R6B - Halton Rex 600 Basic, chilled beam

Halton Rex 600 Basic

Aesthetic, ceiling-integrated chilled beam unit for conventional needs.

  • A base version to the combined cooling, heating, and supply air unit for flush installation within a suspended ceiling.
  • Well suited for spaces where demand based ventilation, individual control and flexibility are not required.
  • Making effective site logistics possible.

Typical applications: office rooms and landscape offices.

Product models and Accessories

  • Model with combined cooling and heating exchanger

The active chilled beam has an integral recirculation air path through the perforated front panel.
The front panel is openable from either side in order to allow general maintenance and cleaning.
The front panel is removable without any special tools.
The active chilled beam is 595 mm wide and 195 mm high.
The active chilled beam has an inlet duct diameter of 125 mm.

Handing of the unit can be changed on site by turning around the heat exchanger
The frame, front, and side panels are made of galvanised steel plate.
All visible parts are white, painted to RAL 9010, 20% gloss.
All pipes are manufactured from copper, and connection pipes with a wall thickness of 0.9-1.0 mm.
The fins are manufactured from aluminium.

Optionally, heating is incorporated within the heat exchanger by means of two 10-mm pipes, connected in series.
All joints are soldered and factory pressure-tested.
The pipework s maximum operation pressure is 1.0 MPa.
The active chilled beam has a measurement tap to allow air flow measurement.

Active chilled beams are protected by a removable plastic coating.
The duct connection and pipe ends remain sealed during transport.
The active chilled beams are identified by labels attached to both the active chilled beam and the plastic packaging.

Halton Rex 600 Basic

R6B - Active chilled beam

Halton Rex 600 Basic chilled beam is:

  • A base version to the combined cooling, heating, and supply air unit for flush installation within a suspended ceiling. 
  • Well suited for spaces where demand based ventilation, individual control and flexibility are not required. 
  • Making effective site logistics possible.

 Typical applications: office rooms and landscape offices.

Product models & accessories

  • Model with combined cooling and heating exchanger

Dimensions

Total lengths 1200, 1800 and 2400 mm


 

 

Total length 3000 mm


 

 

  ØD  125
  Coil length  1000, 1600, 2200, 2800
  L-5  1195, 1795, 2397, 2995
  kg/m  14

 

Integration with suspended ceiling

Material

 Part  Material  Finishing  Note
 Front panel  Pre-painted
 galvanised steel
 Polyester
 - painted
 white RAL 9010
 (20% gloss)
 Special  colours
 not available
 
 Side plates  Pre-painted
 galvanised steel
 Polyester
 - painted
 white RAL 9010
 (20% gloss)
 Special  colours
 not available.
 
 End plates  Pre-painted
 galvanised steel
  Polyester
 - painted
 white RAL 9010
 (20% gloss)
 Special  colours
 not available
 Supply air plenum  Galvanised steel    
 Brackets  Galvanised steel    
 Coil pipes  Copper    
 Coil fins  Aluminium    

Accessories

 Accessory / model Code  Description  Note
 Combined cooling and
 heating coil
TC = H  Coil with hot
 water circulation
 Cooling/heating copper
 water pipe connections
 are Ø 15/10 mm


The Halton Rex 600 Basic's cooling/heating water pipe connections are Cu15/Cu10
with wall thickness of 0.9-1.0 mm fulfilling European Standard EN 1057:1996.

The maximum chilled/hot water circuit operating pressure is 1.0 MPa.
The supply air duct connection is 125 mm.

Function

The Halton Rex 600 Basic chilled beam is designed to be installed flush with a suspended ceiling.

The primary supply air enters the plenum of the active chilled beam. From there the air is diffused into the room through nozzles.

The supply air nozzle jets efficiently induce ambient room air, which is then directed horizontally along the ceiling surface. The secondary air is drawn through the perforation located at the bottom of the beam. The air then cycled through the heat exhanger, where it is either cooled or heated before being diffused into the room.

Installation

The Halton Rex 600 Basic active chilled beam is especially suitable for ceiling mounting running parallel to the exterior wall of the room.
When selecting of the chilled beam orientation, the location of the supply air and water circuit connections are taken into account.

The chilled beam can be attached directly to the ceiling surface (H1 = 195 mm) or suspended using threaded drop rods (8 mm). Each beam is equipped with movable brackets fixed to both sides of the beam. It is recommended that the brackets be positioned one quarter of the unit length (L/4) away from the end of the beam.

Install the main pipelines of the cooling and heating water circuits above the level of the chilled beam in order to enable venting of the pipework.

The duct connection is located at the middle of the long side. Handing of the unit can be changed on site by turning the heat exhanger.

Adjustment

Cooling

The recommended cooling water mass flow rate is 0.02-0.10 kg/s, resulting in a temperature rise of 1-4 °C in the heat exchanger. To avoid condensation, the recommended inlet water temperature of the heat exchanger is over 14 °C.    

Heating

The recommended heating water mass flow rate is 0.01-0.04 kg/s, resulting in a temperature drop of 5-15 °C in the heat exchanger. The maximum recommended temperature of the inlet water for the heat exchanger is 35 °C. 

Balancing and control of water flow rates

Balance the water flow rates of the Halton Rex 600 Basic chilled beam with adjustment valves installed on the outlet side of the cooling and heating water loops. The cooling capacity and heating capacity of the chilled beam are controlled by regulating the water mass flow rate. The water mass flow rate can be controlled by using an ON/OFF valve or a two- or three-way proportional valve. Valves are not included to the delivery of the beams. 

Adjustment of supply air flow rate

Connect a manometer in the measurement tap and measure the static pressure in the Halton Rex 600 Basic chilled beam. The air flow rate is calculated according to the formula below:

Nozzle jet air flow rate (qv)

   

eff            Length of the coil [m]
Δpm           Measured static chamber pressure [Pa]
 

Nozzle 

k (l/s) k (m3/h)
A 0,71 2,56
B 0,99 3,56
C 1,36 4,90
D 2,09 7,52
E 3,33 11,99

Servicing

Code description:
1.   Front panel
2.   Casing
3.   Supply air connection
4.   Heat exchanger

Open the front panel (1) of the chilled beam. In beams longer than 2400 mm, the front panel can be opened in two sections.

Clean the supply air plenum and fins of the heat exchanger (4) with a vacuum cleaner, taking care not to damage the fins.
Clean the front panel and other visible painted plates using a damp cloth.

Specification

The active chilled beam has an integral recirculation air path through the perforated front panel.
The front panel is openable from either side in order to allow general maintenance and cleaning.
The front panel is removable without any special tools.
The active chilled beam is 595 mm wide and 195 mm high.
The active chilled beam has an inlet duct diameter of 125 mm.

Handing of the unit can be changed on site by turning around the heat exchanger
The frame, front, and side panels are made of galvanised steel plate.
All visible parts are white, painted to RAL 9010, 20% gloss.
All pipes are manufactured from copper, and connection pipes with a wall thickness of 0.9-1.0 mm.
The fins are manufactured from aluminium.

Optionally, heating is incorporated within the heat exchanger by means of two 10-mm pipes, connected in series.
All joints are soldered and factory pressure-tested.
The pipework s maximum operation pressure is 1.0 MPa.
The active chilled beam has a measurement tap to allow air flow measurement.

Active chilled beams are protected by a removable plastic coating.
The duct connection and pipe ends remain sealed during transport.
The active chilled beams are identified by labels attached to both the active chilled beam and the plastic packaging.

Order Code

R6B-S-L, LD-TC-CO-ZT

S = Nozzle type
       A      Bi-directional/ Nozzle 1
       B      Bi-directional/ Nozzle 2
       C      Bi-directional/ Nozzle 3
       D      Bi-directional/ Nozzle 4
       E      Bi-directional/ Nozzle 5

L = Total length
      1200, 1800, 2400, 3000
 

Other options and accessories 

LD = Duct connection / Duct size / Damper
        
L2N    Left / 125 / Without damper

TC = Cooling / Heating functions (Coil type)
         
C       Cooling
          H       Cooling and Heating

CO = Colour
          W     White (RAL 9010/20% gloss)

ZT = Tailored product
         N       No
         Y       Yes
 

 Code example

          R6B-A-3000 , LD=L2N,TC=C,CO=W, ZT=N

Downloads & Media

Halton Rex 600 Basic - se
Type
Datasheet
Taal
Zweeds (Zweden)
Grote
359,6 kB
Halton Rex 600 Basic - uk
Type
Datasheet
Taal
Engels (Verenigd Koninkrijk)
Grote
360,2 kB
Halton Rex 600 Basic - R6B - fr
Type
Datasheet
Taal
Frans (Frankrijk)
Grote
1,8 MB
Eurovent beams 2017-2018
Type
Certificaat
Taal
Engels (Verenigd Koninkrijk)
Grote
1,8 MB