DKS - Multi-nozzle diffuser

Square multi-nozzle ceiling diffuser

Square diffuser with aesthetic design and adjustable throw pattern.

  • Supply air pattern can freely be directed horizontally to any direction through adjustable nozzles
  • Radials swirl and vertical air patterns are also possible
  • Directional nozzles with two-slot air path, efficiently deflects the airstreams.
  • Supply air jet velocity is efficiently reduced due to high mixing effect.
  • Detachable front plate in enables cleaning of the diffuser and supply duct work
  • Size 600 adapted for installation in modular 600x600 mm suspended ceiling

ACCESSORIES

  • Balancing plenum with measurement and adjustment functions

The diffuser must be made of epoxy-painted steel with a white (RAL 9010) standard colour. Air is supplied through plastic nozzles, which must have a two-slot design in order to ensure efficient mixing of supply air. Nozzles must also be individually adjustable in order to provide high flexibility for the adjustment of the throw pattern.
 

Option 1; no balancing plenum

The diffuser has a galvanised steel casing with a spigot with integral gasket for connection to circular duct.
The diffuser has a detachable perforated front panel that provides access to the duct.
 

Option 2; option with balancing plenum

The diffuser is connected to a balancing plenum equipped with a measurement and adjustment module.
The diffuser has a detachable front panel that provides access to the measurement and adjustment module in the plenum.
The balancing plenum has a spigot with integral gasket for air-tight duct connection.
The balancing plenum has sound attenuation material made of polyester fiber with a washable surface.

Overview

Halton DKS

Square multi-nozzle ceiling diffuser 


 

  • Supply air pattern can freely be directed horizontally to any direction through adjustable nozzles.
  • Radials swirl and vertical air patterns are also possible.
  • Directional nozzles with two-slot air path, efficiently deflects the airstreams.
  • Supply air jet velocity is efficiently reduced due to high mixing effect.
  • Detachable front plate in enables cleaning of the diffuser and supply duct work.
  • Size 600 adapted for installation in modular 600x600 mm suspended ceiling
     

Accessories

  • Balancing plenum with measurement and adjustment functions
     

Dimensions and weight

Dimensions and weight


Halton DKS

NS W W1 H ØD
100-300 300 259 77 99
100-300-600 595 259 77 99
125-300 300 259 77 124
125-300-600 595 259 77 159
160-300 300 259 77 159
160-300-600 595 259 77 159
160-450 452 411 97 159
160-450-600 595 411 97 159
200-450 452 411 97 199
200-450-600 595 411 97 199
250-600 595 554 97 199
250-450 452 411 97 249
250-450-600 595 411 97 249
250-600 595 554 97 249
315-600 595 554 97 314

NS = Connection size - Diffuser size 
 

Weight

NS Weight (kg)
100-300 1.75
125-300 1.77
160-300 1.77
160-450 3.59
200-450 3.55
250-450 5.32
200-600 3.55
250-600 5.35
315-600 5.33

Material

Material


Halton DKS

 Part  Material  Note
 Frame  Galvanised steel  
 Front panel  Steel  
 Nozzle  Polyacetal POM  Colour alternatives:
 White, Grey and Black
 Coupling sleeve  Galvanised steel  
 Gasket  Rubber compound  
 Finishing  Painted
 White (RAL 9010)
 Special colours available

Accessories

Accessories


Halton DKS

 Accessory Code  Description
 Balancing plenum TRI  For balancing & equalising the airflow
 and attenuating the duct noise
 Balancing plenum TRH  For balancing & equalising the airflow
 and attenuating the duct noise



 

Function

Function


Halton DKS


 

Air is supplied both horizontally and vertically into the space through the front panel of the diffuser. 

The supply air pattern can be directed radially in the direction(s) desired (1, 2, 3 and 4) by rotating the nozzles (model DKS/S). Horizontal swirl jet and vertical air patterns can also be achieved by adjusting the nozzles (model DKS/W). 

Direction of the supply air jet has no effect on the pressure drop or the airflow rate. 

The recommended maximum air temperature difference between supply and room air is 10 °C.
The maximum recommended temperature for plastic material is 60°C.
 


Nozzle Settings

Nozzle settings


Halton DKS

 

                               300x300                450x450                               600x600



 


 

 





 



 


 

Installation

Installation


Halton DKS



The diffuser is connected either directly to the duct by screwing or riveting, or alternatively to the Halton TRI or Halton TRH balancing plenum.

Direct the flow pattern in the desired directions by individually rotating each nozzle in order to meet the required specifications.

A minimum safety distance upstream of the diffuser of 3xD is recommended.
 

Installation with plenum Halton TRI



The collar of Halton TRI plenum can be installed either internally in the plenum or externally on the bottom of the plenum. The height of the unit is presented in the table below for the external installation. When the collar is installed internally, the total height H1 is reduced by 60 mm.

The technical performance for the combination of supply air diffuser and Halton TRI plenum is presented separately for the two different installations.

NS Ø D1 TRI W2 H1
100-300 100 TRI-100-100 270 293-343
125-300 100 TRI-100-125 270 293-343
160-300 125 TRI-125-160 270 323-373
160-450 160 TRI-160-160 425 385-435
200-450 160 TRI-160-200 425 385-435
250-450 200 TRI-200-250 425 435-485
200-600 200 TRI-200-200 565 435-485
250-600 250 TRI-250-250 565 499-549
315-600 250 TRI-250-315 565 499-549

Adjustment

Adjustment


Halton DKS



It is not possible to adjust the airflow rate in Halton DKS itself.

In order to enable the adjustment and measurement of airflow rate it is recommended to connect the diffuser to TRI balancing plenum. The supply flow rate is determined by using the MSM measurement and adjustment module.
Open the front panel and pass the tubes and control spindle through the plastic nozzle. Replace the front panel.

Measure the differential pressure using a manometer. The flow rate is calculated using the formula below.

Adjust the airflow rate by rotating the control spindle until the desired setting is achieved. Lock the damper position with a screw.
Replace the tubes and spindle in the plenum and replace the diffuser front panel.


The k factor for installations with different safety distances
(D= duct diameter)

TRI/S >8xD min 3xD
100 6.0 7.5
125 9.9 12.6
160 16.9 21.9
200 28.3 31.0
250 47.9 51.5
315 78.6 -

Servicing

Servicing


Halton DKS



Detach the front panel of the diffuser by gently pulling it down and let it balance on the hinges. Each nozzle can be easily removed by pressing the stoppers and then pushing the nozzle through the front panel. Wipe the nozzles and the front panel with a damp cloth. The nozzles are replaced into the front plate by pushing. Reattach the front panel.

Option with balancing plenum

Remove the measurement and adjustment module by gently pulling the shaft; (not the control spindle or measurement tubes!).
Wipe the parts with a damp cloth, instead of immersing in water.
Reassemble the measurement and adjustment module by pushing the shaft until the unit meets the stopper.
Push the front panel back into place so that the springs lock.

Technical specification

Technical specification

 

The diffuser must be made of epoxy-painted steel with a white (RAL 9010) standard colour. Air is supplied through plastic nozzles, which must have a two-slot design in order to ensure efficient mixing of supply air. Nozzles must also be individually adjustable in order to provide high flexibility for the adjustment of the throw pattern.
 

Option 1; no balancing plenum

The diffuser has a galvanised steel casing with a spigot with integral gasket for connection to circular duct.
The diffuser has a detachable perforated front panel that provides access to the duct.
 

Option 2; option with balancing plenum

The diffuser is connected to a balancing plenum equipped with a measurement and adjustment module.
The diffuser has a detachable front panel that provides access to the measurement and adjustment module in the plenum.
The balancing plenum has a spigot with integral gasket for air-tight duct connection.
The balancing plenum has sound attenuation material made of polyester fiber with a washable surface.
 

Product Code

Product code


DKS/S-D-A
 

S = Airflow pattern
  
    S       1, 2, 3 or 4 directions
       W      Swirl jet construction

D = Connection size
       100, 125, 160, 200, 250, 315

 A = Diffuser size
        300x300, 450x450, 600x600
 


Other options and accessories
 

WS = Width of suspended ceiling tile
      
    NA       Not Assigned
          600      600x600 (if A=300 or 450)

CO = Colour
     
    W         White (RAL9010)
           X         Special colour

ZT =Tailored product
         N           No
 

Sub products

         TRI        Plenum (Diffusers)
         TRH      Plenum (Diffusers)


 

Code example

         DKS/S-100-300, WS=NA,CO=W,ZT=N


 

Downloads & Media

Halton DKS - fi
Type
Datasheet
Taal
Frans (België)
Grote
2,0 MB
Halton DKS - dk
Type
Datasheet
Taal
Deens (Denemarken)
Grote
2,0 MB
Halton DKS - se
Type
Datasheet
Taal
Zweeds (Zweden)
Grote
2,0 MB
Halton DKS - ru
Type
Datasheet
Taal
Russisch (Rusland)
Grote
2,0 MB
Halton DKS - fr
Type
Datasheet
Taal
Frans (Frankrijk)
Grote
1,4 MB
Halton DKS - gb
Type
Datasheet
Taal
Engels (Verenigd Koninkrijk)
Grote
2,0 MB
Halton DKS - nl