Halton Jaz JDB – Diffuser

Internal info: This field is not in use

Translation available only in Halton HIT, not in web!

Request a Quote

Oversigt

Halton ‘s Jaz serie af diffusorer kombinerer fremragende ydeevne med ikonisk design. Den aerodynamiske konstruktion er meget lydsvag i drift. Jaz diffusorer er velegnede til både indblæsning og udsugning og sikrer derfor et arkitektonisk flot loft.

  • Rund, diffuser til loftsmontage
  • Egnet for både tilluft og fraluft
  • Installation direkte til kanal eller til trykfordelingsboks
  • Aftageligt frontpanel for nem rengøring af enhed og kanalsytem
  • Sektorblænder for 1-3 vejs strømningsmønster
  • Rund kanaltilslutning med gummitætning

Tilbehør

  • Sæt af sektorblænder,som giver kontrol af strømningsmønsteret.
  • Trykfordelingsboks med lyddæmpning, måle og indreguleringsfunktion.
  • Installationspanel for modullofter.

Produkt modeler

  • JDB/S, massivt front panel
  • JDB/P, perforeret front panel
  • Direct installation to the ceiling opening
    • T-bar loft
    • Clip-In loft

Kvikvalg

Values with adjustment module (MSM) fully open.


Fig. 1. Quick selection with unit l/s

 


Fig. 2. Quick selection with unit m3/h

Dimensioner og vægt

Halton Jaz JDB, standard model (WS=NA)

NS
[mm]
Ø W
[mm]
H
[mm]
ØD
[mm]

Vægt
[kg]

125 300 116 124 1.2
160 300 121 159 1.2
200 450 126 199 2.4
250 450 136 249 2.4
315 570 146 314 4.4

Halton Jaz JDB, loftmodul (WS = T eller C)

NS
[mm]
W
[mm]
W1
(WS=T)
[mm]
W1
(WS=C)
[mm]
H
[mm]
ØD
[mm]
125 300 595 600 119 124
160 300 595 600 124 159
200 450 595 600 129 199
250 450 595 600 139 249
315 600 595 600 149 314

WS-T  =  Standard T-bar, tile 600×600
WS-C  =  Clip-in ceiling, tile 600×600

Halton Jaz JDB with Halton Pop PDI plenum


Fig. 3. Halton Jaz JDB with Halton Pop PDI plenum, externally positioned connection spigot

 


Fig. 4. Halton Jaz JDB with Halton Pop PDI plenum, internally positioned connection spigot

JDB W
[mm]
PDI ØD
[mm]
ØD1
[mm]
L
[mm]
W1
[mm]
H
[mm]
L1
[mm]
Weight
[kg]
125 300 100-125 99 127 308 282 172 168 3.9
300 125-125 124 127 308 282 172 168 4.0
160 300 125-160 124 162 308 282 172 168 3.9
300 160-160 159 162 458 358 239 280 6.2
200 450 160-200 159 202 458 358 239 280 7.3
450 200-200 199 202 458 358 239 280 7.4
250 450 200-250 199 252 458 358 239 280 7.3
450 250-250 249 252 520 480 359 280 10.6
315 570 250-315 249 317 520 480 359 280 12.4
570 315-315 314 317 520 480 359 280 12.6

Materiale

Del Materiale  Bemærkning
Svøb Stål
Front panel Stål
Sektorblænder (DP) Skummet plastik
Tilslutningsstuts med tætning Galvaniseret stål Gummipakning
Installations panel (PI) Stål
Finish Malet, hvid
(RAL 9003/30%)
 Speciel farve mulig

Features and options

Tilbehør Kode Beskrivelse
Sektorblænde DP Et sæt af sektorblændersom giver kontol af strømningsmønster 3, 2 og 1 vejs
Trykfordelingsboks PDI For indregulering og strømningsudjævning af luftmængden samt lyddæmpning af kanalstøj
Installations panel PI-N For 600×600 mm modullofter, farve hvid (RAL 9003)
PI-C For Clip-In modullofter, farve hvid (RAL 9003)

Installation panel (PI)

Funktion

  • Luften tilføres rummet gennem diffusorens sidespalter og opblandes derefter med rumluften.
  • Den anbefalede maksimumtemperaturdifferens mellem tilluft og rumluft er 10°C.
  • Strømningsmønstret kan ændres til 1, 2, 3 eller 4 vejs indblæsning vha sektorblænder.

Produktmodeller

Halton Jaz JDB/S (massivt front panel )

Halton Jaz JDB/P (perforeret front panel)

 Halton Jaz JDB, loftmodul (WS=T eller C)

Installation


Fig. 5. Halton Jaz JDB diffuser connected to a Halton Pop PDI plenum

Diffusoren tilsluttes enten direkte til kanalen med skruer eller alternativt til en Halton Pop PDI. Alternatively, it can be connected direct to the duct by riveting or screwing. In that case, minimum safety distance to the next T-branch or curve is three times the duct diameter (3xD).

The desired flow pattern is selected during installation with the deflector panels, according to the installation manual.

Installation i nedhængt loft

Ø D Ø d
124 160
159 215
199 255
249 320
314 405

Installation med loft panel (PI)

Loftpanelet vil muliggøre installation i forskellige modullofter.

 

Code Description
PI-N T-bar loft
PI-C Clip-in loft

Installation with integrated ceiling model (WS)


Code Description
WS-T T-bar loft
WS-C Clip-in loft

 

Indregulering


Fig. 6. Adjustment of airflow of diffuser and plenum combination

Airflow control

The diffuser itself has no airflow adjustment. To adjust and measure the supply airflow rate, the diffuser shall be combined with Halton Pop PDI balancing plenum with measurement and adjustment module MSM. In case of exhaust air, use of adjustment module MEM is recommended. It is not possible to measure exhaust airflow rate with adjustment module MEM.

Open the front plate and pass the tubes and control spindle through the front panel (Fig. 6.). Replace the front panel. Measure the differential pressure with a manometer. The flow rate is calculated using the formula below:

where

  • qv           Airflow rate [l/s] or [m3/h]
  • ∆pm      Measured pressure [Pa]
  • k            The k factor (see the table below)

Adjust the airflow rate by rotating the control spindle until the desired airflow rate (pressure difference) is achieved.

Set the tubes and spindle back into the plenum. Damper position can be locked with a knurled head screw of the adjuster.

Duct connection (PDI) k factor of MSM adjuster, opening > 0 [l/s]
> 8D Min. 3D
100 5.7 7.5
125 9.6 12.6
160 16.4 21.9
200 26.3 31.0
250 47.1 51.5
315 78.8

 

Duct connection (PDI) k factor of MSM adjuster, opening > 0 [m3/h]
> 8D Min. 3D
100 20.6 27.0
125 34.4 45.4
160 59.0 78.8
200 94.8 111.6
250 169.5 185.4
315 283.6

Service

Åbn diffusorens frontpanel og aftør delene med en fugtig klud.
Skub frontpanelet på plads, til fjedrene låser.

Alternativ med  trykfordelingsboks

Åbn diffusorens frontpanel.
Fjern måle og indreguleringsmodulet ved forsigtigt at trække i huset
NB! Træk ikke i styrespindelen eller i slangerne.

Aftør delene med en fugtig klud. Brug ikke rindende vand.

Monter måle og indreguleringsmodulet ved at skubbe det på plads, til det møder stoppet.
Skub frontpanelet på plads, til fjedrene låser.

Specifikation

Diffusoren skal være fremstillet af epoxy-malet stål i farven hvid (RAL 9003) som standard. Luften skal tilføres rummet gennem diffusorens sidespalter, for at sikre en høj opblanding. Strømningsmønstret skal kunne reguleres i 1, 2, 3, eller 4 retninger ved hjælp af sektorblænder.

Alternativ 1: Ingen trykfordelingsboks

Diffusoren skal have en tilslutningsdel af galvaniseret stål beregnet for tilslutning til runde kanaler. Tilslutningsdelen har en integreret gummipakning, som sikrer lufttæt kanaltilslutning.
Diffusoren skal have et aftageligt massivt eller perforeret frontpanel, som giver nem adgang til kanalsystemet.

Alternativ 2: Med trykfordelingsboks

Diffusoren skal være forbundet til en trykfordelingsboks, som indeholder en indregulerings og måleenhed.
Diffusorens frontpanel skal kunne åbnes for at tillade nem adgang til indregulerings og måleenheden i   trykfordelingsboksen.
Indreguleringsboksen skal have en studs med integreret pakning for lufttæt kanaltilslutning.
Trykfordelingsboksen skal indeholde lyddæmpningsmateriale af polyester fibre med vaskbar overflade.

Bestillingskode

JDB/S-D; CO-WS-ZT

Main options
S = Model
S Massivt front panel
P Perforeted front panel
D = Diameter af kanal tilslutning [mm] 125, 160, 200, 250, 315
Andre muligheder og tillbehør
CO = Farve
SW Signal white (RAL 9003)
X Special farve (RAL xxxx)
WS = Loftmodul
NA Ikke fastlagt
T T-bar loft, tile 600×600 (standard)
C Clip-In loft, tile 600×600
ZT = Kundetilpasset produkt
N Nej
Y Ja (ETO)
Sub product (ordered separately)
DP Sektorblænde sæt
PI-N Panel for loftinstallation T-bar
PI-C Panel for loftinstallation Clip-In
Halton Pop PDI Trykfordelingsbokse

Kode eksempel

JDA/S-200, CO=SW, WS=NA, ZT=N

Downloads

  • Halton Jaz JDB – Fiche technique

    Data

    fr_FR

    Shape 2
  • Halton Jaz JDA and JDB – installation – universal

    Data

    en_GB

    Shape 2

"*" indicates required fields

This field is for validation purposes and should be left unchanged.
Marketing Communications Consent
Max. file size: 128 MB.