Skip to content

Product / SCS

Halton Sec SCS – Smoke control damper (MAsingle, AAsingle)

This CE marked single compartment smoke control damper for automatically (AA) and manually (MA) activated systems is one of the narrowest in the market.

  • Sizes from 200×200 up to 1250×1000 mm available
  • Model with stainless steel (AISI 316L) material available
Request a Quote

Overview

  • CE marked according to the product standard EN 12101-8:2011
  • Fire resistance class
    • E600 120 (hodw-i↔o) S 1500C10000 AAsingle
    • E600 120 (hodw-i↔o) S 1500C10000 MAsingle
    • E600 120 (vew-i↔o) S 1500C10000 AAsingle
    • E600 120 (vew-i↔o) S 1500C10000 MAsingle
  • Certificate of constancy of performance 0809-CPR-1018
  • Classification of casing leakage EN 1751 class C
  • Manufacturing in accordance with the ISO 9001 quality standard.
  • Third party certification product audit by Eurofins Expert Services Oy.
  • Suitability for use in smoke extraction ducts with a maximum of 1500 Pa under pressure
  • Suitability for use in ducts with a maximum air speed of 15 m/s.
  • Suitability for rectangular smoke extraction ducts from size 200 mm x 200 mm to 1250 mm x 1000 mm.

Product models and accessories

  • Suitable for the automatically activated fire alarm systems (AA)
  • Suitable for the manual activated fire alarm systems (MA)
  • Models equipped with electric actuator (no fuse, no spring return)
  • Actuator with a visual position indicator
  • Circular duct connections
  • Modular damper casing extension for optional protecting mesh (L+210 mm)
  • Model with stainless steel AISI 316 material also available

Dimensions

Rectangular connections (R)

H/W 200-1000 1050 1100 1150 1200 1250
200 B H H H H H
300 B H H H H H
350 B H H H H H
400 B H H H H H
450 B H H H H H
500 B H H H H H
550 B H H H H H
600 B H H H H H
650 B H H H H H
700 B H H H H H
750 B H H H H H
800 B H H H H H
850 B H H H H H
900 B H H H H H
950 B H H H H H
1000 B H H H H H

B      Both horizontal and vertical blade direction allowed
     Horizontal blade direction only

Circular connections (C)

ØD W x H
100 200×200
125 200×200
160 200×200
200 200×200
250 300×300
315 300×300
400 400×400
500 500×500
630 600×600
800 800×800
1000 1000×1000

Material

Number Part Material Note
1, 2, 3 Casing Galvanised steel Stainless steel available
(EN 1.4404 / AISI 316L)
4 Blade stopper Stainless steel (AISI 316)
5 Support beam, W sides Stainless steel (AISI 316)
6 Bearing list,
form actuator side
Galvanised steel Stainless steel available
(EN 1.4404 / AISI 316L)
7 Actuator
mounting bridge
Galvanised steel Stainless steel available
(EN 1.4404 / AISI 316L)

Accessories and actuators

 Accessory Code  Description
 Damper casing extension CE Length 210 mm, for
structual thickness >200 mm
E600 120 (hodw-i↔o) S 1500C10000 AAsingle
E600 120 (vew-i↔o) S 1500C10000 AAsingle
A  Non insulated actuator
E600 120  (hodw)-i↔o) S 1500C10000 MAsingle
E600 120  (vew-i↔o) S 1500C10000 MAsingle
M  Actuator with
heat insulated box

Electric actuator options

Actuators do not have a fuse and are equipped with a limit switch.

R1         BEN24, operating voltage AC/DC 24 V, 15 Nm (H or W < 400 mm)
R2         BEN230, operating voltage AC 230 V, 15 Nm   (H or W < 400 mm)
R3         BE24, operating voltage AC/DC 24 V, 40 Nm
R4         BE230, operating voltage AC 230 V, 40 Nm

Fig.1. Halton Sec SCS, model M = Actuator with insulated box, for manual activation system.

Function

The Halton Sec SCS is a motorised rectangular smoke control damper that allows smoke to be extracted from the single compartment space by dedicated smoke extraction system.

The smoke damper is made of fireproof materials with incombustible glass fiber blade gaskets. They are preventing the air to infiltrate the extraction ducts to collect smoke from closed dampers.

The Halton Sec SCS  smoke control damper shall be connected to the control and testing system delivered by Halton or to common building automation systems. The smoke control damper can be used in fully automatic (SCS/A) or manual activation (SCS/M) systems.

In case of fire sequence of operation is important, smoke extract fans should not be started before the smoke control dampers are opened.

Installation

Smoke control damper Halton Sec SCS can be installed on the certified single compartment ducts. Damper can be also installed on the wall or floor surface. The blade direction may be either horisontal or vertical.

The correct operation of the smoke control damper must be ensured before and after installation.

After fixing the smoke control damper check the diagonal dimension.
The damper should be cleaned after installation.

Detailed installation instructions, as well as an installer’s installation certificate form, are supplied with each product.

See also the section Downloads for detailed installation guidance.

Installation on the single compartment duct

All dampers are delivered with an installation flange, which is used to fasten the fire damper with screws to the surface of steel duct or to a connection.

The gap between the damper and the supporting structure is filled with fireproof seal rock wool or firestop mastic, after fixing of the damper.

When Halton Sec SCS is used as manual activated (MA) smoke control damper, connect the connection cables for electrical actuator inside of heat insulated box. Use nonflammable cables

Use M10 threaded rod for supporting the smoke control damper. See drawings below.

Installed to side of horisontal duct

Installed to side of vertical duct
Note!
Need to use CE marked smoke ducts.

Installed on the top and bottom of duct

Installed in the horisontal duct

Installed on the wall or floor surface

Electric actuator wiring diagram

Diagram below is used for actuators:

R1     BEN24                                   R3     BE24
R2     BEN230                                 R4     BE230

Servicing

No regular maintenance is required for the product.

Regular testing with the separate testing system is recommended twice a year.
Upon failure during testing of the smoke damper, a Halton representative shall be connected to ensure appropriate operation of the product

Specification

Multi-blade-type single zone smoke control damper Halton Sec SCS for rectangular and circular ducts with electric actuator and position indicator.

Damper has to fulfill the requirements from harmonized product standard EN 12101-8 and tested according to demands in standard EN 1366-10 and be labeled with CE Mark.

Damper has to be classified as:

E600 120(hodw-i↔o) S 1500C10000 AAsingle

E600 120(hodw-i↔o) S 1500C10000 MAsingle

E600 120 (vew-i↔o) S 1500C10000 AAsingle

E600 120 (vew-i↔o) S 1500C10000 MAsingle

The casing and blades of the smoke control damper shall be made of galvanised or stainless steel and the blade gaskets made of incombustible material.

The smoke control damper shall be installed horisontal and vertical position, CE marked, single compartment duct with incombustible sealing mass to ensure tightness of the connection

Order code

SCS-W-H; CM-MA-CT-SF-RE-AC-ZT

S  = Type of connection
R     Rectangular
C     Circular

D  = Connection size (if circular connection)
100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000

W  = Width (if rectangular connection)
200, +50, …, 1250

H  = Height (if rectangular connection)
200, 300, +50, …, 1000

Other options and accessories

CM = Model
A      Actuator without heat insulated box (for automatic activation system)
M      Actuator with heat insulated box (for manual activation system)

MA = Material
CS    Galvanised Steel
AS    Stainless steel (EN 1.4404/AISI 316L)

CT = Type of circular connection
D2    Circular connections on both sides
D1    Circular connection only on actuator side

SF = Flange option
NA     Standard
L1      Standard + flange connection
L2      Flange connection on both sides
R2      Flange connection with holes

RE = Release type
R1     BEN24 (no fuse), 15 Nm  (H or W < 400 mm)
R2     BEN230 (no fuse, 15 Nm (H or W < 400 mm)
R3     BE24 (no fuse), 40 Nm
R4     BE230 (no fuse), 40 Nm

AC = Accessories
CE     Casing extension of 210 mm, for structural thickness > 200mm

ZT  = Tailored product
N       No
Y       Yes (ETO)

Code example

SCS/R-200-200 , CM=A, MA=CS, CT=D2, SF=NA, RE=B3, AC=NA, ZT=N

Downloads

  • Halton Sec SCS – Smoke control damper (MAsingle, AAsingle)

    Data

    en

    Shape 2
  • Halton Sec SCS – Savunhallintapelti (MAsingle, AAsingle)

    Data

    fi

    Shape 2
  • Halton SCS – huolto-ohje

    Data

    fi_FI
    Shape 2
  • Halton SCS – Installation Instructions and Proof of Installation

    Data

    en_GB
    Shape 2
  • Construction Product Regulation (CPR) – SCS

    Data

    en_GB
    Shape 2
  • Declaration of Performance (DoP) – Halton Sec SCS

    Data

    English (en)
    Shape 2
  • Halton SCS – asennusohjeet ja asennustodistus

    Data

    fi_FI
    Shape 2
  • Palo- ja savunhallintapeltien asennustodistus

    Data

    Suomi (fi)
    Shape 2
Contact Us
  • Hidden
  • Max. file size: 64 MB.