ULC - Valve

Circular supply valve
Aesthetic in design and easy to adjust.
- Supply air valve.
- Ceiling installation.
- Adjustable airflow rate and flow pattern.
- Ability to measure airflow rate.
- Installation without installation frame / with a separate installation frame.
Supply air valve has a detachable front plate and collar made of painted steel with a white (RAL 9010) standard colour.
The collar has a screw fastening and incorporate a sealing gasket.
Supply airflow is directed by angling the front plate. Throw length is adjusted by rotating the front plate. Pressure loss is selected at the same time as the throw length adjustment and balancing.
- Dimensions
- Material and finíshing
- Function
- Installation
- Adjustment
- Servicing
- Specification
- Order Code
Halton ULC
Circular supply valve
- Supply air valve.
- Ceiling installation.
- Adjustable airflow rate.
- Ability to measure airflow rate.
- Installation without installation frame / with a separate installation frame.
Dimensions ▲
NS | ØD | ØW | H | H1 | B |
100 | 96 | 165 | 63 | 49 | 14 |
125 | 123 | 192 | 63 | 49 | 14 |
Material and finíshing ▲
Part | Material | Note |
Collar | Steel | |
Front plate | Steel | |
Fixing bar | Aluminium | |
Gasket | Rubber combound | |
Finishing | Painted white (RAL 9010) | Special colour available |
Function ▲
The supply airflow (radial jet) of Halton ULC is directed as required by angling the front plate. The throw length and pressur drop are adjusted by turning the front plate open or closed.
Installation ▲
Halton ULC is installed into the duct with finger screws from inside the valve. The front plate is mounted and the correct adjustment position selected. When the adjustment has been made, lock the front plate.
Adjustment ▲
Adjustment position (A) is determined by angling the fronty plate. The volume frlow rate is determined by setting a probe inside the devicev and reading the pressure difference between the probe and room.
The airflow rate for Halton ULC is calculated with the formula:
ULC-100 | ULC-125 | ||
A | k | A | k |
3 | 0.75 | 4 | 1,34 |
4 | 1,11 | 6 | 1,98 |
5 | 1,56 | 8 | 2,71 |
6 | 1,90 | 10 | 3,40 |
8 | 2,32 | 12 | 4,01 |
10 | 2,77 | 14 | 4,43 |
11 | 3,16 | 16 | 4,69 |
12 | 3,53 | 18 | 5,01 |
13 | 3,88 | 20 | 5,49 |
When the adjustment has been made, lock the front panel. Finally direct the suitable flow pattern.
Servicing ▲
Code description
1. Front plate
2. Fixing screw
3. Collar
For cleaning check first the adjustment position and detach the front panel from the collar. Remove the collar by loosening the fixing screws and clean the components with damp cloth. They must not be immersed in water.
Reassemby the valve in reverse order.
Specification ▲
Supply air valve has a detachable front plate and collar made of painted steel with a white (RAL 9010) standard colour.
The collar has a screw fastening and incorporate a sealing gasket.
Supply airflow is directed by angling the front plate. Throw length is adjusted by rotating the front plate. Pressure loss is selected at the same time as the throw length adjustment and balancing.
Order Code ▲
ULC-D; D-ZT
D = Connection size
100, 125
Other options and Accessories
CO = Colour
W White (RAL 9010)
X Special colour
ZT = Tailored product
N No
Y Yes
Code example
ULC-100, CO=W, ZT=N
Downloads & Media
Halton ULC - fi | 类型 技术参数 | 语言 芬兰文 (芬兰) | 尺寸 356.9 kB |
Halton ULC - se | 类型 技术参数 | 语言 瑞典文 (瑞典) | 尺寸 218.8 kB |
Halton ULC - fr | 类型 技术参数 | 语言 法文 (法国) | 尺寸 402.9 kB |
Halton ULC - uk | 类型 技术参数 | 语言 英文 (英国) | 尺寸 394.7 kB |