B | L | H | ØD1 male/female | ØD2 male | |
HMC | 250 | 400 | 175 | 159/161 | 98 |
Note:
Male connection: outer dimensions
Female connection: inner dimensions
PART | MATERIAL |
Casing | Galvanised steel or EN 1.4404 (AISI316L) available as an option |
Spigots | Galvanised steel and EPDM rubber or EN 1.4404 (AISI316L) available as an option |
Insulation | Mineral wool, S = 25 mm, MED approved |
Airflow is controlled via an adjusting knob installed through the diffuser. The control mechanism has mechanical limits for minimum and maximum airflows.
HMC can be installed directly through one ceiling blade.
The supply flow rate is determined by using a handheld measurement device. Adjust the minimum airflow rate by rotating the D-shape bar until the desired setting is achieved. Move the minimum airflow mechanical limiter against the stand and tighten socket cap screw. Adjust the maximum airflow rate by rotating the D-shape bar until desired setting is achieved. Move the maximum airflow mechanical limiter against the stand and tighten socket cap screw.
HMC cabin unit without a diffuser weights 6,2 kg.
f(Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
HMC-100 | ∆L(dB) | 3,7 | 4,1 | 12,4 | 21,5 | 23,8 | 33,4 | 34,9 | 35,2 |
f(Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
HMC-100 with TCL-160 | ∆L (dB) | 3,7 | 6,4 | 16,9 | 21,7 | 31 | 41,2 | 35,7 | 36,8 |
∆L: Sound attenuation not including end reflection