FDV - Fire valve

  • Combined exhaust valve and fire damper for circular ducts
  • Type-approved unit compliant with the EN 1366-2 and EN 13501-3 standards
  • Fire resistance class ES120/EIS15 for installations on a lightweight plasterboard, lightweight concrete, concrete and masonry walls
  • Fire resistance class ES120/EIS30 on concrete slabs
  • Fuse release temperature of 50, 72, or 100 °C
  • Manufacture in accordance with an ISO 9001 quality management system
  • External quality control by the Technical Research Centre of Finland, VTT