Compact square unit with 360º swirl air distribution. Ideal for multipurpose use as a chilled beam and as a supply and exhaust diffuser. Suitable for demand based ventilation when equipped with Halton Air Quality controller.
The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.
The comfort unit shall have an integral re-circulation air path through the perforated front panel. The induced room air flow shall be manually adjustable via three setting positions without influencing the primary air supply flow rate.
The primary air-flow rate of the comfort unit shall be adjustable by opening and closing of the nozzles.
The comfort unit shall have as options a manual air-flow adjustment damper and a motorised air-flow-control damper unit for increasing the supply-air-flow rate, in addition to the nozzle air flow. The manual damper unit shall be easily replaced with a motorised unit.
Control of outdoor air’s rate of flow shall not have any effect on coil cooling capacity. The comfort with adjustable air flow shall have only one duct connection.
Adjustment shall be effected by opening of the product, with no need to remove ceiling panels or use external access panels.
The product shall have an option for exhaust operation equipped with either manual or motorised control. Adjustment of air flow shall be easily implemented, without a need to remove ceiling panels or use external access panels.
The units shall be available for air–water and all-air room air conditioning. The appearance of the comfort unit, supply-air diffuser, and exhaust unit shall be the same.
The front panel shall be openable, to allow general maintenance and cleaning.
The air supply to the room space shall be supplied radially through 360º. The comfort unit shall have an inlet duct diameter of 125 mm. The casing shall be made of galvanised steel plate.
All visible parts shall be white, painted to RAL 9010, 20% gloss. All pipes shall be manufactured from copper, and connection pipes with a wall thickness of 0.9–1.0 mm. The fins shall be manufactured from aluminium. All joints shall be soldered and factory pressure-tested. The maximum operation pressure of the pipework is 1.0 MPa. The comfort unit shall have a measurement tap to allow measurement of air flow.
Each comfort unit shall be protected by removable plastic film and individually packed in a plastic bag. The duct connection and pipe ends shall remain sealed during transport.
The comfort units shall be identified by a serial number printed on labels attached to both the comfort unit and its plastic packaging.
The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.
Water excluded (kg/unit) | Water included (kg/unit) |
17,8 | 18,3 |
Part | Material | Finishing | Note |
Front panel | Pre-painted galvanised steel | Epoxy-painted, white (RAL 9010/ 20% gloss) | Special colours available, polyester-epoxy -painted |
Front panel frame | Pre-painted galvanised steel | Epoxy-painted, white (RAL 9010/ 20% gloss) | Special colours available, polyester-epoxy -painted |
Casing | Galvanised steel | ||
Nozzles | Plastic | ||
Supply air plenum | Galvanised steel | ||
Brackets | Galvanised steel | ||
Coil pipes | Copper | ||
Coil fins | Aluminium |
Harmonised appearance of units for different functions:
Cooling water pipe connections are Cu10 with a wall thickness of 0.9–1.0 mm, fulfilling the requirements of European standard EN 1057:1996.
The maximum chilled-water circuit operating pressure is 1.0 MPa.
The supply-air duct connection diameter is 125 mm. With exhaust model connection diameter is 160mm.
The Halton CSW swirl comfort unit is designed to be installed flush with a suspended ceiling.
The primary supply air enters the plenum of the swirl comfort unit, from which it is diffused into the room with a swirl effect through nozzles and supply slots at the bottom of the swirl comfort unit. Nozzles are in a circle supplying air 360º radially. The supply air nozzle jets efficiently induce ambient room air. Induced air flows through the heat exchanger, where it cools. The supply air jet is supplied from the nozzles, creating swirl functioning. Some of the nozzles are openable, to enable different supply airflow rates.
The swirl comfort units and high-induction diffuser can be used in constant or variable airflow applications.
In variable airflow operation mode, the air flow is controlled by means of an integrated motorised Halton Air Quality control damper, with either room temperature or CO2 content as the ventilation demand indicator. Supply air supplied by the HAQ damper is mixed with the induction air at high efficiency.
It is also possible to use a Halton CSW unit for exhaust. The Halton CSW exhaust unit has integrated airflow adjustment dampers. Air flow can be adjusted later also, with ease – just open the front panel and adjust the damper position. An actuator can also be incorporated, to enable continuous control of the air-flow rate. It is also possible to install the motorised version afterwards.
Induction control in the occupied zone
Halton Induction Control is used for adjusting room air velocity conditions either when room layout is changed (e.g., in cases where the partition wall is located near the chilled beam) or when local, individual velocity conditions need to be altered. Induction adjustment has an impact on the induced room airflow through the heat exchanger, and therefore it either increases or decreases both the velocities in the occupied zone and the cooling capacity of the comfort unit.
Pos.1 = Flush Pos. 2 = Enhanced Pos.3 = Boost.
Halton Induction Control uses manual velocity adjustment with three settings.
The supply airflow of the swirl comfort unit nozzle jets depends on the static chamber pressure, which can be adjusted by means of a separate air-flow adjustment damper, for example.
Halton Air Quality control is an option for adjusting and/or controlling the rate of outdoor air flow in a room space. The air-flow rate is dependent on the opening position of the control damper and the static chamber pressure.
Airflow adjustment is needed when the use of the space changes and there is need to adapt the supply-air flows. Air-flow rate can also be automatically adjusted to demand via a motorised control damper. When there is a need for demand-based ventilation, motorised HAQ can be used for adjusting air flow in VAV operation.
A swirl comfort unit equipped with HAQ manual air-flow rate adjustment can be retrofitted for motorised operation for demand-based ventilation.
It is recommended that swirl comfort units for demand-based air flow be connected to a constant‑pressure ductwork zone when
The appearance of different units with constant, adjustable, or variable air flow is identical.
The Halton Air Quality control unit’s position and the selection of swirl comfort unit nozzle size allow adjustment of the primary air-flow rate in the space. The separate air-flow-adjustment damper installed in the duct branch is used for balancing the air flows in the ductwork. When a motorised air quality control (HAQ) unit is used, the maximum and minimum air flow are adjusted with the stroke-limiters of the damper.
The primary air-flow rate of each beam is adjusted by means of the Halton Air Quality control unit during installation and commissioning.
The Halton CSW exhaust model can be used for constant- or variable-flow exhaust applications.
The exhaust version is equipped with a built-in damper for easy adjustment of airflow rates to meet the flow demands as they change during the building’s service life.
In variable airflow applications, the exhaust damper is equipped with an actuator enabling control on the basis of the required exhaust‑air flow. Minimum and maximum air-flow rates can be set for different demands at any point in the building’s service life without any special tools, just by changing the position of stroke-limiters.
The appearance of both exhaust-air models is the same as that of supply-air diffuser units.
The cooling and heating capacities of the swirl comfort unit are controlled by regulation of the water-flow rate on the basis of the control signal of the room temperature controller.
Air quality control for a room space can be arranged via, for example, a CO2 sensor when room airtemperature is controlled separately through regulation of water flow. Alternatively, a temperature sensor can be used for air quality control, with the air flow modulated in the first sequence;, if the temperature exceeds that set, the water valve starts to open in the second sequence.
For heating mode, it is recommended that the temperature difference between jet outlet and room air be no greater than 3 °C. The inlet water temperature of the heat exchanger should not be higher than 35 °C. Optimal heating performance requires an appropriate primary air-flow rate, so the air-handling unit operates during heating season to ensure appropriate heating performance.
The Halton CSW swirl comfort unit is suitable for ceiling mounting flexibly in different positioning patterns in the room space. Air and water connections can be connected from any of four directions.
The variable airflow model is equipped with a motorised HAQ unit:
Each swirl comfort model is equipped with three brackets attached to the casing of the unit. The unit can be attached directly to the ceiling surface (H1 = 241 mm) or suspended by means of threaded drop rods (8 mm). Install the main pipelines of the chilled-water circuit above the level of the swirl comfort unit, in order to enable venting of the pipework.
The recommended chilled-water mass flow rate for Halton CSW is 0.02 to 0.06 kg/s, resulting in a temperature increase of 1 to 4 °C in the heat exchanger. For avoiding condensation, the recommended inlet water temperature of the heat exchanger is 14 to 16 °C.
Balance the water-flow rates of the swirl comfort unit by using adjustment valves, ideally for installation on the outlet side of the chilled-water loops. The cooling capacity of the swirl comfort unit is controlled by regulation of the water mass flow rate. The water mass flow rate can be controlled by means of an ON/OFF valve or a two- or three-way proportional valve.
Connect a manometer at the measurement tap, and measure the static pressure in the swirl comfort unit. The air-flow rate is calculated according to the formula below.
Nozzle jet air-flow rate (qv)
Key
N Number of opened big nozzles
ΔPm Measured static chamber pressure [Pa]
(l/s) | (m3/h) | |
K1 | 0.73 | 2.63 |
K2 | 0.097 | 0.35 |
Air quality control diffuser airflow rate (qv2)
Key:
a HAQ unit position
ΔPm Measured static chamber pressure [Pa]
k(l/s) | k(m3/h) |
0.08 | 0.29 |
Total airflow rate, qv
qv= qv1+ qv2
Key:
qv Total airflow rate, l/s or m3/h
qv1 Nozzle jet airflow rate, l/s or m3/h
qv2 Air quality control diffuser airflow rate, l/s or m3/h
Connect a manometer to the measurement tap, and measure the static pressure in the swirl comfort unit. The air-flow rate is calculated according to the formula below.
Total air-flow rate, qv
qv= (a1 + a2) * k * √∆Pm
Key:
a1 Position of HAQ unit 1
a2 Position of HAQ unit 2
ΔPm Measured static chamber pressure [Pa]
k(l/s) | k(m3/h) |
0.16 | 0.59 |
Determine the position, in millimetres, of the HAQ unit that corresponds to the air-flow rate at the actual chamber pressure level.
Adjustment of HAQ is done manually with the aid of the position scale by adjusting the opening of the unit. It is possible to verify the opening, in millimetres, from the position scale.
To ensure accurate adjustment, it is recommended to adjust HAQ position and at the same time read the target chamber pressure by using the manometer.
It is also possible to remove the HAQ unit from the frame, by opening the two knurled-head adjustment screws (4).
Manual HAQ damper unit for constant-air-flow adjustment.
Variable flow adjustments of the HAQ damper unit.
1. Release of the actuator
2. Limiter of the maximum opening
3. Limiter of the minimum opening
Switch off the power supply to the actuator.
Disengage the actuator gear for manual override position by releasing the knob (1).
Determine the maximum and minimum positions, in millimetres, that correspond to maximum and minimum air-flow rates at the actual chamber pressure level. The maximum and minimum positions are adjusted with two hexagonal socket set screws (2, 3). It is possible to verify the opening from the position scale (in millimetres).
Switch on the power supply of the actuator (24 VAC). The actuator calibrates the minimum and maximum positions automatically according to the limits set.
The actuator can be controlled from this point on via a 0 to 10 VDC control signal (0 VDC = min. position, 10 VDC = max. position).
It is also possible to remove the HAQ unit from the frame for adjustment, by opening the two knurled-head screws (4).
Exhaust models of Halton CSW unit are equipped with two adjustable dampers. In variable-flow operation, the second of these is equipped with an actuator, which controls the damper position.
Code description
1. Front panel
2. Casing; plenum box
3. Heat exchanger
4. Supply air connection
5. Access panel
Open the front panel (1) of the supply-air plenum in order to gain access to the ductwork and to the heat exchanger (3). Clean the supply-air plenum and finned coils of the heat exchanger with a vacuum cleaner, taking care not to damage the finned coils.
Clean the front panel, using a damp cloth.
Check at regular intervals that the chilled-water flow control valve is working.
The access panel enables access for duct-cleaning. Unscrew the screws of the access panel to open it.
The comfort unit has an integral re-circulation air path through the perforated front panel. The induced room airflow is manually adjustable via three setting positions without influencing the primary air supply flow rate.
The primary airflow rate of the comfort unit is adjustable by opening and closing of the nozzles.
The comfort unit has as options a manual airflow adjustment damper and a motorised airflow control damper unit for increasing the supply airflow rate, in addition to the nozzle airflow. The manual damper unit can be easily replaced with a motorised unit.
Control of outdoor air’s rate of flow has not any effect on coil cooling capacity. The comfort with adjustable airflow has only one duct connection.
Adjustment is effected by opening of the product, with no need to remove ceiling panels or use external access panels.
The product has an option for exhaust operation equipped with either manual or motorised control. Adjustment of airflow is easily implemented, without a need to remove ceiling panels or use external access panels.
The units are available for air–water and all-air room air conditioning. The appearance of the comfort unit, supply air diffuser, and exhaust unit are the same.
The front panel is openable, to allow general maintenance and cleaning.
The air supply to the room space is supplied radially through 360º.
The comfort unit has an inlet duct diameter of 125 mm.
The casing is made of galvanised steel plate.
All visible parts are white, painted to RAL 9010, 20% gloss.
All pipes are manufactured from copper, and connection pipes with a wall thickness of 0.9–1.0 mm.
The fins are manufactured from aluminium. All joints are soldered and factory pressure-tested.
The maximum operation pressure of the pipework is 1.0 MPa.
The comfort unit has a measurement tap to allow measurement of airflow.
Each comfort unit is protected by removable plastic film and individually packed in a plastic bag.
The duct connection and pipe ends remain sealed during transport.
The comfort units are identified by a serial number printed on labels attached to both the comfort unit and its plastic packaging.
M = Model
S Supply device
E Exhaust device
IO = Ceiling type installation option
NA Standard for T-profile 600
TP T-profile 625
T2 T-profile 675
AM Armstrong Orcal ceiling
DC Dampa ceiling
FL Fineline ceiling 600
F2 Fineline ceiling 675
TC = Cooling / Heating functions (Coil type)
C Cooling
H Heating
N Without coil
AQ = Air quality control
A Manual
B Motorised
R Retrofit
EQ = Exhaust control
A Manual
B Motorised
CO = Colour
W White
X Special colour
ZT = Tailored product
N No
Y Yes
CSW/S-NA-C, AQ=A, EQ=NA, CO=W, ZT=N