Halton Sec SMR – Smoke control damper (MAmulti, AAmulti)

This CE marked multi compartment smoke control damper is the most trusted choice in the market for demanding enviroments. It is manufactured of mineral fibre and this fire proof material enables the opening of blade during fire.

The smoke control damper is suitable for vertical and horizontal installation on smoke extract ducts and concrete, masonry or lightweight structures. Can also be installed direct to the surface of the structure.

Fire resistance class for all installation options is provided up to EI 120 S requirements.

  • For automatically (AA) or manually (MA) activated systems
  • Suitability for all installation methods
  • Sizes from 200×200 mm up to 1600×1000 mm are available
Request a Quote

Overview

This multi compartment smoke control damper is the most trusted choice in the market for demanding enviroments. It is manufactured of mineral fibre and this fire proof material enables the opening of blade during fire. The smoke control damper is suitable for vertical and horizontal installation on smoke extract ducts and concrete, masonry or lightweight structures. Can also be installed direct to the surface of the structure. Fire resistance class for all installation options is provided up to EI 120 S requirements.

Features

  • Installation to multi zone fire compartment for automatically (AA) or manually (MA) activated systems
  • Supplied with electrical non-spring return actuator (24 V or 230 V)
  • Sizes from 200×200 mm up to 1600×1000 mm are available
  • Maximum air speed through smoke control damper in open position is 12 m/s
  • Suitability for use in smoke extraction ducts with a maximum of 1500 Pa under pressure
  • Damper casings and blades are made of fire resistant asbestos free boards (mineral fibres), fasteners are galvanized steel
  • No spare parts or additional installation frames needed, regardless of installation method

Installation options

  • Suitability for all installation methods
  • CE marked for installation in concrete, masonry or lightweight sructure with fire resistance classes of EI 120, EI 90 or EI 60

Standards

This product complies with the following standards:

  • CE certified according to product standard EN 12101-8
  • Fire classification according to EN 13501-4 standard:
    • Horizontal duct
      • EI 120 (ved– i↔o) S 1000C10000 AAmulti
      • EI 120 (ved– i↔o) S 1000C10000 MAmulti
    • Vertical duct
      • EI 120 (hod– i↔o) S 1000C10000 AAmulti
      • EI 120 (hod– i↔o) S 1000C10000 MAmulti
    • Walls
      • EI 120 (vew– i↔o) S 1000C10000 AAmulti
      • EI 90 (vew– i↔o) S 1500C10000 AAmulti
    • Floor/ceiling
      • EI 120 (how– i↔o) S 1000C10000 AAmulti
      • EI 90 (how– i↔o) S 1500C10000 AAmulti
  • Fire testing according to EN 1366-10
  • CE certificate of constancy of performance, No P-1391-CPR-2018/0206
  • Declaration of Performance, No: 10037-SMR-2019/01/01
  • Smoke control damper casing tightness class C according to EN 1751
  • Leakage through closed damper blade fulfils class 2 according to EN 1751

Dimensions and weight

 W = Width (mm)  H = Height (mm)
200, 250, 300, 350, 400, 450, 500, 550,
600, 700, 800, +100, … 1600
200, 250, 300, 350, 400, 450, 500, 550,
600, 700, 800, 900, 1000

Weight (kg)

With flanges

H W
200 250 300 350 400 450 500 550 600 700 800 900
200 44.1 47.5 49.0 51.7 55.5 58.8 58.7 62.8 65.9 68.0 76.4 81.1
250 47.5 51.2 52.7 55.6 59.5 62.9 62.7 67.0 70.4 72.5 81.5 86.4
300 51.0 54.8 56.3 59.4 63.4 67.1 66.9 71.4 74.9 77.2 86.5 91.7
350 54.8 58.7 60.3 63.5 68.0 71.8 71.5 76.3 79.9 82.2 92.1 97.6
400 58.1 62.1 63.7 66.9 71.5 75.5 75.2 80.1 83.9 86.4 96.6 102.2
450 61.4 65.7 67.3 70.8 75.5 79.7 79.2 84.5 88.4 90.9 101.6 107.5
500 64.9 69.4 71.1 74.6 79.6 83.9 83.4 88.9 92.9 95.5 106.8 112.8
550 68.4 73.0 74.8 78.5 86.6 88.0 87.5 93.3 97.5 100.1 111.8 118.1
600 72.0 76.7 78.4 82.2 87.6 92.3 91.6 97.5 102.0 104.7 116.8 123.4
700 111.0 113.8 126.9 135.1
800 120.0 124.1 138.2 145.7
900 130.4 133.2 148.4 156.2
1000 139.4 142.4 158.5 166.8
H W
1000 1100 1200 1300 1400 1500 1600
200 85.7
250 91.2
300 96.8
350 102.8
400 107.7
450 113.2
500 118.7
550 124.1
600 129.7
700 141.8 147.0 164.3 168.7 173.2 181.9 190.7
800 152.8 158.4 176.8 181.5 186.3 195.6 205.0
900 163.9 169.6 189.4 198.2 207.2 217.2 227.1
1000 174.9 180.9 204.6 212.4 220.3 230.9 241.4

= Size not available as standard. Please contact Halton Sales.
Without flanges

H W
200 250 300 350 400 450 500 550 600 700 800 900
200 40.9 43.9 45.2 47.7 51.2 54.2 55.0 57.9 60.2 66.4 70.4 74.8
250 44.0 47.3 48.8 51.3 55.0 58.1 58.9 61.9 65.0 71.0 75.2 79.8
300 47.3 50.6 52.1 54.9 58.8 62.0 62.9 66.0 69.3 75.6 79.9 84.7
350 50.8 54.4 55.9 58.8 62.9 66.3 67.1 70.5 73.9 80.6 85.3 90.2
400 53.6 57.4 58.9 62.0 66.2 69.9 70.8 74.3 77.8 84.8 89.5 94.8
450 56.8 60.8 62.4 65.5 69.9 73.8 74.6 78.3 82.0 89.4 94.3 99.8
500 60.1 64.1 65.8 69.1 73.7 77.7 78.6 82.4 86.3 93.9 99.2 104.9
550 63.2 67.5 69.2 72.6 77.5 81.6 82.5 86.5 90.5 98.5 103.9 109.9
600 66.4 70.9 72.5 76.2 81.3 85.5 94.4 90.6 94.8 103.1 108.7 115.0
700 103.3 112.3 118.3 126.2
800 111.8 122.8 129.2 136.3
900 121.6 131.9 138.7 146.3
1000 130.1 141.0 148.4 156.4
H W
1000 1100 1200 1300 1400 1500 1600
200 80.2
250 85.6
300 90.8
350 96.7
400 101.5
450 106.9
500 112.2
550 117.6
600 122.9
700 134.8 143.4 156.4 159.3 162.2 170.4 178.7
800 145.4 154.7 168.6 171.7 174.8 183.7 192.5
900 156.1 166.1 180.8 187,2 195.3 204.7 214.1
1000 166.8 177.4 192.9 200,4 207.9 217.9 228.0

= Size not available as standard. Please contact Halton sales.

Structure and materials

 Number  Part  Material  Note
1  Casing Asbestos free boards
made of mineral fibre
 –
2  Blade Asbestos free boards
made of mineral fibre
 –
3 Inspection hatch
covering
Asbestos free boards
made of mineral fibre
 –
4 Operating model
(actuator)
 – Actuator cover,
asbestos free boards
(mineral fibre)

Operating model

Electric actuator

The Halton Sec SMR smoke control damper is equipped with an electric actuator, 24 V or 230 V (no spring return or fuse aloud). The actuator is equipped with built-in limit switches for indicating both open and closed positions.

The smoke control damper must be connected to a common fire alarm or building automation system. It can be used in fully automatic (AA) or manual activation (MA) systems.

In case of manually activated system (MA), the non-flammable cables in must be connect to electrical actuator inside the heat insulated cover box.

Order code Operating model Damper sizes
(WxH, mm)
Operating voltage Limit switch
 R1 BEN 24
15 Nm
    200×200 –
1000×400
AC/DC 24 V
 R2 BEN 230
15 Nm
    200×200 –
1000×400
AC  230 V
 R3 BE 24
40 Nm
   600×800 –
1600×800
AC/DC 24 V
 R4 BE 230
40 Nm
    600×800 –
1600×800
AC  230 V
 I1 Schischek InMax
50.75-s
72 Nm
  1300×1000 –
1600×1000
24 V / 230 V

Function

The Halton Sec SMR multi compartment smoke control damper is CE certified for vertical (ve) and horizontal (ho) installation in concrete, masonry or lightweight structures and also vertical (ve) and horizontal (ho) smoke extract duct orientations. It fulfils all fire resistance classes up to EI 120 S requirements.

Smoke control dampers allow smoke to be extracted from the multi compartment smoke zone by dedicated smoke extraction systems. In case of fire sequence of operation is important, smoke extract fans should not be started before the smoke control dampers are opened.

The blade of the smoke control damper can be opened during and after fire.

The smoke control damper must be connected to a common fire alarm or building automation system. It can be used in manually (MA) or automatically (AA) activated systems.

In case of manually activated system (MA), the non-flammable cables in must be connect to electrical actuator inside the heat insulated cover box.

The smoke control damper is equipped with an electric actuator 24 V or 230 V (no spring return or fuse aloud). The actuator is equipped with built-in limit switches for both open and closed position.

Installation

Please see/download Installation Guide for this smoke control damper from section Downloads.

Servicing

No regular maintenance is required for the product.

In any case to ensure proper operation of smoke control dampers, an inspection must be carried out regularly according to local building codes. The minimum recommended inspection period is every 6 months. Documentation of testing must be saved for future needs.

The smoke control damper must be connected to a common fire alarm or building automation system.

The smoke control damper is equipped with two inspection hatches, enabling the possibility to check the position of the damper blade.

Upon failure during testing of the fire damper, maintenance service shall be ordered from an authorised Halton representative to ensure appropriate operation of the product.

Specification

The multi compartment smoke control damper is CE certified and marked according to the standard EN 12101-8 and fire tested according to the EN 1366-10 standard.

Smoke control damper of maximum fire resistance class requirements:

  • Horizontal duct
    • EI 120 (ved– i↔o) S 1000C10000 AAmulti
    • EI 120 (ved– i↔o) S 1000C10000 MAmulti
  • Vertical duct
    • EI 120 (hod– i↔o) S 1000C10000 AAmulti
    • EI 120 (hod– i↔o) S 1000C10000 MAmulti
  • Walls
    • EI 120 (vew– i↔o) S 1000C10000 AAmulti
    • EI 90 (vew– i↔o) S 1500C10000 AAmulti
  • Floor/ceiling
    • EI 120 (how– i↔o) S 1000C10000 AAmulti
    • EI 90 (how– i↔o) S 1500C10000 AAmulti

The smoke control damper casing complies with the tightness requirements for EN 1751 class C. Leakage through closed damper blade fulfils class 2 according to EN 1751.

The casing and blade of the smoke control damper is made of fire resistant asbestos free boards (mineral fibre).

The smoke control damper can be installed in either horizontal or vertical position to smoke extract duct, wall or floor/ceiling.

The actuator is equipped with built-in limit switches for both open and closed position.

The smoke control damper is equipped with two inspection hatches, enabling the possibility to check the position of the damper blade.

Order code

SMR/W-H; MA-OP-FL-ZT

W  = Width of duct connection (mm)
200, 250, 300, 350, 400, 450, 500, 550, 600, +100, …, 1600

H  = Height of duct connection (mm)
200, 250, 300, 350, 400, 450, 500, 550, 600, 700, 800, 900, 1000

Other options and accessories

MA = Material
MF     Asbestos free boards, mineral fibre

OP = Operating models
R1     BEN24, 24 V, 15 Nm
R2     BEN230, 230 V, 15 Nm
R3     BE24, 24 V, 40 Nm
R4     BE230, 230 V, 40 Nm
I1      Inmax 50.75-S, 75 Nm

FL = Flanges
Y      Yes
N      No

ZT  = Tailored product
N       No
Y       Yes (ETO)

Code example

SMR-300-300, MA=MF, OP=R2, FL=Y, ZT=N

Downloads

  • Halton Sec SMR – Smoke control damper (MAmulti, AAmulti)

    Data

    en

    Shape 2
  • Halton Sec SMR – Savunhallintapelti (MAmulti, AAmulti)

    Data

    fi

    Shape 2
  • Installation guide – Halton Sec SMR

    Data

    English (en)
    Shape 2
  • Declaration of Performance (DoP) – Halton Sec Mighty Rectangular (SMR)

    Data

    English (en)
    Shape 2
  • Construction Product Regulation (CPR) – SMR

    Data

    English (en)
    Shape 2
Contact Us
  • Hidden
  • Max. file size: 64 MB.