DRV - Terminal unit

Multi-nozzle terminal unit for installation without suspended ceiling

Circular and compact in design for free installation with adjustable air flow.

  • Horizontal or vertical air supply
  • Directional nozzles with two-slot air path efficiently deflect the airstreams
  • Supply air velocity is efficiently reduced due of high mixing effect
  • Integrated circular balancing plenum with measurement and adjustment functions
  • Circular duct connection with gasket
  • Detachable front panel enables cleaning of the terminal unit and ductwork

The diffuser and plenum shall be made of painted steel with a white (RAL 9010) standard colour. The front panel of the diffuser is equipped with plastic nozzles, which shall have two-slot construction in order to ensure effective mixing of supply air. Nozzles shall be individually adjustable to provide high flexibility for the adjustment of the throw pattern.

The diffuser shall be integrated to a balancing plenum equipped with a measurement and adjustment module.

The diffuser shall have detachable front panel in order to provide access to the measurement and balancing module in the plenum and to the duct.

The plenum shall have detachable a spigot equipped with integral gasket for airtight duct connection.

Introduction

Halton DRV

Terminal unit

  • Horizontal or vertical air supply
  • Directional nozzles with two-slot air path efficiently deflect the airstreams
  • Supply air velocity is efficiently reduced due of high mixing effect
  • Integrated circular balancing plenum with measurement and adjustment functions
  • Circular duct connection with gasket
  • Detachable front panel enables cleaning of the terminal unit and ductwork

Dimensions

Dimensions


Halton DRV

NS ØW ØW1 H H1 ØD
100 300 289 231 93 99
125 300 289 231 103 124
160 450 439 269 121 159
200 450 439 293 138 199
250 600 589 351 174 249

Material

Material


Halton DRV 

 Part  Material  Note
 Front panel  Steel  
 Nozzles  Polypropylene (PP)  Colour alternatives:
 White, Grey and Black
 Plenum  Galvanised steel  
 Attenuation material  Polyester fibre  
 Coupling sleeve  Galvanised steel  
 Gasket  Rubber compound  
 Finishing  Painted, white (RAL 9010)  Special colours available

Function

Function


Halton DRV

 

Air is supplied either horizontally into the space or alternatively vertically through the adjustable nozzles in the front panel of the diffuser and mixed with the room air outside of the diffuser. Horizontal swirl jet and different air patterns can also achieved by adjusting the nozzles.

The recommended maximum air temperature difference between supply and room air is 10 0C.

The maximum recommended temperature for plastic material is 60 0C.

Installation

Installation


Halton DRV

Code description
1.    Front panel with nozzles
2.    Plenum

The terminal unit is connected directly to the duct by screwing or riveting. Adjust the flow pattern in the desired direction by individually rotating each nozzle in order to meet the required specification.

 It is recommended that the minimum safety distance before the terminal unit is 3xD.

Adjustment

Adjustment


Halton DRV

 

Code description
1.   Front panel with nozzles
2.   Measurement and adjustment module
3.   Plenum

The supply airflow is determined using the measurement and adjustment module MSM.

Detach the plug in the plenum and connect the manometer. Measure the differential pressure using the connected manometer. The supply airflow rate is calculated using the formula below.

Adjust the supply airflow rate by rotating the control spindle until the desired setting is achieved.
Lock the damper position with the screw.
Reassemble the tubes and spindle into the plenum and reinstall the plug.

The k- factors for installations with different safety distances (D = duct diameter)

NS > 8xD min. 3xD
100 6,0 8,5
125 10,0 13,0
160 17,1 22,8
200 27,5 32,1
250 47,9 55,5

Servicing

Servicing


Halton DRV

Detach the cover plug and open the front panel of the diffuser. By pressing the stoppers each nozzle can easily be removed through the front panel. Wipe the nozzles and front panel with damp cloth. The nozzles are relpaced by pushing into the front panel.

Remove the measurement and adjustment module by gently pulling the shaft (not the control spindle or measurement tubes!). Wipe the parts with damp cloth, instead of immersing in water.

Reassembly the measurement and adjustment module by pushing the shaft back into place until yhe unit meets the stopper.

Reinstall the front panel back into place.

Technical specification

Technical specification
 

The diffuser and plenum shall be made of painted steel with a white (RAL 9010) standard colour. The front panel of the diffuser is equipped with plastic nozzles, which shall have two-slot construction in order to ensure effective mixing of supply air. Nozzles shall be individually adjustable to provide high flexibility for the adjustment of the throw pattern.

 The diffuser shall be integrated to a balancing plenum equipped with a measurement and adjustment module.

The diffuser shall have detachable front panel in order to provide access to the measurement and balancing module in the plenum and to the duct.

The plenum shall have detachable a spigot equipped with integral gasket for airtight duct connection.

Product code

Product code
 

DRV-D

D = Diameter of duct Connection
      100, 125, 160, 200, 250  
     

Other options and accessories

CO = Colour
          W    White RAL 9010
          X     Special colour
          
         
Colour for nozzles not selectable.

ZT  = Tailored product
         N       No


Code example

           DRV-100, CO=W, ZT =N

Downloads & Media

Halton DRV - se
Type
Datasheet
Language
sueco (Suecia)
Size
196.3 kB
Halton DRV - gb
Type
Datasheet
Language
inglés (Reino Unido)
Size
558.8 kB
Halton DRV - fr
Type
Datasheet
Language
francés (Francia)
Size
1.0 MB