Skip to content

Product / SFR

Halton Sec SFR – Smoke control damper (AAsingle)

This CE marked single compartment smoke control damper for automatically activated system (AA) is one of the lightest in the market. Light construction makes installation easy.
It is suitable for installation to smoke extract ducts. Can also be installed direct to end of the smoke extract duct.

Fire resistance class for all installation options is provided up to E600 90 S requirements.

  • Suitability for installation to the sides of the the horizontal smoke extract duct or directly to the end of the smoke extract duct
  • Sizes from 200×200 mm up to 1600×1000 mm are available
Request a Quote

Overview

This smoke control damper is one of the lightest in the market. Light construction makes installation easy. It is suitable for installation to smoke extract ducts. Fire resistence class for all installation options is provided up to E600 90 S requirements.

Features

  • Supplied with electrical non-spring return actuator (24 V or 230 V)
  • Installation to single zone fire compartment with automatically activated systems (AA)
  • Sizes from 200×200 mm up to 1600×1000 mm are available
  • Maximum air velocity through smoke control damper in open position is 15 m/s
  • Suitability for use in smoke extraction ducts with a maximum of 1500 Pa under pressure
  • Frame construction is galvanised steel
  • No spare parts or additional installation frames needed, regardless of installation method

Installation options

  • Suitability for installation to the sides of the the horizontal smoke extract duct or directly to the end of the smoke extract duct

Standards

This product complies with the following standards:

  • CE certified according to product standard EN 12101-8
  • Fire classification according to EN 13501-4 standard
    E600 90 (ved-i↔o) S 1000C300 AAsingle
  • Fire testing according to EN 1366-10
  • CE certificate of constancy of performance No: 1391-CPR-2018/0209
  • Declaration of Performance No: 10036-SFR-2019/01/01
  • Smoke control damper casing tightness class C according to EN 1751
  • Leakage through closed damper blade fulfils class 2 according to EN 1751

Dimensions and weight

 W = Width (mm)  H = Height (mm)
 200, 250, 300, 350, 400, 450, 500, 550,
600, 700, 800, +100, … 1600
 200, 250, 300, 350, 400, 450, 500, 550,
600, 700, 800, 900, 1000

Weight (kg)

H W
200 250 300 350 400 450 500 550 600 700 800 900
200 13.3 14.2 15.1 16.1 16.9 17.7 20.7 21.7 22.7 24.8 26.8 28.9
250 14.2 15.2 16.1 17.2 18.1 19.1 22.2 23.3 24.5 26.7 28.9 31.2
300 15.1 16.1 17.2 18.4 19.3 20.4 23.8 25.0 26.2 28.6 31.0 33.4
350 16.1 17.2 18.4 19.7 20.7 21.9 25.5 26.8 28.1 30.7 33.3 35.9
400 16.9 18.1 19.3 20.7 21.8 23.0 26.9 28.3 29.7 32.4 35.2 37.9
450 19.7 21.1 22.6 24.2 25.5 27.0 28.5 29.9 31.4 34.3 37.3 40.2
500 20.7 22.3 23.8 25.5 26.9 28.5 30.0 31.6 33.1 36.2 39.3 42.4
550 21.8 23.4 25.0 26.8 28.3 30.0 31.6 33.2 34.9 38.1 41.4 44.7
600 22.8 24.5 26.3 28.2 29.7 31.4 33.2 34.9 36.6 40.1 43.5 47.0
700 40.1 43.9 47.7 52.5
800 43.6 48.7 52.9 57.0
900 48.0 52.5 57.0 61.5
1000 51.5 56.4 61.2 66.0
H W
1000 1100 1200 1300 1400 1500 1600
200 31.0
250 33.4
300 35.8
350 38.5
400 40.7
450 43.1
500 45.6
550 48.0
600 50.4
700 56.3 60.1 65.8 68.6 71.5 75.3 79.1
800 61.2 65.3 71.5 74.5 77.7 81.9 86.0
900 66.0 70.5 77.2 83.9 90.8 95.3 99.8
1000 70.9 75.7 89.8 93,3 97.0 101.9 106.7

= Size not available as standard

Structure and materials

 Number  Part  Material  Note
1  Casing  Galvanised steel  –
2  Blade  Galvanised steel  –
3  Inspection hatch covering  Galvanised steel  –
4 Operating model
(actuator)
 –  –

Operating models

Electric actuator

The Halton Sec SFR smoke control damper is equipped with an electric actuator, 24 V or 230 V (no spring return or fuse aloud). The actuator is equipped with a visual position indicator and built-in limit switches both open and closed positions.

The smoke control damper must be connected to a common fire alarm or building automation system. It can be used in fully automatic (AA) activation systems.

Order code Operating model Damper sizes
(WxH, mm)
Operating Voltage Limit switch
 R1 BEN 24
15 Nm
200×400 –
1000×600
AC/DC 24 V
 R2 BEN 230
15 Nm
200×400 –
1000×600
AC  230 V
 R3 BE 24
40 Nm
600×900 –
1600×800
AC/DC 24 V
 R4 BE 230
40 Nm
600×900 –
1600×800
AC  230 V
 I1 Schischek InMax
50.75-s
72 Nm
1200×1000 –
1600×1000
24 V / 230 V

Function

The Halton Sec SFR single compartment smoke control damper is CE certified for horizontal duct orientation. It fulfils the fire resistance class up to E600 90 (Ved-i↔o) S 1000C300 AAsingle requirements.

Smoke control dampers allow smoke to be extracted from the single compartment smoke zone by dedicated smoke extraction system. In case of fire sequence of operation is important, smoke extract fans should not be started before the smoke control dampers are opened.

The smoke control damper must be connected to common fire alarm or building automation system. It can be used in fully automatic (AA) activation systems.

The smoke control damper is equipped with an electric actuator 24 V or 230 V (no spring return or fuse aloud). The actuator is equipped with built-in limit switches for both open and closed position.

The actuator has visual position indicator.

Installation

Please see/download Installation Guide for this smoke control damper from section Downloads.

Servicing

No regular maintenance is required for the product.

To ensure proper operation of smoke control dampers, an inspection must be carried out regularly according to local building codes. The minimum recommended inspection period is every 6 months. Documentation of testing must be saved for future needs.

The smoke control damper must be connected to a common fire alarm or building automation system.

The smoke control damper is equipped with two inspection hatches, enabling the possibility to check the position of the damper blade.

Upon failure during testing of the fire damper, maintenance service shall be ordered from an authorised Halton representative to ensure appropriate operation of the product.

Specification

The single compartment smoke control damper is CE certified and marked according to the standard EN 12101-8 and fire tested according to the EN 1366-10 standard.

A smoke control damper of maximum fire resistence class E600 90 (ved-i↔o) S 1000C300 AAsingle requirements.

The smoke control damper casing complies with the tightness requirements for EN 1751 class C. Leakage through closed damper blade fulfils class 2 according to EN 1751.

The smoke control damper can be installed to horizontal smoke extract duct or directly to the end of the smoke extract duct.

The casing of the smoke control damper is made of galvanised steel.
The blade of the smoke control damper is made of fire resistant asbestos free board (mineral fibre).

The actuator is equipped with visual position indicator and built-in limit switches for both open and closed positions.

The smoke control damper is equipped with two inspection hatches.

Order code

SFR-W-H; MA-OP-ZT

W  = Width of duct connection (mm)
200, 250, 300, 350, 400, 450, 500, 550, 600, 700,  +100, …, 1250

H  = Height of duct connection (mm)
200, 250, 300, 350, 400, 450, 500, 550, 600, 700, 800, 900, 1000

Other options and accessories

MA = Material
GS    Galvanised Steel

OP = Operating models
R1     BEN24, 24 V, 15 Nm
R2     BEN230, 230 V, 15 Nm
R3     BE24, 24 V, 40 Nm
R4     BE230, 230 V, 40 Nm
I1      Inmax 50.75-S, 75 Nm

ZT  = Tailored product
N       No
Y       Yes (ETO)

Code example

SFR-300-300, MA=GS, OP=R2, ZT=N

Downloads

  • Halton Sec SFR – Smoke control damper (AAsingle)

    Data

    en

    Shape 2
  • Halton Sec SFR – Savunhallintapelti (AAsingle)

    Data

    fi

    Shape 2
  • Installation guide – Halton Sec SFR

    Data

    English (en)
    Shape 2
  • Declaration of Performance (DoP) – Halton Sec Fit Rectangular (SFR)

    Data

    en_GB
    Shape 2
  • Construction Product Regulation (CPR) – SFR

    Data

    en_GB
    Shape 2
Contact Us
  • Hidden
  • Max. file size: 64 MB.