Skip to content
Circular fire damper
Circular fire damper

Halton Exe Competent Circular (ECC) – Fire damper (EI 60 S)

This CE marked fire damper needs minimum free space around the body in case of installation. It is suitable for both vertical and horizontal installation in concrete, masonry and lightweight structures. Fire resistance class is provided up to EI 60 S requirements.

  • Vertical (wall) or horizontal (ceiling/floor) installation
  • Frame construction is galvanised steel as standard. Stainless steel option available on request.
  • Data
  • Downloads
  • Request a quote

Overview

This fire damper needs minimum free space around the body in case of installation. It is suitable for both vertical and horizontal installation in concrete, masonry and lightweight structures. Fire resistance class is provided up to EI 60 S requirements.

Features

  • Supplied with electrical spring return actuator (24 V or 230 V)
  • Sizes from Ø100 mm up to 400 mm are available
  • Maximum air velocity through fire damper in open position is 12 m/s
  • Suitable for use in ducts with a maximum pressure difference of 1200 Pa
  • Frame construction is galvanised steel as standard. Stainless steel option available on request.
  • No spare parts or additional installation frames needed, regardless of installation method

Installation options

  • Suitable for vertical (wall) or horizontal (ceiling/floor) installation
  • Spindle of the blade and the operating model (electric actuator) can be installed in any position (360°) in wall installation
  • CE marked for installation in concrete, masonry or lightweight structure with fire resistance class of EI 60

Standards

This product complies with the following standards:

  • CE certified according to product standard EN 15650
  • Fire classification according to EN 13501-3+A1 standard
    EI 60 (ve ho i↔o) S
  • Fire testing according to EN 1366-2
  • CE certificate of Constancy of Performance 1391-CPR-2018/0203
  • Declaration of Performance No:10026-ECC-2019/01/01
  • Leakage through closed damper blade fulfils class 3 (Ø200-400) and class 1 (Ø100-160) according to EN 1751
  • Damper casing tightness class C according to EN 1751
  • Corrosion resistance: Salt mist test EN 60068-2-52