Skip to content

Product / DWI

Halton Windis DWI – Air curtain

Halton Windis DWI is a compact and compatible air curtain for various entrance types. It is designed for horizontal installation and has a maximum height of 3.5m. Its standout feature is the intelligent control system, which simplifies the configuration of the air curtain settings. Delivers high performance and highly energy efficiency with built-in integrated energy measurement using ultrasound technology.

  • It is fast and easy to install, with no need to open the product for connection.
  • Features recessed mounting and water heating capabilities.
  • Connectivity to automation is simple, facilitated by a QR code.
  • Equipped with built-in thermal energy measurement.
  • Includes an intelligent controller with seamless control and monitoring of the air curtain settings
  • Allows adjustable impulse force giving you control over its performance.
  • Comes with integrated water valves.
Request a Quote

Overview

Halton Windis DWIis an air curtain that generates an invisible and uniformly controlled air stream directed downwards in an open doorway. It is a water-heated air curtain designed for integrated installation. It is compact and compatible with various entrance types, and installation is up to a maximum height of 3.5 m. With its integrated energy measurement, energy consumption remains under control. The unit employs EC motors and features with adjustable impulse force for an efficient air barrier function.

Application area

  • Excellent for retail spaces, shops, offices, schools, and daycares.
  • Interior or exterior doorways.
  • Designed for horizontal installation directly above door openings with a maximum height of 3.5 m.

Key features

  • Fast and easy to install, it requires no opening of the product for connection.
  • Suspended mounting and water-heated.​
  • Connectivity to automation is simple via a QR code.
  • Built-in thermal energy measurement.
  • ​Intelligent Controller - with web server and ready-to-use Modbus and BACnet interfaces.​
  • Adjustable
  • Integrated water valves.

Operating principle

Fig. 1. Halton Windis DWI, air curtain - Operating principle

Air curtains, distinguished by their unique aerodynamic design, offer a highly efficient solution for separating two temperature zones or two environments. This unique design not only provides effective separation but also contributes significantly to energy conservation, making it a cost-effective choice.

When faced with challenges of natural heat exchange through open doors, air curtains step in as a practical solution. These curtains effectively separate two areas or environments, halting the natural transfer of heat and thereby playing a crucial role in energy conservation.

In principle, an air curtain is a device equipped with a fan and a heat exchanger (water or electrical). It operates by pushing air to the floor in a smooth, laminar flow, creating a 90% air seal. This seal, akin to an invisible waterfall, effectively stops heat transfer, dust, and flying insects, thereby maintaining a controlled indoor environment.

Key technical data

Feature Description
Airflow rate 73-1404 l/s or 1750-3900 m3/h
Sound pressure level 30-77 dBa
Dimensions Height [H] = 600 mm
Width [W] = 1017, 1517, 2017, 2517 mm
Weight 46 - 95 kg
Adjustability / Positions 3
Mounting height 3.5 m (max)

Features and options

Feature Description
Color Frame: RAL 7035 Grille: RAL 7024
Casing Galvanised steel
Fans EC - motor, Ball bearings
Heat exchanger Copper (3/8"), aluminium, G1" thread, max 6 bar/100°C
Electrical connections Power supply 2 m, safety grounded plug
Other connections M12 connector, Ethernet, USB
Standard delivery 2-way heating valve, Heating energy meter, Filter G4, Room sensor NTC10
Internal temperature sensors
  • Water in and water out
  • Air in and air out
Cables 10 m cable - BMS - RS-485 connection (M12 connector)
10 m cable - Room sensor (M12 connector)
10 m cable - Door switch (M12 connector)
10 m cable - Slave device (M12 connector)

Product selection

Technical data (Air, volume and sound)

Halton Windis DWI, 1000

Regulation Air volume HVC Sound pressure level Power consumption
1 [l/s] [m 3 /h] Position [dB(A)] 10 m 2 sab [W]
10 531 1913 1 74 333
8 421 1516 1 69 175
6 290 1043 1 60 68
4 153 552 1 47 20
2 80 288 1 30 8
10 524 1885 2 74 333
8 402 1446 2 69 176
6 290 1043 2 61 68
4 152 546 2 47 20
2 74 266 2 30 8
10 524 1885 3 75 333
8 402 1446 3 69 175
6 287 1033 3 61 68
4 148 533 3 48 20
2 73 262 3 31 8

Halton Windis DWI, 1500

Regulation Air volume HVC Sound pressure level Power consumption
1 [l/s] [m 3 /h] Position [dB(A)] 10 m 2 sab [W]
10 766 2757 1 76 502
8 620 2232 1 71 268
6 444 1597 1 63 104
4 257 926 1 50 31
2 116 416 1 32 12
10 759 2733 2 77 503
8 595 2142 2 71 268
6 415 1496 2 63 104
4 241 867 2 49 31
2 113 408 2 32 12
10 725 2611 3 77 503
8 560 2016 3 71 268
6 398 1431 3 63 104
4 268 964 3 49 31
2 106 381 3 32 12

Halton Windis DWI, 2000

Regulation Air volume HVC Sound pressure level Power consumption
1 [l/s] [m 3 /h] Position [dB(A)] 10 m 2 sab [W]
10 1016 3656 1 77 666
8 871 3135 1 73 384
6 585 2105 1 64 149
4 336 1210 1 51 44
2 142 513 1 34 17
10 1016 3656 2 77 667
8 871 3135 2 73 383
6 565 2034 2 64 149
4 331 1192 2 51 44
2 135 485 2 34 17
10 1016 3656 3 78 667
8 841 3029 3 73 384
6 554 1993 3 65 149
4 324 1166 3 51 44
2 133 478 3 35 17

Halton Windis DWI, 2500

Regulation Air volume HVC Sound pressure level Power consumption
1 [l/s] [m 3 /h] Position [dB(A)] 10 m 2 sab [W]
10 1404 5055 1 77 665
8 1142 4112 1 72 355
6 811 2919 1 64 137
4 415 1496 1 51 41.9
2 231 831 1 34 17
10 1349 4857 2 78 665
8 1102 3966 2 73 355
6 772 2781 2 64 138
4 406 1460 2 51 41.9
2 220 792 2 35 17
10 1244 4478 3 78 665
8 990 3565 3 73 355
6 718 2585 3 64 138
4 381 1372 3 51 41.9
2 220 792 3 36 17

Structure and materials

Fig. 2. Halton Windis DWI, structure.
No. Part Description Note
1 Connector panel Plastic, steel PVC cable
2 Filter Aluminium -
3 EC-fan Metal -
4 Outlet grille Aluminium / Steel -
5 Intelligent controller - -

Dimensions and weight

Fig. 3. Halton Windis DWI - Dimensions
DWI L [mm] W [mm] H [mm] L1 [mm] Weight [kg]
1000 1017 250 550 432 46
1500 1517 250 550 432 60
2000 2017 250 550 432 79
2500 2517 250 550 432 95

Specification

The Halton Windis DWI is an air curtain designed for integrated installation. The system features integrated thermal energy measurement using precise ultrasound technology, a smart controller with a built-in web server and ready Modbus and BACnet interfaces, as well as an adjustable blowing impulse to tailor to specific needs.

Function

  • Four product models equipped with integrated controls eliminate the need for additional controls on the walls, allowing for a clean, streamlined design.​
  • Adjustable blowing speeds and an in-built schedule function for efficient management.
  • Includes programmatic freeze protection and a Master-Slave function for synchronised operation.
  • ​Integrated control valves and actuators, along with energy measurement, air bubble detection, and pressure measurement of the heating network.​
  • Featuring a counter for door openings enhances overall functionality.​
  • Supporting ECM engines allows optimized operation for each building.
  • Ready-to-implement graphic images simplify design processes.
  • Functional changes to easily adapt to specific needs.

Structure

  • Available in four different widths: 1000 mm, 1500 mm, 2000 mm, and 2500 mm.

Material

  • The frame is painted in light grey RAL 7035, and the grill is painted in graphite grey RAL 7024. The colours are customizable RAL xxxx.
  • ​The heating radiator system features 3/8" copper pipes with aluminium strips for enhanced heat dissipation and a G1" internal thread for secure connections. Designed to operate at a maximum pressure of 6 bar and a temperature of up to 100°C.
  • The electrical connections include a 2 m power supply with safety grounding, a spark plug, and additional interfaces like an M12 connector, Ethernet, and USB.​
  • The fan is equipped with centrifugal blades and ball bearings for efficient and reliable operation.
  • The system includes a 2-way heating valve, a heat energy meter, a G4 filter, an adjustable blow impulse, and supports Modbus TCP, BacNet TCP, Modbus RTU, BacNet MSTP, and an I/O interface for connectivity.

Integrated controller

  • The automation system of the door curtain unit provides significant advantages by ensuring all components are pre-tested and the control system operates as intended.
  • ​The pre-tested control system quickly adapts to changing conditions, optimising performance and energy efficiency in real-time.​
  • This advanced controller integrates seamlessly with building automation systems via Modbus or BACnet interfaces. Network topology options include TCP/IP or RS-485, ensuring flexible and robust communication.
  • ​It contains various integrated sensors for measuring air temperature, water-side energy meter, water pressure and freeze protection. Additionally, external sensors can be connected.​, external sensors can be connected.
  • The controller can be integrated into the BMS, allowing all control signals to be managed directly through the BMS, except for bypassing the freeze protection function.

Installation

Installation instructions, covering installation options, space requirements, wiring, and other installation requirements, are available in a separate document.

See Halton Windis DWI Installation, commissioning, operations and maintenance guide. Preparation is in progress, and will enable the link as soon as it becomes available.

Commissioning

The commissioning of both the central unit and the Controller is available in a separate document.

See Halton Windis DWI Installation, commissioning, operations and maintenance guide. Preparation is in progress, and will enable the link as soon as it becomes available.

Maintenance

The maintenance instructions are available in a separate document.

See Halton Windis DWI Installation, commissioning, operations and maintenance guide. Preparation is in progress, and will enable the link as soon as it becomes available.

Order code

DWI-M-L; VC-CO-ZT

Main options
M = Model
S Small
L = Length [mm] 1000, 1500, 2000, 2500
Other options and accessories
VC = Impulse force
1 Position 1
2 Position 2
3 Position 3
CO = Colour
TG Grey
x Special colour (RAL xxxx)
ZT = Tailored product
N No
Y Yes (ETO)
Order code example
DWI-S-1500; VC=2, CO=TG, ZT=N

Downloads

  • Halton Windis DWI – Air curtain

    Data

    en

    Shape 2
  • Halton Windis DWI – Technical description

    Data

    English (en)
    Shape 2
  • Halton Windis – Declaration of Conformity

    Data

    en
    Shape 2
Contact Us