Halton Rex RXP - Chilled beam (CAV/VAV)

More info
Product page
Product image
Room Normal
Room temperature [°C]
14 50
Temperature near ceiling [°C]
Relative humidity [%]
1 100
Air Normal
Supply air temperature [°C]
8 60
Total pressure drop [Pa]
Static chamber pressure [Pa]
50 150
Airflow [l/s]
2.7 51.6
Velocity control (HVC)
Water Normal
Inlet water temperature [°C]
14 25
Water mass flow rate [kg/s]
Outlet water temperature [°C]
0.02 0.1
Unit performanceNormal
Total capacity [W]64
Primary air capacity [W]23
Coil capacity [W]41
Dew point temperature [°C]13.8
Static chamber pressure [Pa]80
Water pressure drop [kPa]3.4
Air quality control (HAQ) opening [mm]0.5
Outlet water temperature [°C]15.2
Sound pressure level [dB(A)]27
Nozzle jet temperature [°C]20.1
Lp10A [dB] airNR Sound power level, Lw [dB] by octave band
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
27 232920303126221211