Skip to content
FCE - Fire damper (EI 60 S)
FCE - Fire damper (EI 60 S)

FCE – Fire damper (EI 60 S)

Halton FCE fire dampers are CE-marked according EN 15650:2010 and tested according to EN 1366-2 standard. Halton FCE fire dampers are used as safety-related components in ventilation systems to prevent fire and smoke spreading through ducting.

  • Data
  • PDF
  • Downloads
  • Request a quote

Overview

  • Certified by Centrum Techniki Okretowej S.A.
  • Automatic electrical operation system
  • Blades contain silicone seals (effective up to 300 ºC) for low leakage in normal conditions and thermal expansion graphite seals (effective from 150 ºC) to increase tightness in a case of fire
  • Blades contain ceramic wool insulation or calcium silicate fire protective board depending on fire resistance class
  • Low weight due to double skin blade structure
  • Closed blade leakage to EN 1751, Class 3 size >=200×200
  • Casing leakage to EN 1751, Class C
  • Maximum duct pressure for damper construction 5000 Pa (3mm casing), 3000 Pa (1mm casing) and maximum air velocity 15 m/s
  • Normal operation temperature for damper between  -30 ºC to +50 ºC. Actuator and component selection can have an effect on this temperature range. Other temperatures available on request
  • Option of circular connection
  • Available as ATEX certified