Skip to content

Product / HSP

Halton Safe HSP – Power unit

Transformer that is used to provide power to Halton Safe Link units. One unit can provide power to six Halton Safe HSL link units.

  • Controlling fire dampers and smoke detectors in buildings.
Request a Quote

Overview

Halton Safe HSP is part of the Halton fire and smoke safety offering.

Transformer is used to provide power to Halton Safe Link units. One unit can provide power to six Halton Safe HSL link units.

The supply power (230 V AC) comes to the primary coil. The secondary coil feeds power (24 V AC) to Halton Safe HSL link units.

Note: Do not connect a device that does not have its own fuse to the 24 V AC side of a Halton Safe HSP power unit. It is recommended that the cables between Halton Safe HSP power units and Halton Safe HSL link units have a cross sectional area of at least 2.5 mm2.

Applications

  • Controlling fire dampers and smoke detectors in buildings.

Key features

  • Can provide power to six Halton Safe HSL link units
  • Easy to install

Features and options

Feature Description
Primary coil 230 V AC / 50-60 Hz
Primary coil fuse 2A glass tube fuse, 5×20 mm
Secondary coil 24 V AC
Maximum power 260 VA

Structure and components

HSP_structure

Fig.1. Structure of Halton Safe HSP

No. Part Details
1 24 V AC terminals Power connections for Halton Safe HSL link units
2 Transformer 260 VA
3 Terminal for power supply 230 V AC
4 230 V AC fuse 2 A

Dimensions and weight

HSP_dimensions

Fig.2. Dimensions of Halton Safe HSP

Weight:

2.8 kg

Specification

Power unit for fire dampers and smoke detectors in the Halton Safe Management 2.0 system.

  • 230 V AC to 24 V AC transformer
  • 260 VA power outlet

Installation information

Connection diagram

HSP_connection_diagram

Fig.3. Connection diagram of  Halton Safe HSP

Terminals

Outlet power
Terminal Comment
24V G, Terminals for supply voltage connection + (24 V)
G0 G0, Terminals for supply voltage connection – (24 V)
Inlet power
Terminal Comment
L 230 V AC Line
N 230 V AC Neutral
PE Ground

Order code

HSP; ZT

ZT = Tailored product
N    No

Code example

HSD, ZT=N