Halton EVA – Exhaust air unit

Exhaust air unit with airflow measurement and adjustment arrangement.

  • Exhaust air unit with airflow measurement and adjustment arrangement
  • Wide pressure drop range with low noise level
Request a Quote

Overview

  • Exhaust air unit with airflow measurement and adjustment arrangement
  • Wide pressure drop range with low noise level
  • Installation with balancing plenum or directly to rectangular ductwork
  • Detachable front panel enables cleaning of the unit and ductwork

Accessories

  • Balancing plenum with circular duct connection

Quick selection

Fig.1. Without plenum

Fig.2. With Halton PRL plenum

Dimensions

NS L L1
300×150 350 295
500×150 550 495
800×150 850 795

Weight

NS kg
300×150 2.5
500×150 3.6
800×150 5.4

Material

Part Material Note
Front panel Perforated steel
Adjustment
module
Aluminium Black as standard colour
Casing Galvanised steel  –
Finishing Painted /
White (RAL 9003/30%)
Special colours available

Function

Air in Halton EVA is exhausted through the front panel. The valve throttles the exhaust airflow and attenuates duct noise. The pressure drop and airflow rate are dependant on the distance of the cone elements of the adjustment module. The desired exhaust airflow rate is adjusted during the balancing of the airflows in a ductwork system.

Installation

Code description
1.   Front panel
2.   Adjusment module
3.   Casing

The Halton EVA exhaust unit is connected either directly to the duct by screwing or by riveting or alternatively to the Halton PRL balancing plenum
(models without flow control damper, but with sound attenuation material).
When the Halton EVA unit is installed to a Halton PRL balancing plenum, the Halton EVA casing (3) replaces the telescopic collar of the Halton PRL thus making the Halton PRL collar unnecessary.

Dimension of wall or ceiling openings

NS X Y
300×150 298 148
500×150 498 148
800×150 798 148

Adjustment

Measure the differential pressure using a manometer. The flow rate is calculated using the formula below:

Adjust the airflow rate by turning the adjustment spindle until the desired setting is achieved.

Note!
Airflow rate adjustment is carried out using the adjustment arrangement of the Halton EVA exhaust unit even when connected to Halton PRI balancing plenum.

The k factor for different adjustment module openings (A)

Size 300×150 500×150 800×150
A k k k
0 1.90 3.54 6.00
1 2.68 5.66 10.95
 2 4.02 8.49 14.61
3 5.77 11.18 18.26
4 7.07 14.14 23.57
5 9.00 16.43 28.00
6 10.61 18.97 32.27
7 12.50 21.00 35.00

Servicing

Detach the perforated front panel of Halton EVA by gently pulling.
Remove the adjustment module by opening the clips.

Wipe the parts with a damp cloth. Do not immerse in water.

Reassemble the adjustment module so that the clips lock.
Push the front panel into place so that the clips lock.

Specification

The exhaust unit has a telescopic casing made of galvanised steel.
The unit comprises internal removable adjustment module and detachable perforated front panel.
The front panel is attached to the casing with clips.

The unit has a fixed measurement tap for airflow measurement.
The airflow is adjustable by rotating the adjustment spindle.

Order code

EVA-W-H, CO-ZT

W = Width (mm)
300, 500, 800

H = Height (mm)
150

Other options and accessories

CO = Colour
SW   Signal white (RAL 9003)
X       Special colour (RAL xxxx)

ZT = Tailored product
N       No
Y       Yes (ETO)

Sub products

PRL  Balancing plenum

Code example

EVA-300-150, CO=SW, ZT=N

Downloads

  • Halton EVA – Exhaust air unit

    Data

    en

    Shape 2
  • Halton EVA – Poistoilmayksikkö

    Data

    fi

    Shape 2
  • Halton EVA – Unité d’extraction

    Data

    fr

    Shape 2
  • Halton EVA – Abluftelement

    Data

    de

    Shape 2
  • Halton EVA – Frånluftsdon

    Data

    se

    Shape 2
  • Halton EVA – fr

    Data

    fr_FR
    Shape 2
Contact Us
  • Hidden
  • Max. file size: 64 MB.