Skip to content

Product / FDB2

FDB2 – A0(A60) Fire and gas damper

Halton FDB2 fire and gas damper is the most widely sold marine fire and gas damper in the world.

Request a Quote

Overview

  • Type-approved by the most recognized classification societies: class A0 without insulation, A15-A60 when suitably insulated
  • Shock and vibration tested
  • Blades contain silicone seals (effective up to 300 ºC) for low leakage in normal conditions and thermal expansion graphite seals (effective from 150 ºC) to increase tightness even up to 50% in a case of fire
  • A closed damper fulfils the requirement of leakage (EN1751:2014) from class 1 to class 3 depending on the size. Details available from Halton Marine
  • Casing leakage (EN1751:2014) class B
  • The nominal fuse release temperatures are 50 ºC, 74 ºC or 100 ºC. Other temperatures available
  • Low weight due to patented double skin blade structure
  • Automatic electrical, pneumatic or spring operation system available
  • Maximum duct pressure for damper construction 5000 Pa and maximum air velocity 15 m/s
  • The normal operating temperature for the damper is between -50 ºC to +80 ºC. Actuator and component selection can affect this temperature range. Other temperatures available on request
  • Available as ATEX certified
  • SIL 2 safety assessment certificate available for the damper on specific terms

Specification

Halton FDB2 fire dampers are type-approved class A0(A60) fire and gas dampers for use in offshore, marine and navy ventilation systems. The FDB2 can be installed in rectangular or circular ducts. All fire dampers have a fusible link and they prevent the spread of fire and gases within the ventilation ductwork. When the blades are in the open position, the device does not cause significant pressure loss, noise or flow disturbance. Fire dampers are set from outside and can be installed in any position. An open-closed indicator is visible on the outside of the damper. Fire dampers with non-standard dimensions can be supplied on request.

Dimensions

FDB2 fire dampers meet international standards for both rectangular (width B 100-1200 mm and height H 100-1600 mm, 1 mm division) and circular ducts (Ø100-1250 mm). Modular constructions are available for bigger sizes. Non-standard dimensions and flange drilling available on request. Standard flange width 27 mm. Flanges and drilling also available according to ISO 15138 standards. Frame thickness 3 mm or 3-5 mm according to SOLAS. Also 6, 8 and 10 mm frame thicknesses are available on request. Blades are made of two sheets, each of them being 1 mm thick (sandwich design).

Frame thickness according to SOLAS

DIMENSIONS S
If B or H > 100, but < 449 3
If B or H > 450 but < 649 4
If B or H > 650 5

Frame thickness according to SOLAS, Edition Dec. 2015

DIMENSIONS S
If A < 0.075 m2 3
If A > 0.075 and A < 0.45 m2 4
If A > 0.45 m2 5

Actuator effect in dimensions

ACTUATOR R A
Electrical (EL) BF230, BF24, BF120 100 H<300 = 300, H>300 =H
Pneumatic (PNR) Pneumatic rotating actuator AT100 170 H<300 = 300, H>300 =H
Pneumatic (PNR) Pneumatic rotating actuator AT200 190 H<350 = 350, H>350 =H
Spring (SP) Spring 140 H

The above table contains only some examples of actuators and their effect on dimensions.

FDB2 general drawings

FDB2 circular connections

FDB2 general drawing, top

FDB2 general drawing, circular with connection flanges

DAMPER HEIGHT TOTAL DEPTH WITH BLADES OPEN
< 250 mm 210 mm
> 250 mm < 300 mm 250 mm
> 300 mm < 349 mm 210 mm
> 350 mm 240 mm

Material and Finishing

PART MATERIAL FINISHING
Frame Carbon steel Painted or galvanized
Frame Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L)  –
Blades Steel Galvanized
Blades Stainless steel EN 1.4301 (AISI304), EN 1.4404 (AISI316L), EN 1.4432 (AISI316L)  –
Maintenance-free
bearings
Stainless steel EN 1.4404 (AISI316L)  –
Shafts Stainless steel EN 1.4404 (AISI316L)  –

Product Models and Accessories

Halton FDB2 is available with following actuators:

  • FDB2-EL: Electrical spring return motor; standard actuators being 24 V or  230 V or 120 V. The motor contains built-in open-closed limit switches. Separate junction box included in the EL-model. A wide range of Ex actuators available, including a one second closing time function as an option.
  • FDB2-PNR: Pneumatic rotating actuator
  • FDB2-SP: Manual spring-actuated damper with fusible link

DOT: manual override function available for PNR and EL models.

HSO: Halton Smart Override function for HVAC damper black-start available for PNR and EL models. With automatic reset function when power and/or pneumatic air supply is reinstated.

A wide range of accessories available.

Operation Principle

In the event of a temperature rise in ductwork:

  • FDB2-EL: fusible link releases and cuts off operating voltage to the spring return motor, allowing the spring to close the damper blades. The fire damper opens automatically when the fuse has been changed and the operating voltage to the motor is re-established.
  • FDB2-PNR: fusible link releases and cuts off operating pressure to the spring return actuator, allowing springs to close the damper blades. The fire damper opens automatically when the fuse has been changed and the pneumatic air supply is re-established.
  • FDB2-SP: fusible link releases allowing the spring to close the damper blades. When the fuse has been changed, the fire damper must be reset into open position manually.

Weights

Weights of standard Halton Marine FDB2 dampers without an actuator (kg)

H/HEIGHT
(mm)
 B / WIDTH (mm)
100 200 300 400 500 600 700 800 900 1000 1100 1200
100 5 (5) 7(7) 9(9) 10(10) 12(13) 14(15) 15(22) 17(25) 19(27) 20(30) 22(32) 24(35)
200 7(7) 9(9) 11(11) 12(12) 14(16) 16(18) 18(26) 20(28) 22(31) 23(34) 25(36) 27(39)
300 9(9) 11(11) 13(13) 15(15) 17(19) 19(21) 21(30) 23(32) 25(35) 27(38) 29(41) 31(43)
400 11(11) 13(13) 15(15) 17(17) 20(22) 22(24) 24(33) 26(36) 28(39) 30(42) 32(45) 34(48)
500 13(16) 16(19) 18(22) 21(25) 23(27) 25(30) 28(38) 30(41) 32(44) 35(47) 37(50) 39(54)
600 15(18) 18(21) 20(24) 23(27) 25(30) 28(33) 30(41) 33(45) 35(48) 38(51) 40(55) 43(58)
700 18(25) 21(28) 23(32) 26(35) 29(39) 32(42) 34(46) 37(50) 40(53) 42(57) 45(60) 48(64)
800 20(27) 23(31) 25(35) 28(38) 31(42) 34(46) 37(50) 40(53) 43(57) 46(61) 49(64) 51(68)
900 22(31) 25(35) 28(39) 32(42) 35(46) 38(50) 41(54) 44(58) 47(62) 50(66) 53(70) 56(74)
1000 24(33) 27(37) 31(41) 34(45) 37(50) 40(54) 44(58) 47(62) 50(66) 53(70) 57(74) 60(78)
1100 26(36) 30(41) 33(45) 37(49) 40(54) 44(58) 47(62) 51(67) 54(71) 58(75) 61(79) 65(84)
1200 28(39) 32(44) 36(48) 39(52) 43(57) 46(61) 50(66) 54(70) 57(75) 61(79) 65(84) 68(88)
1300 31(42) 35(47) 38(52) 42(56) 46(61) 50(66) 54(70) 58(75) 62(80) 65(84) 69(89) 73(94)
1400 32(45) 37(50) 41(55) 45(59) 49(64) 53(69) 57(74) 61(79) 65(84) 69(88) 73(93) 77(98)
1500 35(48) 39(53) 43(58) 48(63) 52(68) 53(73) 60(78) 65(83) 69(89) 73(94) 77(99) 82(104)
1600 36(51) 41(56) 45(61) 50(66) 54(72) 59(77) 63(82) 67(87) 72(92) 76(98) 81(103) 85(108)
D2 ØD WEIGHT
(mm) kg
100 8 (8)
125 8 (8)
160 12 (12)
200 13 (13)
250 19 (19)
315 20 (20)
400 27 (27)
500 35 (43)
630 46 (62)
800 62 (89)
1000 83 (118)
1250 113 (162)

(Frame thickness according to SOLAS)

Examples of actuator weights: FDB2-EL GGA 326.1E 2,3 kg, GNA 326.1E 1,3 kg, BF230 +3,2 kg, BLF230 +1,7 kg, ExMax/Redmax +3,5 kg, CSQP +3 kg ,
FDB2-PNR AT100 +2,1 kg, AT100 as AISI316 4,4 kg, AT200 +3,2kg, AT200 as AISI316 +6,2 kg, FDB2-SP +1 kg. Control enclosure +4 kg.

Installation

Installation and maintenance instructions are with each fire damper delivery. Copies of Operation and Maintenance manuals are available from Halton Marine Sales offices and distributors.

Product Code

(S)=Shape of Connection
(A) Circular on one side
(C ) Circular on two sides
(R) Rectangular

(W)=Width
100-1200

(H)=Height
100-1600

(D)=Diameter
100-1250

(FA)=Fire Approval
(C1) ABS American Bureau of Shipping
(C2) MED Marine Equipment Directive
(C3) LRS Lloyds Register
(C4) DNV-GL
(C5) BV Bureau Veritas
(C9) RMRS Russian Maritime Register

(EX)=Atex Class
(NA) No
(X1) ATEX certified damper [please fill]

(SF)=Flange Option
(H0) Eurovent flange in circular connections
(H1) Eurovent flange + loose flange in circular connections
(HA) Eurovent flanges
(HB) Eurovent flanges + counter flanges (2 sides)
(HC) Eurovent flanges + counter flange (1 side)
(N0) ISO15138 flange drilling in circular connection
(N1) ISO15138 flange drilling + Loose flange in circular connection
(NA) Circular connections without flanges
(NR) ISO15138 flange drilling

(FS)=Frame Dimensioning
(HS) Manual dimensioning
(SO) SOLAS dimensioning
(S1) SOLAS dimensioning (supplement 2015)

(MA)=Material
(AS) Stainless steel 1 mm EN1.4404
(CS) Carbon steel 1 mm
(LS) Stainless steel 1 mm EN1.4432
(SS) Stainless steel 1 mm EN1.4301

(FM)=Frame Material
(A3) Stainless steel 3 mm EN1.4404
(A4) Stainless steel 4 mm EN1.4404
(A5) Stainless steel 5 mm EN1.4404
(C3) Carbon steel 3 mm
(C4) Carbon steel 4 mm
(C5) Carbon steel 5 mm
(L3) Stainless steel 3 mm EN1.4432
(L4) Stainless steel 4 mm EN1.4432
(L5) Stainless steel 5 mm EN1.4432
(S3) Stainless steel 3 mm EN1.4301
(S4) Stainless steel 4 mm EN1.4301
(S5) Stainless steel 5 mm EN1.4301

(FI)=Finishing
(HG) Hot galvanized
(NA) Acid treatment
(PN) Standard painting grey RAL7001
(PX) Special Painting C5-M ISO12944

(IN)=Insulation
(N) No
(Y) A60 insulation on actuator side

(RE)=Actuator
(E1) Electric – Belimo, BF24-2-HL
(E3) Electric – Belimo, BF230-2-HL
(E7) Electric – Belimo, BF120-HL
(E8) Electric – Belimo, NF24A-SR
(E9) Electric – Belimo, NF24A-SR-S2
(E10) Electric – Belimo, SF24A-SR
(E11) Electric – Belimo, SF24A-SR-S2
(I1) InMax – Schischek, 15-SF
(I2) InMax – Schischek, 15-SF VAS
(I3) InMax – Schischek, 15-SF1 VAS
(I4) InMax – Schischek, 8-SF-1
(I6) InMax – Schischek, 15-SF-1
(I9) InMax – Schischek, 5.10-SF
(I10) InMax – Schischek, 5.10-SF VAS
(I11) InMax – Schischek, 8-SF-1 VAS
(K0) Electric – Belimo, BFN24.1
(K2) Electric – Belimo, BFN230.1
(P0) Pneumatic – Air Torque, AT101, Aluminium
(P3) Pneumatic – Air Torque, AT104, AISI316
(Q1) Pneumatic – Air Torque, AT201, Aluminium
(Q2) Pneumatic – Air Torque, AT204, AISI316
(S1) Spring
(T1) Electric – Belimo, BF24-T-2.1HL
(T3) Electric – Belimo, BF230-T-2.1HL
(Z2) Electric (EX) – Schischek, ExMax 15-SF
(Z3) Electric (EX) – Schischek, ExMax 5-10SF
(Z4) Electric (EX), Schischek, ExMax 15-SF VAS
(Z5) Electric (EX) – Schischek, ExMax 15-SF1 VAS
(Z6) Electric (EX) – Schischek, ExMax 8-SF1
(Z7) Electric (EX) – Schischek, ExMax 15-SF1
(Z10) Electric (EX) – Schischek, ExMax 5.10-SF VAS
(Z11) Electric (EX) – Schischek, ExMax 8-SF1 VAS
(C1) Electric – Elodrive, CSQP-05A1E 24V
(C2) Electric – Elodrive, CSQP-05A2E 120/230V
(C3) Electric – Elodrive, CSQP-10A1E 24V
(C4) Electric – Elodrive, CSQP-10A2E 120/230V
(C5) Electric – Elodrive, CSQP-15A1E 24V – Blocked
(C6) Electric – Elodrive, CSQP-15A2E 120/230V – Blocked

(FU)=Fuse
144 °C
100 °C
95 °C
74 °C
72 °C
70 °C
65 °C
50 °C

(AC)=Accessories
(E1) Junction box – Ensto, Plastic, IP66 & 67
(E2) EX junction box – Cooper, GRP, IP66, T6
(E4) Cable connectors – Wieland & Hensel
(L2) Limit switch 2 pcs – Bernstein, Plastic, IP66, Mechanical
(L4) EX Limit switch 2 pcs – Bartec, Plastic, IP66, Mechanical
(L5) EX Limit switch 4 pcs – Bartec, Plastic, IP66, Mechanical
(L6) EX Magnetic switch 2 pcs – Elobau, AISI6118, Magnetic
(L7) EX Magnetic switch 4 pcs – Elobau, AISI6118, Magnetic
(L8) EX Magnetic switch 2 pcs – Pepperl & Fuchs, AISI303, Inductive
(L9) EX Magnetic switch 4 pcs – Pepperl & Fuchs, AISI303, Inductive
(M1) Solenoid valve – SMC, Aluminium, 24 VDC
(M2) Solenoid valve – SMC, Aluminium, 230 VAC
(M3) EX solenoid valve – ASCO, Brass, 24 VDC
(M4) EX solenoid valve – ASCO, Brass, 230 VAC
(M5) EX solenoid valve – Bifold, AISI316, 24 VDC
(P1) Manual pneumatic valve – SMC, Aluminium
(P2) Manual pneumatic valve – Bifold, AISI316
(S3) Limit switch open/Close – Belimo, SN2, Mechanical
(SC) Cover box – Stainless steel
(ST) Pneumatic tubing & fittings – AISI316
(ED) Manual over-ride handle – Halton DOT or HV-SKU
(O1) Smart override handle – Halton, HSO Schischek
(O2) Smart override handle – Halton, HSO Pneumatic

Code example
FD3/R-1300-1200,FA=C1,SF=HA,FS=SO,MA=CS,FM=C5,FI=HG,RE=Z2,FU=50,ZT=N,AC=E2

Downloads

  • FDB2 – A0(A60) Fire and gas damper

    Data

    en

    Shape 2
  • FDB2 A0(A60) Kaasutiivis palopelti

    Data

    fi

    Shape 2
  • FDB2 – A0(A60) Clapet coupe-feu et gaz

    Data

    fr

    Shape 2
  • FDB2 – A0(A60) Brand- und Gasschutzklappe

    Data

    de

    Shape 2
  • FDB2 用于高要求应用的 A0(A60) 防火隔烟阀

    Data

    cn

    Shape 2
  • Halton FDB2 datasheet 2022

    Data

    English
    Shape 2
  • ABS Certificate for Halton FDB2

    Data

    English
    Shape 2
  • ATEX Certificare for FDB2, FEX, FDL, FDO, FDA

    Data

    English
    Shape 2
  • BV Certificate for Halton FDB2

    Data

    English
    Shape 2
  • CCS Certificate for Halton FDB2

    Data

    简体中文 (zh)
    Shape 2
  • DNV Certificate for Halton FDB2

    Data

    English
    Shape 2
  • EAC Certificate for Halton FDA, FDB2, FDO, FDH, FCE, UTA, UTG, BDH, BRD, BLD

    Data

    Русский (ru)
    Shape 2
  • EC Type Examination Certificate for Halton FDB2

    Data

    English
    Shape 2
  • RMRS Certificate for Halton FDB2

    Data

    Русский (ru)
    Shape 2
  • TR CU – SAFE Certificate for Halton FDB2, FDL, FEX, UTG, UTX, UTP, UTN, UTT, BLD, BRD

    Data

    Русский (ru)
    Shape 2
  • LR Transport Canada Certificate for Halton FDB2

    Data

    English
    Shape 2
  • LR Certificate for Halton FDB2

    Data

    English
    Shape 2
  • Halton Marine Oy MED Quality System Module D Certificate

    Data

    English
    Shape 2
  • SIL 2 Safety Assessment Certificate

    Data

    English
    Shape 2
Contact Us
  • Hidden
  • Max. file size: 64 MB.