Skip to content

Product /

CPR-01 Pressure Relief Damper

The CPR‑01 Pressure Relief Damper provides reliable pressure relief in demanding ventilation systems, maintaining controlled overpressure while combining robust construction with dependable operation across critical industrial applications and environments.

Request a Quote

Overview

The CPR‑01 Pressure Relief Damper is designed to provide reliable pressure relief performance and efficient operation under arduous conditions. It is intended for use in applications where controlled overpressure must be maintained, such as electrical equipment rooms, control rooms and living quarters, helping to prevent the ingress of hazardous gases. The robust construction ensures consistent performance and long service life. The damper is typically set to operate at a defined differential pressure and may be installed vertically or horizontally, with airflow in the upward direction, offering flexibility for a wide range of ductwork configurations.

Key Features

Casing

The damper casing is formed from 3.0 mm thick sheet steel into a rigid channel section to ensure proper alignment of blades and shafts. The CPR-01 is available as a single unit, maximum size 1200mm x 2000mm, or as a multiple unit assembly, maximum size 2500mm x 2000mm. The insertion length is 200mm. Where circular dampers are required, additional spigot adaptors are used.

Blades

The blades are a formed single skin of 1.5 mm sheet steel and operate with a parallel linkage. They seal against a flame-retardant PVC strip attached to the blades and top and bottom stops.

 

Materials

Part Material Finishing
Case Mild steel Galvanised
Case Stainless steel – 1.4307 (304L) –
Blades Mild steel Galvanised
Blades Stainless steel – 1.4307 (304L) –
Shafts Stainless steel – 1.4307 (304L) –
Bearings Phosphor bronze self-lubricated plain ‘Oilite’ –

Technical Specification

  • Low leakage
  • Vertical or horizontal installation
  • Minimal pressure drop
  • SIL 2 rated in accordance with IEC 61508-2:2010
  • Damper certified to ATEX Directive 2014/34/EU. Any fitted actuators, switches, junction boxes or accessories must be separately ATEX-certified for the required hazardous area
  • Operated by either spring or weighted adjustment unit

Installation

Dampers are typically provided with integral drilled flanges that allow for bolting to ductwork, structural divisions, wall sleeves and similar. Flanges and drillings can be to Halton standard or customer specification.

Installation and maintenance instructions are provided with each damper delivery.