PRA - Airflow damper

Circular adjustment and measurement unit

Quiet, accurate, easy to install due to compact size, easy to adjust. The best seller of its category and legendary product of Halton which has been sold in millions.

  • Airflow balancing, adjustment and measurement functions
  • Manual adjustment, no tools required
  • Accurate airflow measurement based on flow nozzle principle
  • Minimized sound generation due to conical adjustment section
  • Temperature operation range from -30 °C to +70 °C
  • Self-locking adjustment mechanism, position can be ensured with locking screw
  • Duct cleaning enabled through the unit up to size 315 mm
  • Adjustment position marker indicates proper position e.g. repositioning after cleaning
  • Inlet and outlet spigots equipped with integral rubber gaskets
  • Used also as supply air jet nozzle for air diffusion in large spaces
  • Classification of casing leakage EN 1751 class C

Product model

  • PRA unit integrated with cleaning access panel

The adjustment damper comprisse an adjustable cone and airflow measurement taps for differential pressure measurement.

The casing and adjustment cone vanes are be made of galvanised steel.

The airflow determination is based on the differential pressure measurement caused by airflow over the damper cone.
The adjustment damper has an adjustment position indicator and adjustment position marker to be used during cleaning.

Quick selection

Inleiding

Halton PRA

Inregel- en meetmodule

  • Unit voor de regeling, inregeling en meting van het luchtdebiet.
  • Handmatige inregeling, geen gereedschap vereist.
  • Nauwkeurige luchtdebietmeting op basis van het stromingsnozzelprincipe.
  • Geluidsarm dankzij conische inregelsectie.
  • Temperatuurbereik tussen -30 °C en +70 °C.
  • Zelfvergrendelend inregelmechanisme; de stand kan met een borgschroef worden vastgezet.
  • Het kanaal kan worden gereinigd via de unit tot maat 315.
  • De inregelstandindicator geeft de juiste stand aan, wat makkelijk is wanneer deze na reiniging opnieuw moet worden ingesteld.
  • De in- en uitgangkanaalaansluitingen zijn uitgerust met rubber afdichtingsmanchetten.
  • Kan als jetrooster worden gebruikt om lucht in grote ruimten te blazen.
  • Lekverlies van de behuizing: klasse C volgens EN 1751.

 

Productmodellen

  • PRA-unit voorzien van een inspectieluikje voor reiniging.

Afmetingen

Afmetingen en gewicht

 

Halton PRA 100...315
 



 

NS ØD
100 99
125 124
160 159
200 199
250 249
315 314



Halton PRA 350...1000
 



 

NS ØD H
350 349 70
400 399 70
500 499 70
630 629 70
800 799 70
1000 999 85


 

Gewicht (kg)

NS PRA/N   PRA/R 
100 0.43 1.15
125 0.53 1 .37
160 0.70 1 .73
200 0.86 2.0 9
250 1.16 2 .96
315 1.5 5 4.17
400 4.53 7.97
500 6.13 14.16
630 9.43 19.14


Materiaal

Materiaal

 

Halton PRA

 Onderdeel  Materiaal  Opmerking
 Behuizing  Gegalvaniseerd staal  
 Klepbladen  Gegalvaniseerd staal  
 Werkingsmechanisme  ABS en PBT  Maten 100…315
 Werkingsmechanisme  Staal  Maten 350…1000
 Externe afdichtingsmanchetten  1C-Polyurethaan hybrid  
 Meetnippels  Polyurethaan (PU)  

Productmodellen

Productmodellen


Halton PRA 

De Halton PRA-unit (PRA/R), die voorzien is van een RLA-inspectieluikje voor reiniging, biedt de mogelijkheid de regelklep te verwijderen om zo het kanaal te kunnen reinigen.
 

Werking

Werking


Halton PRA 



Het luchtdebiet kan worden ingesteld door aan de stelknop te draaien; zo wordt de opening van de regelconus, gevormd door iriskleppen, gewijzigd. Wanneer de opening verkleind is, neemt het luchtdebiet af en neemt het totale drukverlies dat door de unit wordt veroorzaakt, toe.

Het luchtdebiet kan worden bepaald door de differentieeldruk in de meetnippels te meten.
 

Halton PRA 100…315

Het werkingsmechanisme bevindt zich gedeeltelijk buiten de unit en tussen de regelconus en de behuizing. Wanneer de unit volledig geopend is, kan deze worden gereinigd met behulp van de gewone middelen die ook worden gebruikt om het kanaal te reinigen.
 

Halton PRA 400…1000

Het werkingsmechanisme bevindt zich gedeeltelijk buiten de unit en in de regelconus. Wanneer de unit volledig geopend is, kan deze worden gereinigd met behulp van de gewone middelen die ook worden gebruikt om het kanaal te reinigen: deze middelen worden voorzichtig door het werkings mechanisme gevoerd.
 

Halton PRA als jet PRA/S

De Halton PRA-unit kan eveneens worden gebruikt als toevoerluchtnozzel, bijv. in industriële ruimten. Raadpleeg de technische gegevens betreffende het Halton PRA/S-model opgenomen in het hoofdstuk over de technische prestaties.

Montage

Montage


Halton PRA


Maten 100...315



Code omschrijving
1.   Stroomrichtingindicator
2.   Stelknop
3.   Borgschroef voor vergrendelen van regelstand
4.   Regelstandindicator
5.   Regelstandindicator voor reiniging
6.   Regelschaal
7.   Meetnippels
 

Maten 350...1000



Code omschrijving
1.   Regelstandindicator
2.   Stelknop
3.   Meetnippels

Bevestig de regelklep d.m.v. klinknagels aan het kanaal. Zorg ervoor dat de klinknagels de werking van de Halton PRA niet verhinderen. De klinknagels moeten zich minstens 10 mm van het kanaaluiteinde bevinden.

De Halton PRA-irisregelaar wordt in het kanaal geïnstalleerd met inachtneming van de veiligheidsafstanden die in de montagerichtlijnen worden vermeld.

De richting van de unit moet overeenstemmen met de luchtstroomrichting. De luchtstroomrichting wordt aangegeven door een pijlindicator op het behuizingslabel . Met het oog op een nauwkeurige aflezing van de meetwaarden moet de unit zo worden gericht dat de plaats van de meetnippels (onder de knop) aan de montagerichtlijnen voldoet.

 

Veiligheidsafstanden

De aanbevolen veiligheidsafstand vereist om een nauwkeurige aflezing van de meetwaarden mogelijk te maken, wordt in de onderstaande afbeelding aangegeven.

Directe kanaalaansluiting zonder verstoring van de luchtstroom

  • Veiligheidsafstand voor PRA: 4xD
  • Veiligheidsafstand na PRA: 1xD

  

 

Indien het onmogelijk is de aanbevolen veiligheidsafstanden na te leven, moeten de op de afbeeldingen vermelde correctiefactoren worden toegepast om het luchtdebiet te bepalen.

Noteer de positie van de meetnippels gemarkeerd in de afbeeldingen.
 

Afbeelding  Montage  Snelheid  K-factor
1  Directe kanaalaansluiting    1
2  T-aftakking, toevoerlucht    0.95 (1D) ...1.00 (4D)
3  T-aftakking, afzuiglucht  > 2 m/s
 1...2 m/s
 0.95 (1D) ...1.00 (4D)
 0.90 (1D) ...1.00 (4D)
4  90°-bocht    0.97 (0D) ...1.00 (4D)
5  T-aftakking    1
6  90°-bocht    1
7  Stroomopwaarts van een toevoerunit    1
8  T-aftakking    1



 

Inregelen

Inregelen


Halton PRA 

Draai de stelknop in de gewenste stand (vooraf ingestelde stand indien beschikbaar).
Het luchtdebiet wordt bepaald door de differentiaaldruk in de meetnippels te meten met behulp van een manometer.
Het luchtdebiet wordt berekend aan de hand van de onderstaande formule.



De k-factor wordt vermeld in de onderstaande tabellen en in de montagerichtlijnen. De k-factor is afhankelijk van de maat van de unit en van de regelstand (a). 

Wanneer de aanbevolen veiligheidsafstanden niet worden nageleefd, moeten de correctiefactoren voor de betreffende montage worden toegepast.


Halton PRA 100, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 1.8 6.5 60.2
1.5 2.1 7.6 70.2
2 2.4 8.6 80.3
2.5 2.7 9.7 90.3
3 3.1 11.2 103.7
3.5 3.6 13.0 120.4
4 4.1 14.8 137.1
4.5 4.7 16.9 157.2
5 5.5 19.8 183.9
5.5 6.4 23.0 214.0
6 7.8 28.1 260.8



Halton PRA 125, k-faktor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 2.5 9.0 83.6
1.5 2.9 10.4 97.0
2 3.3 11.9 110.3
2.5 3.8 13.7 127.1
3 4.4 15.8 147.1
3.5 5 18.0 167.2
4 5.9 21.2 197.3
4.5 6.8 24.5 227.4
5 7.9 28.4 264.2
5.5 9.5 34.2 317.7
6 11.6 41.8 387.9



Halton PRA 160, k-faktor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 4.1 14.8 137.1
1.5 4.7 16.9 157.2
2 5.5 19.8 183.9
2.5 6.4 23.0 214.0
3 7.6 27.4 254.1
3.5 9 32.4 300.9
4 10.6 38.2 354.4
4.5 12.6 45.4 421.3
5 15 54.0 501.6
5.5 18.2 65.5 608.6
6 22.9 82.4 765.7



Halton PRA 200, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 7.1 25.6 237.4
1.5 8 28.8 267.5
2 8.8 31.7 294.3
2.5 10 36.0 334.4
3 11.4 41.0 381.2
3.5 13.1 47.2 438.0
4 15.1 54.4 504.9
4.5 17.5 63.0 585.2
5 20.5 73.8 685.5
5.5 24.2 87.1 809.2
6 29 104.4 969.7



Halton PRA 250, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 10.5 37.8 351.1
1.5 11.9 42.8 397.9
2 13.8 49.7 461.4
2.5 16.1 58.0 538.3
3 18.9 68.0 632.0
3.5 22 79.2 735.6
4 25.6 92.2 856.0
4.5 30.1 108.4 1006.5
5 35.8 128.9 1197.1
5.5 42.9 154.4 1434.5
6 52.8 190.1 1765.5



Halton PRA 315, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 18.3 65.9 611.9
1.5 21.8 78.5 728.9
2 26 93.6 869.4
2.5 30.7 110.5 1026.5
3 36.5 131.4 1220.5
3.5 43.3 155.9 1447.8
4 51.3 184.7 1715.3
4.5 61.5 221.4 2056.4
5 74.3 267.5 2484.4
5.5 92.6 333.4 3096.3
6 120.2 432.7 4019.2




 

Halton PRA 350, k-faktor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 17.6 63.4 588.5
2 24.3 87.5 812.5
3 35.2 126.7 1177.0
4 50 180.0 1671.9
5 71.6 257.8 2394.1
6 99 356. 3310.3




 

Halton PRA 400, k-faktor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 20.5 73.8 685.5
2 26.5 95.4 886.1
3 36.5 131.4 1220.5
4 55 198.0 1839.1
5 86 309.6 2875.6
6 137 493.2 4581



Halton PRA 500, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 27.5 99.0 919.5
2 39 140.4 1304.1
3 59 212.4 1972.8
4 86 309.6 2875.6
5 123 442.8 4112.8
6 175 630 5851.6




 

Halton PRA 630, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 65 234.0 2173.4
2 90 324.0 3009.4
3 115 414.0 3845.3
4 154 554.4 5149.4
5 202 727.2 6754.4
6 295 1062 9863



Halton PRA 800, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 98 352.8 3276.9
2 137 493.2 4581.0
3 198 712.8 6620.6
4 280 1008 9362.5
5 393 1414.8 13141.0
6 570 2052 19059.4




 

Halton PRA 1000, k-factor

Units Luchtdebiet (q v ) [l/s]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [m3/h]
Differentiaaldruk
(dp m ) [Pa]
Luchtdebiet (q v ) [cfm]
Differentiaaldruk
(dp m ) [in WC]
Opening a      
1 144 518.4 4815.0
2 220 792.0 7356.3
3 310 1116.0 10365.7
4 440 1584.0 14712.5
5 620 2232.0 20731.3
6 890 3204.0 29759.5

Onderhoud

Onderhoud
 

Voor het kanaal wordt gereinigd, dient er nagegaan of de huidige regelstand door de regelstandindicator voor reiniging wordt aangegeven.
Open de klep door de stelknop tegen de wijzers van de klok in te draaien.
Reinig het kanaal.
Stel de klep opnieuw op de gemarkeerde regelstand in.
 

Beschrijving

Beschrijving

 

De regelklep bestaat uit een instelbare conus en meetnippels voor de meting van de differentiaaldruk.
De behuizing en de regelconuskleppen zijn vervaardigd uit gegalvaniseerd staal.
Het luchtdebiet wordt bepaald op basis van de gemeten differentiaaldruk veroorzaakt door de luchtstroming over de regelconus.
De regelklep is voorzien van een regelstandindicator en van een specifieke regelstandindicator die moet worden gebruikt voor er wordt gereinigd.
 

Productcode

Productcode


PRA/S-D

S  = Model 
        N    Standaard
        R    Met RLA-inspectieluikje om reiniging mogelijk te maken

D   = Maat van de kanaalaansluiting
        100, 125, 160, 200, 250, 315, 350, 400, 500, 630, 800, 1000

ZT = Tailored product
       
   N   Nee

      
    

Codevoorbeeld

        PRA/N-100, ZT=N
 

Downloads & Media

Halton PRA - fr
Type
Datasheet
Taal
Frans (Frankrijk)
Grote
1,3 MB
Halton PRA - nl
Type
Datasheet
Taal
Nederlands (Nederland)
Grote
1,5 MB
Halton PRA - gb
Type
Datasheet
Taal
Engels (Verenigd Koninkrijk)
Grote
1,5 MB
Halton PRA - ru
Type
Datasheet
Taal
Russisch (Rusland)
Grote
1,6 MB
Halton PRA - se
Type
Datasheet
Taal
Zweeds (Zweden)
Grote
1,5 MB
Halton PRA - it
Type
Datasheet
Taal
Italiaans (Italië)
Grote
1,5 MB
Halton PRA - fi
Type
Datasheet
Taal
Fins (Finland)
Grote
1,5 MB