Product / HSP
Overview
Halton Safe HSP is part of the Halton fire and smoke safety offering.
Transformer is used to provide power to Halton Safe Link units. One unit can provide power to six Halton Safe HSL link units.
The supply power (230 V AC) comes to the primary coil. The secondary coil feeds power (24 V AC) to Halton Safe HSL link units.
Note: Do not connect a device that does not have its own fuse to the 24 V AC side of a Halton Safe HSP power unit. It is recommended that the cables between Halton Safe HSP power units and Halton Safe HSL link units have a cross sectional area of at least 2.5 mm2.
Applications
- Controlling fire dampers and smoke detectors in buildings.
Key features
- Can provide power to six Halton Safe HSL link units
- Easy to install
Features and options
Feature | Description |
Primary coil | 230 V AC / 50-60 Hz |
Primary coil fuse | 2A glass tube fuse, 5×20 mm |
Secondary coil | 24 V AC |
Maximum power | 260 VA |
Structure and components
Fig.1. Structure of Halton Safe HSP
No. | Part | Details |
1 | 24 V AC terminals | Power connections for Halton Safe HSL link units |
2 | Transformer | 260 VA |
3 | Terminal for power supply | 230 V AC |
4 | 230 V AC fuse | 2 A |
Dimensions and weight
Fig.2. Dimensions of Halton Safe HSP
Weight:
2.8 kg
Specification
Power unit for fire dampers and smoke detectors in the Halton Safe Management 2.0 system.
- 230 V AC to 24 V AC transformer
- 260 VA power outlet
Installation information
Connection diagram
Fig.3. Connection diagram of Halton Safe HSP
Terminals
Outlet power |
|
Terminal | Comment |
24V | G, Terminals for supply voltage connection + (24 V) |
G0 | G0, Terminals for supply voltage connection – (24 V) |
Inlet power |
|
Terminal | Comment |
L | 230 V AC Line |
N | 230 V AC Neutral |
PE | Ground |
Order code
HSP; ZT