Skip to content

Product / FCE

FCE – Clapet coupe-feu (EI 60 S)

Halton FCE fire dampers are CE-marked according EN 15650:2010 and tested according to EN 1366-2 standard. Halton FCE fire dampers are used as safety-related components in ventilation systems to prevent fire and smoke spreading through ducting.

Request a Quote

Overview

  • Certified by Centrum Techniki Okretowej S.A.
  • Automatic electrical operation system
  • Blades contain silicone seals (effective up to 300 ºC) for low leakage in normal conditions and thermal expansion graphite seals (effective from 150 ºC) to increase tightness in a case of fire
  • Blades contain ceramic wool insulation or calcium silicate fire protective board depending on fire resistance class
  • Low weight due to double skin blade structure
  • Closed blade leakage to EN 1751, Class 3 size >=200×200
  • Casing leakage to EN 1751, Class C
  • Maximum duct pressure for damper construction 5000 Pa (3mm casing), 3000 Pa (1mm casing) and maximum air velocity 15 m/s
  • Normal operation temperature for damper between  -30 ºC to +50 ºC. Actuator and component selection can have an effect on this temperature range. Other temperatures available on request
  • Option of circular connection
  • Available as ATEX certified
  • SIL 2 safety assessment certificate available for the damper on specific terms

Specification

Halton FCE fire dampers are CE-marked according EN 15650:2010 and tested according to EN 1366-2 standard. Halton FCE fire dampers are used as safety-related components in ventilation systems to prevent fire and smoke spreading through ducting.
The FCE fire damper can be installed in rectangular ducts in solid walls, ceilings and lightweight partition wall. During normal operation, the fire damper is in the open position and does not cause significant pressure loss, noise or flow disturbance.

Dimensions and Material Thickness

The FCE fire dampers meet international standards for both rectangular (width B 150-1000 mm with 25 mm division and height H 150-1000 mm with 50 mm division) and circular ducts (Ø100-1000 mm).
Standard flanges height 50 mm and drilling according to ISO 15138 standards. Frame thickness 1 mm to 3 mm. Blades are made of two sheets, each of being 1 mm thick (sandwich design).

DIMENSIONS ØC F P1 P2 BM
If longest side < 350 10 50 75…150 75…150 20
If longest side 351…1000 12 50 75…150 75…150 30
ACTUATOR T T (external limit switch)
Belimo BF 112 163
Schischek BF 132 184
QT.EX_MFD 95 197

Fire classification according to EN 13501-3

EI 60 (ve ho i ↔ o ) S
E 120 (ve ho i ↔ o ) S
E: Integrity (against flames & hot gases)
I: Insulation (against heat)
S: Smoke leakage (against gases & smoke)
ve: Vertical installation
ho: Horizontal installation
i ↔ o: Fire direction, outside & inside duct
60 Minutes integrity and insulation
120 Minutes integrity

FCE leakage in fire conditions

Test pressure 300 Pa. Damper size 1000×1000 mm. Test according to EN 1366-2.

FCE, general drawings

Drawings of FCE CE-marked fire damper

Material and Finishing

PART MATERIAL FINISHING
Frame Carbon steel (3 mm)
Steel (1 mm)
Hot-dip galvanized / ISO 1464
Z275 / EN 10346:2015
Frame Stainless steel
EN 1.4301 (AISI304),
EN 1.4404 (AISI316),
EN 1.4432 (AISI316L)
(3 mm) Pickling /
(1 mm) N/A
Blades Steel Z275 / EN 10346:2015
Blades Stainless steel
EN 1.4301 (AISI304),
EN 1.4404 (AISI316),
EN 1.4432 (AISI316L)
Blade insulation Calcium silicate (EI 60 S)
Ceramic wool (E 120 S)
Maintenance-free bearings Oil bronze  –
Bearings EN 1.4404 (AISI316)
(Available as an option)
Shafts Stainless steel
EN 1.4404 (AISI316)
 –

Product Models and Accessories

Halton FCE is available with following actuators:

  • FCE-EL: Electrical spring return motor; standard actuators being 24 V to 230 V. The motor contains built-in open-closed limit switches. Separate junction box included in the EL-model. A wide range of Ex actuators available.

HSO: Halton Smart Override function for HVAC damper black-start available. With automatic reset function when power is reinstated.

A wide range of accessories available.

Operation principles

If temperature increases (≥72°C) in case of fire or hot gases the damper blade closes automatically. Alternatively, the FCE damper may be released by a local switch or common building automation system.

Weights

Weights according to fire resistance class ES 120

Standard Halton Marine FCE dampers (kg), without an actuator, frame thickness 1 mm

H/Height 

(mm)

 B/Width (mm)
150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150 7 7 8 9 10 11 11 12 13 14 15 16 16 17 18 19 20 21
200 7 8 9 10 11 11 12 13 14 15 16 17 17 18 19 20 21 22
250 8 9 10 11 11 12 13 14 15 16 17 17 18 19 20 21 22 22
300 10 11 12 13 14 15 16 18 19 20 21 22 23 24 25 26 27 28
350 11 12 13 14 15 16 18 19 20 21 22 23 24 25 26 27 28 29
400 12 13 14 15 17 18 19 20 21 22 23 24 25 26 27 28 29 30
450 14 16 17 18 20 21 22 23 25 26 27 29 30 31 33 34 35 36
500 16 17 18 19 21 22 23 25 26 27 29 30 31 32 34 35 36 38
550 17 18 19 21 22 23 24 26 27 28 30 31 32 34 35 36 37 39
600 18 19 20 22 23 24 26 27 28 29 31 32 33 35 36 37 39 40
650 20 21 23 24 26 28 29 31 32 34 35 37 38 40 41 43 44 46
700 21 23 24 26 27 29 30 32 33 35 36 38 39 41 42 44 45 47
750 22 24 25 27 28 30 31 33 34 36 37 39 40 42 43 45 47 48
800 23 25 26 28 29 31 32 34 35 37 38 40 42 43 45 46 48 49
850 25 27 29 31 32 34 36 38 39 41 43 45 46 48 50 52 53 55
900 27 28 30 32 34 35 37 39 41 42 44 46 48 49 51 53 55 56
950 28 29 31 33 35 36 38 40 42 43 45 47 49 50 52 54 56 57
1000 29 30 32 34 36 37 39 41 43 44 46 48 50 51 53 55 57 58

Standard Halton Marine FCE dampers (kg), without an actuator, frame thickness 3 mm

H/Height 

(mm)

 B/Width (mm)
150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150 12 12 14 15 16 18 19 20 21 22 23 25 26 27 28 29 31 32
200 12 14 15 16 17 19 20 21 22 24 25 26 27 28 29 31 32 33
250 14 15 16 17 18 20 21 22 24 25 26 27 28 29 31 32 33 34
300 16 17 19 20 22 23 25 26 28 29 30 32 33 35 36 37 39 40
350 17 19 20 22 23 25 26 28 29 30 32 33 35 36 38 39 40 42
400 19 20 22 23 24 26 28 29 31 32 33 35 36 38 39 40 42 43
450 22 23 25 27 28 30 32 33 35 36 38 40 41 43 45 46 48 50
500 23 25 26 28 30 31 33 35 36 38 40 41 43 44 46 48 49 51
550 25 26 28 30 31 33 34 36 38 39 41 43 44 46 48 49 51 52
600 26 28 29 31 33 34 36 38 39 41 42 44 46 47 49 51 52 54
650 29 30 32 34 36 38 40 42 43 45 47 49 51 53 55 56 58 60
700 30 32 34 36 37 39 41 43 45 47 49 51 52 54 56 58 60 62
750 32 33 35 37 39 41 43 45 46 48 50 52 54 56 58 59 61 63
800 33 35 37 39 40 42 44 46 48 50 52 53 55 57 59 61 63 65
850 35 38 40 42 44 46 48 50 52 54 56 58 60 63 65 67 69 71
900 37 39 41 43 45 47 49 51 54 56 58 60 62 64 66 68 70 72
950 38 40 43 45 47 49 51 53 55 57 59 61 63 65 68 70 72 74
1000 40 42 44 46 48 50 52 54 56 59 61 63 65 67 69 71 73 75
ACTUATOR OPTIONS CLOSING TIME MATERIAL WEIGHT (APPR.)
Ex/InMax-BF 3/10 seconds Aluminium 3,5 kg
Ex/InMax-BF 3/10 seconds Stainless steel 7,0 kg
QT.Ex-MFD 3 seconds High Tech Polymer 4,1 kg
BF230-T 16 seconds Steel 3,1 kg
BF24-T 16 seconds Steel 2,8 kg

Weights according to fire resistance class EI 60 S

Standard Halton Marine FCE dampers (kg), without an actuator, frame thickness 1 mm

H/Height 

(mm)

 B/Width (mm)
150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150 7 8 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
200 8 9 10 11 11 12 13 14 15 16 17 18 19 20 21 22 23 24
250 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
300 11 12 13 14 16 17 18 19 21 22 23 25 26 27 28 30 31 32
350 12 13 14 16 17 18 20 21 22 24 25 26 27 29 30 31 33 34
400 13 14 16 17 18 20 21 22 24 25 26 28 29 30 32 33 34 36
450 15 17 18 20 22 23 25 26 28 30 31 33 34 36 38 39 41 42
500 16 18 20 21 23 25 26 28 29 31 33 34 36 38 39 41 42 44
550 18 19 21 23 24 26 28 29 31 33 34 36 38 39 41 43 44 46
600 19 21 22 24 26 27 29 31 32 34 36 38 39 41 43 44 46 48
650 21 23 25 27 29 31 33 35 37 39 41 43 45 47 48 50 52 54
700 22 24 26 28 30 32 34 36 38 40 42 44 48 49 50 52 54 56
750 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58
800 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 56 58 60
850 27 29 32 34 36 39 41 43 46 48 50 52 55 57 59 62 64 66
900 28 31 33 35 38 40 42 45 47 49 52 54 56 59 61 63 66 68
950 29 32 34 37 39 41 44 46 48 51 53 56 58 60 63 65 67 70
1000 31 33 36 38 40 43 45 48 50 52 55 57 60 62 64 67 69 72

Standard Halton Marine FCE dampers (kg), without an actuator, frame thickness 3 mm

H/Height 

(mm)

 B/Width (mm)
150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
150 12 13 14 15 17 18 20 21 22 23 25 26 27 29 30 31 32 34
200 13 14 15 17 18 20 21 22 24 25 26 28 29 30 32 33 34 36
250 14 15 17 18 19 21 23 24 25 27 28 29 31 32 33 35 36 37
300 16 18 20 21 23 25 27 28 30 31 33 35 36 38 39 41 43 44
350 18 20 21 23 25 27 28 30 32 33 35 37 38 40 41 43 45 46
400 20 21 23 25 26 28 30 32 33 35 37 38 40 42 43 45 47 48
450 23 25 26 28 30 32 34 36 38 40 42 44 46 48 50 52 53 55
500 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58
550 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
600 27 29 31 33 35 37 39 41 43 46 48 50 52 54 56 58 60 62
650 30 32 34 37 39 41 44 46 48 50 53 55 57 60 62 64 66 69
700 31 34 36 38 41 43 45 48 50 52 56 57 59 62 64 66 68 71
750 33 35 38 40 42 45 47 49 52 54 56 59 61 63 66 68 71 73
800 35 37 39 42 44 46 49 51 54 56 58 61 63 65 68 70 73 75
850 37 40 42 45 48 50 53 56 58 61 63 66 69 71 74 77 79 82
900 39 41 44 47 49 52 55 57 60 63 65 68 71 73 76 79 81 84
950 40 43 46 48 51 54 56 59 62 65 67 70 73 75 78 81 83 86
1000 42 44 47 50 53 55 58 61 64 66 69 72 75 77 80 83 86 88
ACTUATOR OPTIONS CLOSING TIME MATERIAL WEIGHT (APPR.)
Ex/InMax-BF 3/10 seconds Aluminium 3,5 kg
Ex/InMax-BF 3/10 seconds Stainless steel 7,0 kg
QT.Ex-MFD 3 seconds High Tech Polymer 4,1 kg
BF230-T 16 seconds Steel 3,1 kg
BF24-T 16 seconds Steel 2,8 kg

Installation

The FCE fire damper can be installed into rectangular HVAC ducts that penetrate solid or lightweight partition walls and ceilings. The damper ease of installation on-site makes it an ideal choice compared to other fire dampers. The damper is installed 75-1000 mm away from the wall by using a fire-rated duct. This installation method follows the requirements of the above-mentioned standards and therefore the final damper arrangement provides a fully compliant installation.

Note regarding wall installation

At wall installation the blade orientation must always be in horizontal plane.

Product Code

Downloads

  • FCE – Fire damper (EI 60 S)

    Data

    en

    Shape 2
  • FCE Palopelti (EI 60 S)

    Data

    fi

    Shape 2
  • FCE – Clapet coupe-feu (EI 60 S)

    Data

    fr

    Shape 2
  • FCE – Brandschutzklappe (EI 60 S)

    Data

    de

    Shape 2
  • Halton FCE datasheet 2022

    Data

    English
    Shape 2
  • ATEX Certificate for Halton FCE and FDH

    Data

    English
    Shape 2
  • Construction Product Regulation (CPR) – FCE

    Data

    English
    Shape 2
  • Declaration of Performance (DoP) – FCE

    Data

    English
    Shape 2
  • EAC Certificate for Halton FDA, FDB2, FDO, FDH, FCE, UTA, UTG, BDH, BRD, BLD

    Data

    Русский (ru)
    Shape 2
  • SIL 2 Safety Assessment Certificate

    Data

    English
    Shape 2
Contact Us
  • Hidden
  • Max. file size: 64 MB.