CBH - Chilled beam

Active chilled beam for exposed wall installation

Well suited for office, apartments and hotel rooms. Ideal for residential and hotel use where silence operation is preferred.

  • Combined cooling, heating and supply air unit for exposed wall installation
  • Limited need for maintenance, due to simple and hygienic principle of operation

PRODUCT MODELS AND ACCESSORIES

  • Model with combined cooling and heating coil
  • Options for chilled/hot water pipe connection locations
  • Coil with venting valve

 

The active chilled beam shall have an integral uni-directional air supply.
The supply air plenum is to be manufactured as a single construction free from joints. The front panel shall be openable and detachable for cleaning without using any special tools.

The active chilled beam shall be 295 mm wide and 230 mm high, with an inlet duct diameter of 100 mm.
The front panel shall be made of galvanised steel plate to a thickness of 0.75 mm.
All visible parts shall be painted to white RAL 9010, 20 % gloss.

The cooling heat exchanger shall consist of a coil with aluminium fins and six 15-mm pipes connected in series.
All joints shall be fully soldered and factory pressure tested.
Connection pipes shall be manufactured from copper, with a wall thickness of 0.9-1.0 mm.

Heating shall be incorporated within the heat exchanger by two 10-mm pipes connected in series.

The pipework s maximum rated operation pressure is 1.0 MPa.
Each beam shall be protected by a removable plastic coating.
The duct connection and pipe ends shall be sealed during transit.
Each beam is to be identifiable by a serial number printed on a label attached to the beam.

Overview

Halton CBH

Active chilled beam for exposed wall installation
 


 

  • Combined cooling, heating and supply air unit for exposed wall installation
  • Limited need for maintenance, due to simple and hygienic principle of operation
     

Product Models & Accessories

  • Model with combined cooling and heating coil
  • Options for chilled/hot water pipe connection locations
  • Coil with venting valve
     

Dimensions

Dimensions


Halton CBH

 


 

 Coil length  1500,1600...4700
 L-5  1795,1895...4995
 kg/m  10



 

Location of the pipe connections



 

Material

Material


Halton CBH

 Part  Material  Finishing  Note
 Front panel  Pre-painted
 galvanised steel
 Polyester-painted,
 White
 (RAL 9010/20 % gloss)

 Polyester-epoxy-painted
 Special colours available

 Supply air plenum  Galvanised steel    
 Brackets  Galvanised steel    
 Coil pipes  Copper    
 Coil fins  Aluminium    


Cooling/heating water pipe connections are Cu15/Cu10 with a wall thickness of 0.9-1.0 mm fulfilling the European Standard EN 1057:1996.
The maximum operating pressure of chilled/hot water pipework is 1.0 MPa.
The supply air ductwork connection is D100 mm.
 

Accessories

Accessories and product options


Halton CBH

 Accessory/model Code  Description Note
 Combined cooling
 and
 heating coil
TC = H or F  H = Coil with hot
 water circulation
 F = Coil with hot
 water circulation and
 air venting valves
 Cooling/heating copper
 water pipe connestions
 are Ø 15/10 mm
 Coil equiped with
 valves for venting
TC = D or F

 D = Coil with cold
 water circulation and
 air venting valves
 F = Coil with hot
 water circulation and
 air venting valves

 Cooling/heating copper
 water pipe connestions
 are Ø 15/10 mm
 Water pipe
 connections
WD = S or O  S = straight
 connection
 O = pipe connection
 of the heat exchanger
 at the opposite end
 from the supply air
 connection
 
 Duct cover  Made upon request,
 please contact
 sales for details
 Lenghts: 800, 900,
 …2500 mm

 Pre-painted
 galvanised steel,
 Polyester-painted
 white (RAL 9010,
 20% gloss)

Function

Function


Halton CBH 



The supply air enters the plenum of the active chilled beam, from which it is diffused into the room through nozzles and the supply slot located on the top of the beam.
The air nozzle jets efficiently induce flow of ambient room air through the heat exchanger, where it is either cooled or heated.
The supply air jet is directed horizontally along the ceiling surface.
Two different nozzle sizes are available to enable different supply airflow rates.

The cooling and heating capacities of the chilled beam are controlled by regulating the water flow rate according to the control signal of the room temperature controller.

The Halton CBH active chilled beam is designed for exposed installation next to the wall.
 

Installation

Installation


Halton CBH 



Fasten the unit to the wall using two assembly brackets, included in the delivery.
Adjust the beam horizontally and vertically to the desired position by using the two adjustment screws. The beam installation can be secured with screws through pre-drilled holes in the beam.

Install the main pipelines of the cooling and heating water loops above the level of the chilled beam to enable the venting of the pipework.

The supply air duct and pipe connection locations are specified when the product is ordered.
However, due to the symmetrical design, the supply air duct and pipe connection locations can be, when necessary, changed at the installation site:

  • remove the access plug and remount it in the other end of the beam
  • loosen the four fixing screws, then turn around and reassemble the heat exchanger, finally screwing in the fixing screws.


Adjustment

Adjustment


Halton CBH


Cooling

The recommended cooling water mass flow rate is 0.03…0.10 kg/s, resulting in a temperature rise of 1…3 °C in the heat exchanger.
To avoid condensation, the recommended inlet water temperature of the heat exchanger is 14…16 °C.
 

Heating

The recommended heating water mass flow rate is 0.01...0.04 kg/s, resulting in a temperature drop of 5…15 °C in the heat exchanger.
The recommended inlet water temperature of the heat exchanger is 35…45 °C.
 

Balancing and control of water flow rates

The water flow rates of the beam are balanced by installing the balancing valves in the outlet water pipes of the cooling and heating water circuits.
Cooling and heating output of the beam are controlled by regulating water mass flow rates. The mass flow rate can be controlled with either an ON/OFF valve or proportionally with a 2- or 3-way valve.
 

Adjustment of supply airflow rate

Each beam is equipped with a measurement tap for static pressure measurement, which enables fast and accurate measurement of the supply airflow rate.
The airflow rate is calculated with the formula below.



 

 Model Nozzle k
 CBH/F, CBH/K 3 0.73
 CBH/G, CBH/M 4 1.04


Servicing

Servicing


Halton CBH 



Code description
1.  Front panel
2.  Supply air plenum
3.  Heat exchanger
4.  Female supply air connection
5.  Pipe connections
6.  Duct cover


The active chilled beam Halton CBH with its openable construction facilitates fast and easy cleaning of the supply air plenum and heat exchanger. In beams longer than 2500 mm, the front panel can be opened in two sections.

Clean the front panel using a damp cloth.
Clean the heat exchanger using a vacuum cleaner, taking care not to damage the aluminium fins of the coil.

The supply air plenum has an access plug on the back end of the beam for cleaning the plenum.
 

Specification

Specification

 

The active chilled beam shall have an integral uni-directional air supply.
The supply air plenum is to be manufactured as a single construction free from joints. The front panel shall be openable and detachable for cleaning without using any special tools.

The active chilled beam shall be 295 mm wide and 230 mm high, with an inlet duct diameter of 100 mm.
The front panel shall be made of galvanised steel plate to a thickness of 0.75 mm.
All visible parts shall be painted to white RAL 9010, 20 % gloss.

The cooling heat exchanger shall consist of a coil with aluminium fins and six 15-mm pipes connected in series.
All joints shall be fully soldered and factory pressure tested.
Connection pipes shall be manufactured from copper, with a wall thickness of 0.9-1.0 mm.

Heating shall be incorporated within the heat exchanger by two 10-mm pipes connected in series.

The pipework s maximum rated operation pressure is 1.0 MPa.
Each beam shall be protected by a removable plastic coating.
The duct connection and pipe ends shall be sealed during transit.
Each beam is to be identifiable by a serial number printed on a label attached to the beam.
 

Product Code

Product code


CBH/S-E-L-C

S = Direction of supply patterns & nozzle type
       F         Uni-directional / Right / Nozzle 3
       K         Uni-directional / Left / Nozzle 3
       G        Uni-directional / Right / Nozzle 4
       M        Uni-directional / Left / Nozzle 4

E = Duct connection/Duct size/Damper
      S1N     Straight / 100 /Without damper

L = Total length
      1800, +100, .., 5000

C = Effective length (Cooling coil length)
       1500, +100, ... , 4700
     


Other options and accessories

WD = Location of pipe connections
     
    S      Straight
          O      Opposite

TC  = Cooling / Heating functions (Coil type)
          C      Cooling
          H      Cooling and heating
          D      Cooling only, venting valves
          F      Cooling+heating, venting valves

CO = Colour
          W     White
          X      Special colour

FP  = Front panel type
          C       Standard
          N       Without front panel

ZT  = Tailored product
          N       No
 

Code example

         CBH/F-S1N-1800-1500, WD=S, TC=C, CO=W, FP=C; ZT=N
 

Downloads & Media

Halton CBH - nl
Type
Datasheet
Taal
Nederlands (Nederland)
Grote
897,3 kB
Halton CBH - fr
Type
Datasheet
Taal
Frans (Frankrijk)
Grote
1,5 MB
Halton CBH - dk
Type
Datasheet
Taal
Deens (Denemarken)
Grote
897,9 kB
Halton CBH - se
Type
Datasheet
Taal
Zweeds (Zweden)
Grote
896,9 kB
Halton CBH - it
Type
Datasheet
Taal
Italiaans (Italië)
Grote
906,7 kB
Halton CBH - de
Type
Datasheet
Taal
Duits (Duitsland)
Grote
845,0 kB
Halton CBH - ru
Type
Datasheet
Taal
Russisch (Rusland)
Grote
928,5 kB
Eurovent Beams - 2016
Type
Certificaat
Taal
Engels (Verenigd Koninkrijk)
Grote
1,8 MB
Halton CBH - fi
Type
Datasheet
Taal
Fins (Finland)
Grote
897,1 kB
Eurovent beams - 2017
Type
Certificaat
Taal
Engels (Verenigd Koninkrijk)
Grote
1,8 MB
Halton CBH - uk
Type
Datasheet
Taal
Engels (Verenigd Koninkrijk)
Grote
895,1 kB