accessories

   CO = Colour
    W  White
    X  Special colour

Code example

   TCV/A-100, CO=W


Downloads & Media

Halton TCV - ru
Type
Datasheet
Language
ruso (Rusia)
Size
1.6 MB
Halton TCV - fi
Type
Datasheet
Language
finés (Finlandia)
Size
1.5 MB
Halton TCV - se
Type
Datasheet
Language
sueco (Suecia)
Size
1.5 MB
Halton TCV - fr
Type
Datasheet
Language
francés (Francia)
Size
979.9 kB
Halton TCV - nl
Type
Datasheet
Language
neerlandés (Países Bajos)
Size
1.5 MB
Halton TCV - dk
Type
Datasheet
Language
danés (Dinamarca)
Size
1.5 MB
Halton TCV - gb
Type
Datasheet
Language
inglés (Reino Unido)
Size