FDC - Fire damper

Fire damper


To be terminated 1.2.2018

  • CE marked according to the standard  EN 15650:2010
  • Design for installation in separating concrete and masonry walls and ceilings and lightweight plasterboard walls of fire compartments with fire resistance class EIS 120
  • Readiness for installation with all wall options as delivered no additional frames needed
  • Manufacture in accordance with the ISO 9001 quality system
  • VTT, the Technical Research Centre of Finland, is responsible for external quality control
  • Installation in circular ducts with diameter 160 to 500 mm
  • Double sealing, ensuring that the blades are tight when the fire damper is closed before and during a fire
  • Fire damper casing complying with the tightness requirements for Class C, EN 1751
  • Fire damper tightness meeting smoke damper requirement S of standard EN 1366-2
  • Suitability for use in ducts with a maximum pressure of 3100 Pa
  • Damper closing tests performed at 15 m/s duct velocity

Product Models and Accessories

  • Models equipped with either manual or electric actuators

A fire damper of class EI 120 (ve - ho ) S C 50 has a double sealing solution that ensures fire-gas resistance at all temperatures when the fire damper is closed.

In motorised models, the fuse is activated at 72 °C.
In the manually operated system, the fuse activation temperature corresponds to the specifications (50, 72, 100 °C).
The fuse is located inside the damper, and it is possible to replace it from the outside.

The fire damper has means for external opening / triggering of the release and closing.
The fire damper includes a position indicator.
The fire damper is suitable for vertical and horizontal installation on concrete and masonry walls and on ceilings and lightweight plasterboard walls between fire compartments EIS 120.

The fire damper is CE marked according to the standard 15650:2010.
The internal quality control of the fire damper manufacturer is based on the ISO 9001 quality system, and the operations of the manufacturer is subject to external third-party quality control.

Halton FDC - to be terminated 1.2.2018

Fire damper for circular ducts

  • CE marked according to the standard  EN 15650:2010
  • Design for installation in separating concrete and masonry walls and ceilings and lightweight plasterboard walls of fire compartments with fire resistance class EIS 120
  • Readiness for installation with all wall options as delivered no additional frames needed
  • Manufacture in accordance with the ISO 9001 quality system
  • VTT, the Technical Research Centre of Finland, is responsible for external quality control
  • Installation in circular ducts with diameter 160 to 500 mm
  • Double sealing, ensuring that the blades are tight when the fire damper is closed before and during a fire
  • Fire damper casing complying with the tightness requirements for Class C, EN 1751
  • Fire damper tightness meeting smoke damper requirement S of standard EN 1366-2
  • Suitability for use in ducts with a maximum pressure of 3100 Pa
  • Damper closing tests performed at 15 m/s duct velocity

Product Models and Accessories

  • Models equipped with either manual or electric actuators

Dimensions and weight

 

When the damper is installed on concrete and masonry walls or ceilings, the size of the installation hole is D + 50 mm.

When the damper is installed on lightweight walls, consult the section Documents / Installation Instructions for the size of the installation holes.
 

ØD  D-1  D/2  A 
160  159 80 300
200  199 100 360
250  249 125 360
315  314 157 450
400  399 200 550
500  499 250 630


Weight

 Model  kg
 D=160, RE=MA 7.50
 D=160, RE=B3 or B4 7.88
 D=200, RE=MA 8.50
 D=200, RE=B3 or B4 8.86
 D=250, RE=MA 9.10
 D=250, RE=B3 or B4 9.94
 D=315, RE=MA 11.00
 D=315, RE=B3 or B4 11.20
 D=400, RE=MA 13.40
 D=400, RE=B1 or B2 13.15
 D=500, RE=MA 16.60
 D=500, RE=B1 or B2 17.10

Material

The Halton FDC fire damper casing, installation flange, and installation frame are made of galvanised steel. The closing blade is made of calcium silicate and equipped with a flexible silicone seal as well as a graphite mass seal.

Accessories

 Accessory Code  Description  Electric
 actuator
 Manual
 actuator
 Safety mesh on
 actuator side
N1  Galvanised steel (10x10 mm) X X
 Safefty mesh on
 both sides
N2  Galvanised steel (10x10 mm) X X
 Fuse FU  Thermal release at 50, 72 or 100 ºC   X
 Limit switch MS  Closed position indication,
 enclosure class IP65
  X

 

Electric actuator (B1, B2, B3, B4)

In the electric actuator system when a signal from building automation reaches the actuator or the fuse reacts to a rise in temperature (72 °C) power is switched off and the spring closes the blade automatically. When the supply power is turned back on (e.g. during testing), the blade opens automatically. The actuator is equipped with built-in limit switches for both open and closed position.

The Halton FDC fire damper with 24V power supply is recommended to be connected to the Halton Safe fire damper management system (HSM). This system enables the use of smoke detectors in ductwork or room spaces. The Halton FDC fire damper can also be connected to other commonly used building automation systems

Actuator options

B1       BF24 T HL, power supply AC/DC 24V, 72 ºC (for sizes 400 and 500)
B2       BF230 T HL, power supply AC 230V, 72 ºC (for sizes 400 - 500)
B3       BLF24 T HL, power supply AC/DC 24V, 72 ºC (for sizes 160 to 315)
B4       BLF230 T HL, power supply AC 230V, 72 ºC (for sizes 160 to 315)
 

Manual actuator (MA)

The fuse reacts to the rise of temperature (72 ºC as default) and the spring closes the blade automatically. It needs to be opened manually.
Optional fuse release temperatures 50 and 100 °C are also available for the manual actuator.

Limit switch (MS)

The limit switch indicates damper blade position, sending an impulse to other remote-release fire dampers if the blade is closed, tripping an alarm in the monitoring system and/or stops / starts fans, depending on the designed system. The limit switch has no influence on the thermal fuse or release mechanism.

Function

The Halton FDC is a circular fire damper of fire resistance class EIS 120, which prevents fire and smoke from spreading in ventilation ducts. The fire damper is equipped with either a motorised actuator or manual actuation arrangement. Both actuators have a visual position indicator. If the power in the motorised actuator system is switched off, the blade closes automatically.

In both actuator options, a fuse reacts to a rise in temperature, causing a spring-return blade to close. The motorised fire damper is delivered complete with a spring-return actuator and a fuse that is activated at 72 ºC.

The fire damper is made of fireproof materials. Once the fire damper has closed, the double sealing closes the duct tightly, effectively preventing the spreading of flue gases in the ventilation ductwork. The flexible seal of the double sealing system operates at lower temperatures, while the graphite mass seal expands to insulate the system at temperatures above 150 ºC.

The Halton FDC fire damper can be connected to the Halton Safe fire damper management system (HSM)  and testing system for fire dampers. The HSM unit enables the use of smoke detectors in the ductwork or rooms. The Halton FDC fire damper also can be connected to other common building automation systems.

Installation

Installation on concrete and masonry walls

When the fire damper is installed on concrete and masonry walls and ceilings between fire compartments, the blade shaft is always horisontal.

An opening is always left in the separating element for the fire damper, and the product subsequently is grouted into this.
To make installation easier, all products come with an installation flange, which is used to fasten the fire damper to the concrete surface with screws before grouting.

During installation, the fire damper and actuator must be protected with, e.g., a plastic cover.
The correct operation of the fire damper must be ensured before and after grouting.

When the damper is installed on concrete and masonry walls or ceilings, the size of the installation hole is D + 50 mm.
 

Installation on lightweight plasterboard walls

When the fire damper is installed on lightweight plasterboard walls between fire compartments, an opening for the fire damper must be left in the plasterboard in which the installation frame (included in the delivery) is first mounted.
The blade shaft must always be horisontal.

To make installation easier, the fire damper is delivered with an installation flange, which is used to fasten the fire damper to, e.g., the steel frame of the panel wall.

The space between the fire damper and the installation frame is filled with fire prevention mastic. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover.

The correct operation of the fire damper must be ensured after application of the fire prevention mastic.

For lightweight walls, the size of the installation hole varies with the specific product; consult the section Documents / Installation Instructions for the size of the installation holes.

Detailed installation instructions, as well as an installer's installation certificate form, are supplied with each product. See also the section Documents / Installation Instructions.
 

Electric actuator wiring diagram

BF24 HL                                                         BF24 T HL
BF230 HL                                                       BF230 T HL
BLF24 HL                                                       BLF24 T HL
BLF230 HL                                                     BLF230 T HL
 

Manual actuator wiring diagram (limit switches, MS)

Damper open                              Damper drives                       Damper closed
K1:  13/14 closed                          K1:  13/14 open                       K1:  13/14 open
        21/22 open                                   21/22 closed                            21/22 closed

K2:  13/14 open                             K2:  13/14 open                      K2:  13/14 closed
       21/22 closed                                  21/22 closed                           21/22 open

Specification

A fire damper of class EI 120 (ve - ho ) S C 50 has a double sealing solution that ensures fire-gas resistance at all temperatures when the fire damper is closed.

In motorised models, the fuse is activated at 72 °C.
In the manually operated system, the fuse activation temperature corresponds to the specifications (50, 72, 100 °C).
The fuse is located inside the damper, and it is possible to replace it from the outside.

The fire damper has means for external opening / triggering of the release and closing.
The fire damper includes a position indicator.
The fire damper is suitable for vertical and horizontal installation on concrete and masonry walls and on ceilings and lightweight plasterboard walls between fire compartments EIS 120.

The fire damper is CE marked according to the standard 15650:2010.
The internal quality control of the fire damper manufacturer is based on the ISO 9001 quality system, and the operations of the manufacturer is subject to external third-party quality control.

Order Code

FDC/S-D, RE-FU-ZT

S = Model
       E       Europe

D = Connection size
      160, 200, 250, 315, 400, 500
 

Other options and Accessories

RE = Release type
         MA        Spring release
         B1         BF24 T HL, fuse 72°C (D400 ... D500)
         B2         BF230 T HL, fuse 72°C (D400 ... D500)
         B3         BLF24 T HL, fuse 72 ºC (D160 … D315)
         B4         BLF230 T HL, fuse 72 ºC (D160 … D315)

FU = Fuse release temperature (°C)
         72         72 °C
         50         50 °C
        100        100 °C

AC = Accessories
        N1         Safety mesh, 1 side, installed in actuator side
        N2         Safety mesh, 2 sides
        MS         Limit switches

ZT = Tailored Product
        N           No
        Y           Yes

Code example

       FDC/E-160, RE=MA, FU=72, ZT=N

Downloads & Media

Halton FDC - dk
Type
Datasheet
Taal
Deens (Denemarken)
Grote
443,1 kB
Halton FDC - nl
Type
Datasheet
Taal
Nederlands (Nederland)
Grote
442,5 kB
Halton FDC - uk
Type
Datasheet
Taal
Engels (Verenigd Koninkrijk)
Grote
441,1 kB
Halton FDC - se
Type
Datasheet
Taal
Zweeds (Zweden)
Grote
443,0 kB
Halton FDC - fi
Type
Datasheet
Taal
Fins (Finland)
Grote
441,4 kB
Halton FDC - ru
Type
Datasheet
Taal
Russisch (Rusland)
Grote
476,2 kB
FDC-installation-br
Type
Handleiding
Taal
Engels (Verenigd Koninkrijk)
Grote
229,0 kB
Suoritustasoilmoitus (DoP) - FDC
Type
Certificaat
Taal
Fins (Finland)
Grote
99,9 kB
Declaration of Performance (DoP) - FDC
Type
Certificaat
Taal
Engels (Verenigd Koninkrijk)
Grote
91,6 kB
Construction Product Regulation (CPR) - Fire dampers
Type
Certificaat
Taal
Engels (Verenigd Koninkrijk)
Grote
87,3 kB