Skip to content

Product / FDL

FDL A0(A60) 防火阀

浩盾 FDL 防火阀是具有型式认证的 A0(A60) 级防火阀,广泛适用于钻井平台,船舶和舰艇上的通风系统。

Request a Quote

概述

  • 获得各类著名船级社的型式认可:A0 级无绝缘,A15-A60 适当绝缘
  • 可进行 ATEX 认证。通过冲击测试。
  • 焊连的外框和组装的风叶可选材质为喷漆、镀锌或不锈钢。免维护的不锈钢轴套和转轴。
  • 不带密封的风叶
  • 标称熔断温度为 50 ºC、74 ºC 或 100 ºC。可选其它温度。
  • 可以安装在任何位置
  • 自动、气动或手动执行器可选
  • 阀门结构可适应的最大管道压力为 5000 Pa,最大空气流速为 15 m/s。如果管道压力过高,请联系浩盾船舶寻求最佳解决方案。
  • 特定风闸可提供SIL 2安全认证

Dimensions

The Halton FDL fire dampers are manufactured according to international standards for both rectangular (width B 100-1300 mm and height H 100-1200 mm, 1 mm division) and circular ducts (Ø100-1250 mm). Modular constructions are available for bigger sizes. Non-standard dimensions and flange drilling are available on request.
Standard flange width 27 mm. Flanges and drilling also available according to ISO 15138 standards.
Blades are made of two sheets, each of them being 1 mm thick (sandwich design).

Modular construction sizes up to 2660×2460 mm.

Frame material thickness 3 mm or 3-5 mm according to SOLAS.

Frame thickness according to SOLAS

DIMENSIONS S
If B or H > 100, but < 449 3
If B or H > 450 but < 649 4
If B or H > 650 5

Frame thickness according to SOLAS, Edition Dec. 2015

DIMENSIONS S
If A < 0.075 m2 3
If A > 0.075 and A < 0.45 m2 4
If A > 0.45 m2 5

Actuator effect in dimensions

ACTUATOR R A
Electrical (EL) BF230, BF24, BF120 100 H<300 = 300, H>300 =H
Pneumatic (PNR) Pneumatic rotating actuator AT100 170 H<300 = 300, H>300 =H
Pneumatic (PNR) Pneumatic rotating actuator AT200 190 H<350 = 350, H>350 =H
Spring (SP) Spring 140 H

The above table contains only some examples of actuators and their effect on dimensions.

FDL, general drawings

With circular connections

FDL, top


FDL circular, with connection flanges

DAMPER HEIGHT H TOTAL DEPTH WITH BLADES OPEN
< 250 mm 212 mm
> 250 mm <300 mm 250 mm
 > 300 mm <350 mm 212 mm
 > 350 mm 240mm

Material and Finishing

PART MATERIAL FINISHING
Frame Carbon steel Painted or galvanized
Frame Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L)  –
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L)  –
Maintenance-free
bearings
Stainless steel EN 1.4404 (AISI316L)  –
Shafts Stainless steel EN 1.4404 (AISI316L)  –

Standard frame material thickness 3-5 mm according to SOLAS.

Product Models and Accessories

Halton FDL is available with following actuators:

  • FDL-EL: Electrical spring return motor; standard actuators being 24 V or 230 V or 120 V. The motor contains built-in open-closed limit switches. Separate junction box included in the EL-model. A wide range of Ex actuators available, including a one second closing time function as an option.
  • FDL-PNR: Pneumatic rotating actuator.
  • FDL-SP: Manual spring-actuated damper with fusible link.

DOT: manual override function available for PNR and EL models.

HSO: Halton Smart Override function for HVAC damper black-start available for PNR and EL models. With automatic reset function when power and/or pneumatic air supply is reinstated.

A wide range of accessories available.

Operation Principles

In the event of a temperature rise in ductwork:

  •  FDL-EL: fusible link releases and cuts off operating voltage to the spring return motor, allowing the spring to close the damper blades. The fire damper opens automatically when the fuse has been changed and the operating voltage to the motor is re-established.
  • FDL-PNR: fusible link releases and cuts off operating pressure to the spring return actuator, allowing springs to close the damper blades. The fire damper opens automatically when the fuse has been changed and the pneumatic air supply is re-established.
  • FDL-SP: fusible link releases allowing the spring to close the damper blades. When the fuse has been changed, the fire damper must be reset into open position manually.

Weights

Weight of standard Halton Marine FDL dampers without an actuator (kg)

H/HEIGHT
(mm)
 B / WIDTH (mm)
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
100 5 (5) 7 (7) 9 (9) 10 (10) 12 (13) 14 (15) 15 (22) 17 (25) 19 (27) 20 (30) 22 (32) 24 (35) 25 (37)
200 7 (7) 9 (9) 11 (11) 12 (12) 14 (16) 16 (18) 18 (26) 20 (28) 22 (31) 23 (34) 25 (36) 27 (39) 29 (41)
300 9 (9) 11 (11) 13 (13) 15 (15) 17 (19) 19 (21) 21 (30) 23 (32) 25 (35) 27 (38) 29 (41) 31 (43) 33 (46)
400 11 (11) 13 (13) 15 (15) 17 (17) 20 (22) 22 (24) 24 (33) 26 (36) 28 (39) 30 (42) 32 (45) 34 (48) 37 (51)
500 13 (16) 16 (19) 18 (22) 21 (25) 23 (27) 25 (30) 28 (38) 30 (41) 32 (44) 35 (47) 37 (50) 39 (54) 42 (57)
600 15 (18) 18 (21) 20 (24) 23 (27) 25 (30) 28 (33) 30 (41) 33 (45) 35 (48) 38 (51) 40 (55) 43 (58) 46 (61)
700 18 (25) 21 (28) 23 (32) 26 (35) 29 (39) 32 (42) 34 (46) 37 (50) 40 (53) 42 (57) 45 (60) 48 (64) 51 (67)
800 20 (27) 23 (31) 25 (35) 28 (38) 31 (42) 34 (46) 37 (50) 40 (53) 43 (57) 46 (61) 49 (64) 51 (68) 54 (72)
900 22 (31) 25 (35) 28 (39) 32 (42) 35 (46) 38 (50) 41 (54) 44 (58) 47 (62) 50 (66) 53 (70) 56 (74) 59 (78)
1000 24 (33) 27 (37) 31 (41) 34 (45) 37 (50) 40 (54) 44 (58) 47 (62) 50 (66) 53 (70) 57 (74) 60 (78) 63 (82)
1100 26 (36) 30 (41) 33 (45) 37 (49) 40 (54) 44 (58) 47 (62) 51 (67) 54 (71) 58 (75) 61 (79) 65 (84) 68 (88)
1200 28 (39) 32 (44) 36 (48) 39 (52) 43 (57) 46 (61) 50 (66) 54 (70) 57 (75) 61 (79) 65 (84) 68 (88) 72 (92)
D2 ØD WEIGHT
(mm) kg
100 8 (8)
125 8 (8)
160 12 (12)
200 13 (13)
250 19 (19)
315 20 (20)
400 27 (27)
500 35 (43)
630 46 (62)
800 62 (89)
1000 83 (118)
1250 113 (162)

(Frame thickness according to SOLAS)

Examples of actuator weights: FDL-EL BF230 +3,2 kg, BFN +1,4 kg, ExMax /Redmax +3,5 kg, CSQP +3 kg. FDL-PNR AT100 +2,1 kg, AT100 as AISI316 4,4 kg, AT200 +3,2kg, AT200 as AISI316 +6,2 kg, FDL-SP +1 kg. Control enclosure +4 kg.

Installation

Installation and maintenance instructions are with each fire damper delivery. Copies of Operation and Maintenance manuals are available from Halton Marine Sales offices and distributors.

Product Code

(S)=Shape of Connection
(A) Circular (D1)
(C ) Circular (D2)
(R) Rectangular
(W)=Width
100-1300
(H)=Height
100-1200
(D)=Diameter
100-1250
(FA)=Fire Approval
(C1) ABS American Bureau of Shipping
(C2) MED Marine Equipment Directive
(C3) LRS Lloyds Register
(C4) DNV Det Norske Veritas
(C5) BV Bureau Veritas
(C6) GL Germanischer Lloyds
(C7) USCG United States Cost Guard
(C9) RMRS Russian Maritime Register
(SF)=Flange Option
(H0) Connection flange in circular connections
(H1) Connection + loose flange in circular connections
(HA) Flanges (2 sides)
(HB) Counter flanges (2 sides)
(HC) Counter flange (1 side)
(NA) Not Assigned (circular connection)
(FS)=Frame dimensioning
(HS) Halton Standard dimensioning
(S0) SOLAS dimensioning
(MA)=Material
(AS) Stainless steel (1.0) EN1.4404
(CS) Carbon steel (1.0)
(LS) Stainless steel (1.0) EN1.4432
(SS) Stainless steel (1.0) EN1.4301
(FM)=Frame Material
(A3) Stainless steel (3.0) EN1.4404
(A4) Stainless steel (4.0) EN1.4404
(A5) Stainless steel (5.0) EN1.4404
(C3) Carbon steel (3.0) EN1.4404
(C4) Carbon steel (4.0) EN1.4404
(C5) Carbon steel (5.0) EN1.4404
(L3) Stainless steel (3.0) EN1.4432
(L4) Stainless steel (4.0) EN1.4432
(L5) Stainless steel (5.0) EN1.4432
(S3) Stainless steel (3.0) EN1.4301
(S4) Stainless steel (4.0) EN1.4301
(S5) Stainless steel (5.0) EN1.4301
(FI)=Finishing
(HG) Hot galvanized
(NA) Not Assigned (acid treatment)
(PN) Painting
(RE)=Actuator
(E1) Electric BF24-2-HL
(E3) Electric BF230-2-HL
(E7) Electric BF120-HL
(K0) Electric BFN24.1
(K1) Electric BFN24-T.1
(K2) Electric BFN230.1
(K3) Electric BFN230-T.1
(I1) InMax 15-SF
(P0) Pneumatic – Air Torque, AT101, Aluminium
(P1) Pneumatic Lin Roder 245N
(P2) Pneumatic Lin Roder 300N
(P3) Pneumatic – Air Torque, AT104, AISI316
(Q1) Pneumatic – Air Torque, AT201, Aluminium
(Q2) Pneumatic – Air Torque, AT204, AISI316
(R2) Ex-proofed RedMax 15-SF
(S1) Spring
(T1) Electric BF24-T-2.1HL
(T3) Electric BF230-T-2.1HL
(Z2) Ex-proofed ExMax 15-SF
(Z3) Ex-proofed ExMax 5-10SF
(C1) Electric CSQP-05A1E 24V
(C2) Electric CSQP-05A2E 120/230V
(C3) Electric CSQP-10A1E 24V
(C4) Electric CSQP-10A2E 120/230V
(C5) Electric CSQP-15A1E 24V
(C6) Electric CSQP-14A2E 120/230V
(FU)=Fuse
144 °C
100 °C
95 °C
74 °C
72 °C
70 °C
65 °C
50 °C
(AC)=Accessories
(BC) Belimo Casing
(E1) Junction box IP66/67 (Plastic) (Ensto)
(E2) EX junction box IP66/T6 (GRP) (Ensto)
(E4) Connectors (FD) (Wieland & Hensel))
(L1) Limit switch 1 pcs IP66 (Plastic) (Bernstein)
(L2) Limit switch 2 pcs IP66 (Plastic) (Bernstein)
(L3) EX Limit switch 1 pcs (Plastic) (Bartec)
(L4) EX Limit switch 2 pcs (Plastic) (Bartec)
(M1) Solenoid valve 24 VDC (Aluminium)  (SMC)
(M2) Solenoid valve 230 VAC (Aluminium) (SMC)
(M3) EX solenoid valve 24 VDC (Brass) (Norgren)
(M4) EX solenoid valve 230 VAC (SS) (Norgren)
(P1) Pneumatic valve manual (Aluminum) (SMC)
(S3) SN2 auxiliary switch (Belimo)
Stainless steel tubing (AISI316) ( Halton)
(ED) DOT handle (manual overdrive) (Steel) (Halton)
Code example
FD3/R-1300-1200,FA=C1,SF=HA,FS=SO,MA=CS,FM=C5,FI=HG,RE=Z2,FU=50,ZT=N,AC=E2

Downloads

  • FDL – A0(A60) Fire damper

    Data

    en

    Shape 2
  • FDL – A0(A60) Palopelti

    Data

    fi

    Shape 2
  • FDL – A0(A60) Fire damper

    Data

    fr

    Shape 2
  • FDL A0(A60) 防火阀

    Data

    cn

    Shape 2
  • Halton FDL datasheet 2022

    Data

    English
    Shape 2
  • ABS Certificate for Halton FDL

    Data

    English
    Shape 2
  • ATEX Certificare for FDB2, FEX, FDL, FDO, FDA

    Data

    English
    Shape 2
  • DNV GL Certificate for Halton FDL

    Data

    English
    Shape 2
  • LR Certificate of Fire Approval for Halton FDL

    Data

    English
    Shape 2
  • MED BV Certificate for FDL

    Data

    English
    Shape 2
  • RMRS Certificate for Halton FDL

    Data

    Русский (ru)
    Shape 2
  • TR CU – SAFE Certificate for Halton FDB2, FDL, FEX, UTG, UTX, UTP, UTN, UTT, BLD, BRD