BDR - Plenum

Plenum for grilles
Ideal for spaces that need customisation in grille sizes.
- Plenum for connecting supply/exhaust grille to ductwork
- Ensures proper function of the supply air diffuser
- Wide range of grille dimensions and models
- Spring clips fastening of the grille
- Access for ductwork cleaning
Product Models & Accessories
- Model with sound attenuation material
- Detachable airflow rate measurement and adjustment module
Specification
The plenum shall be made of galvanised steel.
The plenum shall comprise an airflow measurement and adjustment unit.
The grille shall be detachable to provide access to the measurement and adjustment module in the plenum.
The plenum shall have mineral wool as sound insulation material.
The plenum shall reduce duct pressure and air velocity in order to supply air through the whole face area of the grille and improve the air distribution quality.
Halton BDR
Plenum for grilles
- Plenum for connecting supply/exhaust grille to ductwork
- Ensures proper function of the supply air diffuser
- Wide range of grille dimensions
- Spring clips fastening of the grille
- Access for ductwork cleaning
Product models & accessories
- Model with sound attenuation material
- Detachable airflow rate measurement and adjustment module (MSM)
Dimensions ▲
NS | L | H | K | K1 | ØD |
200x50 | 195 | 45 | 250 | 80 | 99 |
200x100 | 195 | 95 | 250 | 80 | 99 |
250x100 | 245 | 95 | 275 | 92 | 124 |
300x100 | 295 | 95 | 275 | 92 | 124 |
400x100 | 395 | 95 | 310 | 110 | 159 |
500x100 | 495 | 95 | 310 | 110 | 159 |
600x100 | 595 | 95 | 350 | 130 | 199 |
800x100 | 795 | 95 | 400 | 155 | 249 |
1000x100 | 995 | 95 | 400 | 155 | 249 |
300x150 | 295 | 145 | 310 | 110 | 159 |
400x150 | 395 | 145 | 350 | 130 | 199 |
600x150 | 595 | 145 | 350 | 130 | 199 |
800x150 | 795 | 145 | 400 | 155 | 249 |
1000x150 | 995 | 145 | 465 | 188 | 314 |
1200x150 | 1195 | 145 | 505 | 208 | 354 |
1500x150 | 1495 | 145 | 550 | 230 | 399 |
200x200 | 195 | 195 | 310 | 110 | 159 |
400x200 | 395 | 195 | 400 | 155 | 249 |
600x200 | 595 | 195 | 465 | 188 | 314 |
800x200 | 795 | 195 | 465 | 188 | 314 |
1000x200 | 995 | 195 | 505 | 208 | 354 |
1200x200 | 1195 | 195 | 505 | 208 | 354 |
1500x200 | 1495 | 195 | 550 | 230 | 399 |
300x300 | 295 | 295 | 400 | 155 | 249 |
500x300 | 495 | 295 | 465 | 188 | 314 |
600x300 | 595 | 295 | 505 | 208 | 354 |
800x300 | 795 | 295 | 550 | 230 | 399 |
1000x300 | 995 | 295 | 550 | 230 | 399 |
400x400 | 395 | 395 | 505 | 208 | 354 |
600x400 | 595 | 395 | 550 | 230 | 399 |
800x400 | 795 | 395 | 550 | 230 | 399 |
1000x400 | 995 | 395 | 600 | 255 | 449 |
1200x400 | 1195 | 395 | 600 | 255 | 449 |
500x500 | 495 | 495 | 550 | 230 | 399 |
570x270 | 565 | 265 | 465 | 188 | 314 |
570x570 | 565 | 565 | 550 | 230 | 399 |
1170x570 | 1165 | 565 | 650 | 280 | 499 |
Material ▲
Part | Material | Note |
Plenum box /spigot | Galvanised steel | |
Insulation | Mineral wool | The mineral wool is fixed with nails |
Accessories ▲
Accessory | Code | Description |
Sound attenuation | IN | Mineral wool on 2 sides in the BDR plenum |
Sound attenuation | IN | Mineral wool on 5 sides in the BDR plenum |
Airflow measurement and adjustment unit | MSM | For supply installation (for spigot with diameter Ø 315) |
Airflow measurement and adjustment unit | MEM | For exhaust installation |
Function ▲
The duct pressure and air velocity are reduced inside the Halton BDR plenum box. Consequently supply air is evenly spread over the surface of the grille. The airflow rate can be adjusted using the optional measurement and adjustment module MSM.
Installation ▲
The Halton BDR plenum is connected to the distribution ductwork with a spigot.
When equipped with a measurement and adjustment module (1), the recommended safety distance upstream of the device is at least 3xD, in order to ensure a reliable airflow rate measurement.
The unit's control spindle must not be excessively bent.
With wall installations the required hole size is at least (L x H).
The spigot comprises two grooves to enable the grille springs to lock.
Clip Fastening of grille (Standard)
Adjustment ▲
In order to enable airflow adjustment and measurement of airflow rate, it is recommended that the grille be connected to the plenum equipped with the MSM module.
The supply flow rate is determined by using the measurement and adjustment module MSM.
Detach the grille and pass the tubes and control spindle through the grille.
Push the grille back into place.
Measure the differential pressure with a manometer. The flow rate is calculated using the formula below.
Adjust the airflow rate by rotating the control spindle until the desired setting is achieved.
Lock the damper position with a screw.
Replace the tubes and spindle into the plenum and replace the grille.
The k-factor for installations with different safety distances
(D= duct diameter)
Supply air
BDR-D | >8xD | min 3xD |
125 | 9.9 | 12.6 |
160 | 16.9 | 21.9 |
200 | 28.3 | 31.0 |
250 | 47.9 | 51.5 |
315 | 78.6 | - |
Exhaust
The airflow rate is determined by measuring the differential pressure between the measurement tap on the Halton BDR plenum and the room air.
The corresponding airflow rate is calculated using the formula above.
The desired airflow rate can be adjusted by turning the control spindle of the adjustment unit MEM.
Servicing ▲
Remove the measurement and adjustment module by gently pulling the shaft (not the control spindle).
Wipe the parts with a damp cloth, instead of immersing in water.
Reassemble the measurement and adjustment module by pushing the shaft back into place until the module meets the stopper.
Specification ▲
The plenum is made of galvanised steel.
The plenum will comprise an airflow measurement and adjustment unit.
The grille is detachable to provide access to the measurement and adjustment module in the plenum.
The plenum has mineral wool as sound insulation material.
The plenum will reduce duct pressure and air velocity in order to supply air through the whole face area of the grille and improve the air distribution quality.
Order Code ▲
BDR/S-L-H
S = Parent product (grille)
AGC AGC
AGF AGF
AHD AHD
AHF AHF
ALE ALE
ALU ALU
AWE AWE
AWU AWU
FLE FLE
FLU FLU
HDF HDF
WDD WDD
WSD WSD
WTS WTS
L = Length
200, 201, 202, 203, ... +1, .., 20000
H = Height
50, 51, 52, 53, ... +1, .., 670
Other options and accessories
D = Size of duct connection
100, 125, 160, 200, 250, 315, 355, 400, 500
N = Number of duct connections
1, 2, 3, 4 ... +1, .., ((L-40)/D)
IN = Additional attenuation option
N No additional attenuation
2 2 sides
5 5 sides
OM = Measurement/ Adjustment module MSM
N No MSM-module
Y MSM module in each duct connection
ZT = Tailored Product
N No
Y Yes
Code example
BDR/AGC-200-50, D=100,N=1,IN=N,OM=N, ZT=N
Downloads & Media
Halton BDR - fr | Type Datasheet | Language French (France) | Size 1.0 MB |
Halton BDR - gb | Type Datasheet | Language English (United Kingdom) | Size 440.0 kB |
Halton BDR - ru | Type Datasheet | Language Russian (Russia) | Size 459.6 kB |
Halton BDR - se | Type Datasheet | Language Swedish (Sweden) | Size 440.9 kB |
Halton BDR - fi | Type Datasheet | Language Finnish (Finland) | Size 439.6 kB |
Halton BDR - nl | Type Datasheet | Language Dutch (Netherlands) | Size 441.9 kB |
Byggvarubedömning (Halton BDR) | Type Certificate | Language Swedish (Sweden) | Size 1.0 MB |