Halton FDB2 fire dampers are type-approved class A0(A60) fire and gas dampers for use in offshore, marine and navy ventilation systems. The FDB2 can be installed in rectangular or circular ducts. All fire dampers have a fusible link and they prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. Fire dampers are set from outside and can be installed in any position. An open-closed indicator is visible on the outside of the damper. Fire dampers with non-standard dimensions can be supplied on request.
FDB2 fire dampers meet international standards for both rectangular (width B 100-1200 mm and height H 100-1600 mm, 1 mm division) and circular ducts (Ø100-1250 mm). Modular constructions are available for bigger sizes. Non-standard dimensions and flange drilling available on request. Standard flange width 27 mm. Flanges and drilling also available according to ISO 15138 standards. Frame thickness 3 mm or 3-5 mm according to SOLAS. Also 6, 8 and 10 mm frame thicknesses are available on request. Blades are made of two sheets, each of them being 1 mm thick (sandwich design).
DIMENSIONS | S |
If B or H > 100, but < 449 | 3 |
If B or H > 450 but < 649 | 4 |
If B or H > 650 | 5 |
DIMENSIONS | S |
If A < 0.075 m2 | 3 |
If A > 0.075 and A < 0.45 m2 | 4 |
If A > 0.45 m2 | 5 |
ACTUATOR | R | A | |
Electrical (EL) | BF230, BF24, BF120 | 100 | H<300 = 300, H>300 =H |
Pneumatic (PNR) | Pneumatic rotating actuator AT100 | 170 | H<300 = 300, H>300 =H |
Pneumatic (PNR) | Pneumatic rotating actuator AT200 | 190 | H<350 = 350, H>350 =H |
Spring (SP) | Spring | 140 | H |
The above table contains only some examples of actuators and their effect on dimensions.
FDB2 circular connections
FDB2 general drawing, top
FDB2 general drawing, circular with connection flanges
DAMPER HEIGHT | TOTAL DEPTH WITH BLADES OPEN |
< 250 mm | 210 mm |
> 250 mm < 300 mm | 250 mm |
> 300 mm < 349 mm | 210 mm |
> 350 mm | 240 mm |
PART | MATERIAL | FINISHING |
Frame | Carbon steel | Painted or galvanized |
Frame | Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L) | – |
Blades | Steel | Galvanized |
Blades | Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L) | – |
Maintenance-free bearings |
Stainless steel EN 1.4404 (AISI316L) | – |
Shafts | Stainless steel EN 1.4404 (AISI316L) | – |
Halton FDB2 is available with following actuators:
DOT: manual override function available for PNR and EL models.
HSO: Halton Smart Override function for HVAC damper black-start available for PNR and EL models. With automatic reset function when power and/or pneumatic air supply is reinstated.
A wide range of accessories available.
In the event of a temperature rise in ductwork:
H/HEIGHT (mm) |
B / WIDTH (mm) | |||||||||||
100 | 200 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 | |
100 | 5 (5) | 7(7) | 9(9) | 10(10) | 12(13) | 14(15) | 15(22) | 17(25) | 19(27) | 20(30) | 22(32) | 24(35) |
200 | 7(7) | 9(9) | 11(11) | 12(12) | 14(16) | 16(18) | 18(26) | 20(28) | 22(31) | 23(34) | 25(36) | 27(39) |
300 | 9(9) | 11(11) | 13(13) | 15(15) | 17(19) | 19(21) | 21(30) | 23(32) | 25(35) | 27(38) | 29(41) | 31(43) |
400 | 11(11) | 13(13) | 15(15) | 17(17) | 20(22) | 22(24) | 24(33) | 26(36) | 28(39) | 30(42) | 32(45) | 34(48) |
500 | 13(16) | 16(19) | 18(22) | 21(25) | 23(27) | 25(30) | 28(38) | 30(41) | 32(44) | 35(47) | 37(50) | 39(54) |
600 | 15(18) | 18(21) | 20(24) | 23(27) | 25(30) | 28(33) | 30(41) | 33(45) | 35(48) | 38(51) | 40(55) | 43(58) |
700 | 18(25) | 21(28) | 23(32) | 26(35) | 29(39) | 32(42) | 34(46) | 37(50) | 40(53) | 42(57) | 45(60) | 48(64) |
800 | 20(27) | 23(31) | 25(35) | 28(38) | 31(42) | 34(46) | 37(50) | 40(53) | 43(57) | 46(61) | 49(64) | 51(68) |
900 | 22(31) | 25(35) | 28(39) | 32(42) | 35(46) | 38(50) | 41(54) | 44(58) | 47(62) | 50(66) | 53(70) | 56(74) |
1000 | 24(33) | 27(37) | 31(41) | 34(45) | 37(50) | 40(54) | 44(58) | 47(62) | 50(66) | 53(70) | 57(74) | 60(78) |
1100 | 26(36) | 30(41) | 33(45) | 37(49) | 40(54) | 44(58) | 47(62) | 51(67) | 54(71) | 58(75) | 61(79) | 65(84) |
1200 | 28(39) | 32(44) | 36(48) | 39(52) | 43(57) | 46(61) | 50(66) | 54(70) | 57(75) | 61(79) | 65(84) | 68(88) |
1300 | 31(42) | 35(47) | 38(52) | 42(56) | 46(61) | 50(66) | 54(70) | 58(75) | 62(80) | 65(84) | 69(89) | 73(94) |
1400 | 32(45) | 37(50) | 41(55) | 45(59) | 49(64) | 53(69) | 57(74) | 61(79) | 65(84) | 69(88) | 73(93) | 77(98) |
1500 | 35(48) | 39(53) | 43(58) | 48(63) | 52(68) | 53(73) | 60(78) | 65(83) | 69(89) | 73(94) | 77(99) | 82(104) |
1600 | 36(51) | 41(56) | 45(61) | 50(66) | 54(72) | 59(77) | 63(82) | 67(87) | 72(92) | 76(98) | 81(103) | 85(108) |
D2 ØD | WEIGHT |
(mm) | kg |
100 | 8 (8) |
125 | 8 (8) |
160 | 12 (12) |
200 | 13 (13) |
250 | 19 (19) |
315 | 20 (20) |
400 | 27 (27) |
500 | 35 (43) |
630 | 46 (62) |
800 | 62 (89) |
1000 | 83 (118) |
1250 | 113 (162) |
(Frame thickness according to SOLAS)
Examples of actuator weights: FDB2-EL GGA 326.1E 2,3 kg, GNA 326.1E 1,3 kg, BF230 +3,2 kg, BLF230 +1,7 kg, ExMax/Redmax +3,5 kg, CSQP +3 kg ,
FDB2-PNR AT100 +2,1 kg, AT100 as AISI316 4,4 kg, AT200 +3,2kg, AT200 as AISI316 +6,2 kg, FDB2-SP +1 kg. Control enclosure +4 kg.
Installation and maintenance instructions are with each fire damper delivery. Copies of Operation and Maintenance manuals are available from Halton Marine Sales offices and distributors.
(S)=Shape of Connection
(A) Circular on one side
(C ) Circular on two sides
(R) Rectangular
(W)=Width
100-1200
(H)=Height
100-1600
(D)=Diameter
100-1250
(FA)=Fire Approval
(C1) ABS American Bureau of Shipping
(C2) MED Marine Equipment Directive
(C3) LRS Lloyds Register
(C4) DNV-GL
(C5) BV Bureau Veritas
(C9) RMRS Russian Maritime Register
(EX)=Atex Class
(NA) No
(X1) ATEX certified damper [please fill]
(SF)=Flange Option
(H0) Eurovent flange in circular connections
(H1) Eurovent flange + loose flange in circular connections
(HA) Eurovent flanges
(HB) Eurovent flanges + counter flanges (2 sides)
(HC) Eurovent flanges + counter flange (1 side)
(N0) ISO15138 flange drilling in circular connection
(N1) ISO15138 flange drilling + Loose flange in circular connection
(NA) Circular connections without flanges
(NR) ISO15138 flange drilling
(FS)=Frame Dimensioning
(HS) Manual dimensioning
(SO) SOLAS dimensioning
(S1) SOLAS dimensioning (supplement 2015)
(MA)=Material
(AS) Stainless steel 1 mm EN1.4404
(CS) Carbon steel 1 mm
(LS) Stainless steel 1 mm EN1.4432
(SS) Stainless steel 1 mm EN1.4301
(FM)=Frame Material
(A3) Stainless steel 3 mm EN1.4404
(A4) Stainless steel 4 mm EN1.4404
(A5) Stainless steel 5 mm EN1.4404
(C3) Carbon steel 3 mm
(C4) Carbon steel 4 mm
(C5) Carbon steel 5 mm
(L3) Stainless steel 3 mm EN1.4432
(L4) Stainless steel 4 mm EN1.4432
(L5) Stainless steel 5 mm EN1.4432
(S3) Stainless steel 3 mm EN1.4301
(S4) Stainless steel 4 mm EN1.4301
(S5) Stainless steel 5 mm EN1.4301
(FI)=Finishing
(HG) Hot galvanized
(NA) Acid treatment
(PN) Standard painting grey RAL7001
(PX) Special Painting C5-M ISO12944
(IN)=Insulation
(N) No
(Y) A60 insulation on actuator side
(RE)=Actuator
(E1) Electric – Belimo, BF24-2-HL
(E3) Electric – Belimo, BF230-2-HL
(E7) Electric – Belimo, BF120-HL
(E8) Electric – Belimo, NF24A-SR
(E9) Electric – Belimo, NF24A-SR-S2
(E10) Electric – Belimo, SF24A-SR
(E11) Electric – Belimo, SF24A-SR-S2
(I1) InMax – Schischek, 15-SF
(I2) InMax – Schischek, 15-SF VAS
(I3) InMax – Schischek, 15-SF1 VAS
(I4) InMax – Schischek, 8-SF-1
(I6) InMax – Schischek, 15-SF-1
(I9) InMax – Schischek, 5.10-SF
(I10) InMax – Schischek, 5.10-SF VAS
(I11) InMax – Schischek, 8-SF-1 VAS
(K0) Electric – Belimo, BFN24.1
(K2) Electric – Belimo, BFN230.1
(P0) Pneumatic – Air Torque, AT101, Aluminium
(P3) Pneumatic – Air Torque, AT104, AISI316
(Q1) Pneumatic – Air Torque, AT201, Aluminium
(Q2) Pneumatic – Air Torque, AT204, AISI316
(S1) Spring
(T1) Electric – Belimo, BF24-T-2.1HL
(T3) Electric – Belimo, BF230-T-2.1HL
(Z2) Electric (EX) – Schischek, ExMax 15-SF
(Z3) Electric (EX) – Schischek, ExMax 5-10SF
(Z4) Electric (EX), Schischek, ExMax 15-SF VAS
(Z5) Electric (EX) – Schischek, ExMax 15-SF1 VAS
(Z6) Electric (EX) – Schischek, ExMax 8-SF1
(Z7) Electric (EX) – Schischek, ExMax 15-SF1
(Z10) Electric (EX) – Schischek, ExMax 5.10-SF VAS
(Z11) Electric (EX) – Schischek, ExMax 8-SF1 VAS
(C1) Electric – Elodrive, CSQP-05A1E 24V
(C2) Electric – Elodrive, CSQP-05A2E 120/230V
(C3) Electric – Elodrive, CSQP-10A1E 24V
(C4) Electric – Elodrive, CSQP-10A2E 120/230V
(C5) Electric – Elodrive, CSQP-15A1E 24V – Blocked
(C6) Electric – Elodrive, CSQP-15A2E 120/230V – Blocked
(FU)=Fuse
144 °C
100 °C
95 °C
74 °C
72 °C
70 °C
65 °C
50 °C
(AC)=Accessories
(E1) Junction box – Ensto, Plastic, IP66 & 67
(E2) EX junction box – Cooper, GRP, IP66, T6
(E4) Cable connectors – Wieland & Hensel
(L2) Limit switch 2 pcs – Bernstein, Plastic, IP66, Mechanical
(L4) EX Limit switch 2 pcs – Bartec, Plastic, IP66, Mechanical
(L5) EX Limit switch 4 pcs – Bartec, Plastic, IP66, Mechanical
(L6) EX Magnetic switch 2 pcs – Elobau, AISI6118, Magnetic
(L7) EX Magnetic switch 4 pcs – Elobau, AISI6118, Magnetic
(L8) EX Magnetic switch 2 pcs – Pepperl & Fuchs, AISI303, Inductive
(L9) EX Magnetic switch 4 pcs – Pepperl & Fuchs, AISI303, Inductive
(M1) Solenoid valve – SMC, Aluminium, 24 VDC
(M2) Solenoid valve – SMC, Aluminium, 230 VAC
(M3) EX solenoid valve – ASCO, Brass, 24 VDC
(M4) EX solenoid valve – ASCO, Brass, 230 VAC
(M5) EX solenoid valve – Bifold, AISI316, 24 VDC
(P1) Manual pneumatic valve – SMC, Aluminium
(P2) Manual pneumatic valve – Bifold, AISI316
(S3) Limit switch open/Close – Belimo, SN2, Mechanical
(SC) Cover box – Stainless steel
(ST) Pneumatic tubing & fittings – AISI316
(ED) Manual over-ride handle – Halton DOT or HV-SKU
(O1) Smart override handle – Halton, HSO Schischek
(O2) Smart override handle – Halton, HSO Pneumatic
Code example