
UKV - Airflow damper

Airflow management damper for rectangular ducts
Rectangular VAV and CAV with factory-set airflow range limits option (min./max. airflow rates). Used for different airflow and duct pressure control applications. Pressure-independent operation. Available in various rectangular modular sizes.
- Control damper for different airflow and duct pressure control applications
- Model with shut-off operation; tightness fulfils EN 1751, class 1 requirements
- Casing tightness fulfils EN 1751, class B requirements
- Two extra models with external insulation 15 mm and 30 mm
- Several airflow controller options
- Factory-set airflow range limits (min./max. airflow rates) as an option
- Pressure-independent operation
- Galvanised steel design
- Suitable for large air flow rates, from 1 m/s up-to 11 m/s on some models
Product models and Accessories
- Three external insulation options are available:
- No insulation
- 15 mm insulation thickness of mineral wool
- 30 mm insulation thickness of mineral wool
- Fast running actuators, when the UKV is used in combination with Halton Laboset laboratory system
The pressure-independent variable airflow control damper shall be made of galvanised steel, with an airflow measurement probe of aluminium.
The tightness of the control damper in closed position shall conform to standard EN1751 class 1 and casing tightness to EN 1751/C.
The management damper section shall contain airflow measurement, flow controller and damper actuator.
Design airflow range limits shall be calibrated at the factory.
Controller settings shall be adjustable on site with a PC or a handheld tool.
The airflow controller shall have control signal input 0...10 VDC or 2 ...10 VDC and output 0...10 VDC or 2...10VDC for airflow feedback.
Supply power shall be 24 VAC.
Halton UKV
VAV-regelaar – Voor grote debieten en rechthoekige kanalen
- VAV-regelaar met drukonafhankelijke werking.
- De dichtheid van de kleppen voldoet aan klasse 1van de EN1751, die van de behuizing aan klasse B van de EN1751.
- Toepassing: voor grote luchtdebieten of voor aansluiting op rechthoekige kanalen.
- Vervaardigd uit gegalvaniseerd staal.
- Verscheidene regelaaropties mogelijk.
- In defabriek ingesteld luchtdebietbereik (min.- / max. luchtdebiet).
- Geschikt voor een groot debietbereik, van 1 m/s tot 11 m/smet bepaalde regelaarmodellen.
Opties en accessoires
- 2 isolatieopties :
- glaswolisolatie van 15 mm
- glaswolisolatie van 30 mm
- Verscheidene regelaartypes voor een behoeftespecifieke regeling:
- min.debiet van 1 m/s: motorregelaars EK, EE
- min.debiet van 2 m/s: EG
- Snel lopende motor bij gebruik van de UKV-regelaarmet het Envirolabpro-systeem vanHalton: E6, E7
Materiaal ▲
Onderdeel | Materiaal |
Behuizing | Gegalvaniseerd |
staal Klepblad | Gegalvaniseerd |
staal Klepisolatie | Polyurethaan |
Klepbladafdichting | Silicone |
Lagers | Legering van polyamideen molybdeensulfide |
Meetsonde | Aluminium |
Externe isolatie | Glaswol |
Klepas15 x 15 mm | Gegalvaniseerd staal |
Afmetingen ▲
UKV / I1 - isolatie van 25mm (standaard)
W* | H | W1 | H1 |
400...800 | 200 | W+44 | H+44 |
400...1600 | 400 | W+44 | H+44 |
400...1600 | 600 | W+44 | H+44 |
400...1600 | 800 | W+44 | H+44 |
400...1600 | 1000 | W+44 | H+44 |
*Afmetingen van de kanaalaansluiting (per stap van 100 mm) W1 en H1: maten alles inbegrepen
UKV / I2 - isolatie van 50mm
W* | H | W1 | H1 |
400...800 | 200 | W+95 | H+95 |
400...1600 | 400 | W+95 | H+95 |
400...1600 | 600 | W+95 | H+95 |
400...1600 | 800 | W+95 | H+95 |
400...1600 | 1000 | W+95 | H+95 |
*Afmetingen van de kanaalaansluiting (per stap van 100 mm) W1 en H1: maten alles inbegrepen
Werking ▲
WERKING
De VAV-regelaar UKV bevat een meetkruis, een luchtdebietregelaar en een actuator. Het luchtdebiet wordt op basis van een actuele debietmeting geregeld door de positie van de regelklepbladen te wijzigen. Het instelpunt voor het luchtdebiet kan tussen de in de fabriek ingestelde minimum- en maximumwaarden worden gewijzigd, d.m.v. een analoog 0-10 of 2-10 VDC-stuursignaal. De UKV-regelaar handhaaft het vereiste luchtdebiet onafhankelijk van de drukschommelingen in het kanaal.
De statische-drukregelaar handhaaft de gewenste constante druk(in het kanaal of in het lokaal) op basis van een statische-drukmeting. De regelaar kan ook met een gebouwbeheersysteem worden verbonden.
Modellen ▲
MODELLEN
Min. debiet van1 m/s met motorregelaars EK,EE
Debiete (m3/h) | Lengte W [mm] | |||||||
Hoogte H [mm] | 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 |
200 | 144 | 288 | 432 | 576 | 720 | 864 | 1 008 | 1 152 |
300 | 216 | 432 | 648 | 864 | 1 080 | 1 296 | 1 512 | 1 728 |
400 | 288 | 576 | 864 | 1 152 | 1 440 | 1 728 | 2 016 | 2 304 |
500 | 360 | 720 | 1 080 | 1 440 | 1 800 | 2 160 | 2 520 | 2 880 |
600 | 432 | 864 | 1 296 | 1 728 | 2 160 | 2 592 | 3 024 | 3 456 |
700 | 504 | 1 008 | 1 512 | 2 016 | 2 520 | 3 024 | 3 528 | 4 032 |
800 | 576 | 1 152 | 1 728 | 2 304 | 2 880 | 3 456 | 4 032 | 4 608 |
900 | 648 | 1 296 | 1 944 | 2 592 | 3 240 | 3 888 | 4 536 | 5 184 |
1000 | 720 | 1 440 | 2 160 | 2 880 | 3 600 | 4 320 | 5 040 | 5 760 |
Min. debiet van 2 m/s met motorregelaar EG
m3/h | W | |||||||
H | 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 |
200 | 288 | 576 | 864 | 1 152 | 1 440 | 1 728 | 2 016 | 2 304 |
300 | 432 | 864 | 1 296 | 1 728 | 2 160 | 2 592 | 3 024 | 3 456 |
400 | 576 | 1 152 | 1 728 | 2 304 | 2 880 | 3 456 | 4 032 | 4 608 |
500 | 720 | 1 440 | 2 160 | 2 880 | 3 600 | 4 320 | 5 040 | 5 760 |
600 | 864 | 1 728 | 2 592 | 3 456 | 4 320 | 5 184 | 6 048 | 6 912 |
700 | 1 008 | 2 016 | 3 024 | 4 032 | 5 040 | 6 048 | 7 056 | 8 064 |
800 | 1 152 | 2 304 | 3 456 | 4 608 | 5 760 | 6 912 | 8 064 | 9 216 |
900 | 1 296 | 2 592 | 3 888 | 5 184 | 6 480 | 7 776 | 9 072 | 10 368 |
1000 | 1 440 | 2 880 | 4 320 | 5 760 | 7 200 | 8 640 | 10 080 | 11 520 |
Nominale debieten voor alle motorregelaartypes
m3/h | W | |||||||
H | 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 |
200 | 1859 | 3718 | 5577 | 7435 | 9294 | 11153 | 13012 | 14871 |
300 | 2 788 | 5577 | 8365 | 11153 | 13942 | 16730 | 19518 | 22306 |
400 | 3718 | 7435 | 11153 | 14871 | 18589 | 22306 | 26024 | 29742 |
500 | 4647 | 9294 | 13942 | 18589 | 23236 | 27883 | 32530 | 37177 |
600 | 5577 | 11153 | 16730 | 22306 | 27883 | 33460 | 39036 | 44613 |
700 | 6506 | 13012 | 19518 | 26024 | 32530 | 39036 | 45542 | 52048 |
800 | 7435 | 14871 | 22306 | 29742 | 37177 | 44613 | 52048 | 59484 |
900 | 8365 | 16730 | 25095 | 33460 | 41825 | 50189 | 58554 | 66919 |
1000 | 9294 | 18589 | 27883 | 37177 | 46472 | 55766 | 65060 | 74355 |
REGELUNITS (CU)
De UKV-debietregelaarkan worden uitgerust met verschillende soorten regelunits voor de regeling van het debiet of de druk.
Luchtdebietregeling:
• Voor toevoer- en afzuigtoepassingen
• Functie voor volledige afsluiting
• Bedrijfsbereik:omgevingstemperatuurvan 0tot 50ºC
• Relatieve omgevingsvochtigheid < 95%,niet-condenserend
Luchtregelopties:
EK = Halton NMV-D3-MF-F.1 HI (10 Nm)
EE = Halton NMV-D3-MP-F.1 HI (10 Nm) EG=SiemensGLB181.1E/3(10Nm)
De regelaars EKen EEzijn uitgerust met een dynamische-drukverschilsensor met laag een bypass-debiet via het sensorelement.Daarom zijn deze regelaars niet geschikt om in sterk verontreinigde omgevingen te worden gebruikt.Op de EG-regelaar gebeurt de drukmeting zonder bypass-debiet. De EE-regeling omvat de MP-busverbinding.
Drukregeling:
• Voor toevoer- en afzuigtoepassinen
• Functie voor volledige afsluiting
• Statisch drukbereik van 30tot 100Paofvan 90tot 300Pa
• Bedrijfsbereik:omgevingstemperatuurvan 0tot 50ºC
• Relatieve omgevingsvochtigheid < 95%,niet-condenserend
Statische-drukregelopties:
EG=SiemensGLB181.1E/3(10Nm)
ES = Belimo VRP-STP + VFP-100 + NM24A-V (regelbereik:30tot 100Pa)
ER=BelimoVRP-STP+VFP-300+NM24A-V(regelbereik:90tot 300Pa)
De twee regelaars ESen ERzijn uitgerust met een potentiometer voor de instelling van de statische drukwaarde bereik:30tot 100%).
Installatie ▲
INSTALLATIE
Bij de montage van de luchtdebietregelaar dient er rekening worden gehouden met de afstanden die voor zijn goede werking vereist zijn. Ook de richting van de luchtstroming moet in acht worden genomen bij de montage van deregelaar in het kanaal.
Voor de drukregeling bedraagt de minimumafstand tussen de regelaar en de statische-drukmeetnippel 5xD. Voor een rechthoekige sectie wordt de equivalente aeraulische diameter berekend d.m.v. onderstaande formule:
D=2 x W x H/(W+H)
BEDRADING
De bedrading moet steeds door vaklui en overeenkomstig het algemene regelingschema worden uitgevoerd. Voor de voeding van alle stuurinrichtingen moet er een veiligheidsisolatietransformatorworden gebruikt.
De bedradingschema’s worden gegeven voor de volgende toepassingen:
1A: UKV;CU=EK/EE VAV-toepassing
1B: UKV;CU=EK/EE Tijdelijke opheffing sturing
1C: UKV;CU =EK/EE Voorbeeld:VAV-sturing door een ruimtethermostaat
1D: UKV;CU =EK/EE Voorbeeld:VAV-regeling d.m.v. gebouwbeheersysteem
1E: UKV;CU =EK/EE Voorbeeld:parallelmontagemet gebouwbeheersysteeM
3A: UKV;CU = EG VAV-toepassing
3B: UKV;CU = EG Constant luchtdebiet
5A: UKV;CU = ES/ER Drukregeling in het kanaal
5C: UKV;CU = ES/ER Tijdelijke opheffing sturing
1A&B.UKV;EK/EE(NMV-D3-MP/MFHI)–typische en algemene bedradingopties
1A.VAV-toepassing 1B.Tijdelijke opheffing voor sturing –alle opties
CODE | OMSCHRIJVING |
Halton | Geleverd door Halton |
OEM | Geleverd door een andere fabrikant |
ACD | UKV |
1 ( ^ ) | Nulleider VAC-systeem |
2 (~) | Fase 24 VCA |
3 (Y) | 2tot10of 0tot 10 VDC-stuursignaalinput luchtdebietinstelling |
5 (U5) | 2tot10of 0tot 10 VDC-stuursignaaloutput debietterugkoppeling |
*) | Diode 1N 4007 |
2 ... 10 VCA | 0 ... 10 VCA | A | B | C | D | E | |
GESLOTEN | qv_min | ON | Off | Off | Off | Off | |
qv_min | qv_min | Off | Off | Off | Off | Off | Constant debiet |
Variabelqv_min...qv_max | Variabelqv_min...qv_max | Off | ON | Off | Off | Off | |
0,5 x (qv_max - qv_min)+qv_min | 0,5 x (qv_max - qv_min)+qv_min | Off | Off | ON | Off | Off | Constant debiet |
qv_max | qv_max | Off | Off | Off | ON | Off | Constant debiet |
OPEN | OPEN | Off | Off | Off | Off | ON |
Er zijn twee stuurmodi mogelijk:0tot10VDCen 2tot 10VDC.De voornaamste verschillen tussen deze modi hangen samen met de werking met lageluchtdebietenen met het gebruik van de sluitfunctie.
Sluiting door stuursignaal:
Behalve in situaties waarin de relaissturing tijdelijk wordt opgeheven, wordt de regelklep volledig gesloten als:
• 0tot 10VDC:hetminimumdebiet van de UKV-regelaaris ingesteld op 0 %(0dm³/sof0m³/h)en het stuursignaalwonder de 0,1VDC daalt
• 2tot 10VDC:het stuursignaalwvan deUKV-regelaaronder de 0,5VDC daalt
• 0tot10VDCen 2tot 10VDC.despanning voor de instelling van het luchtdebiet daalt onder een waarde die overeenstemt met een luchtsnelheid van minder dan 1,5m/s
MODUS | SPANNING Y, VCC | FUNCTIE |
0 tot10 VCC | 0,0 tot 0,1 | Nominaaldebiet (gesloten alsqv_min=0%) |
0,1 tot 10,0 | Modulerend,qv_mintotqv_max | |
10,0 | Maximumluchtdebiet | |
2 tot10 VCC | 0,0 tot 0,5 | Klep gesloten |
0,5 tot 2,0 | Minimumluchtdebiet | |
2,0 tot 10,0 | Modulerend,qv_mintot qv_max | |
10,0 | Maximumluchtdebiet |
1C&1D.Voorbeeld:UKV;EK/EE(NMV-D2-MP/MFHI) -variabel debiet geregeld door eenruimtethermostaatof door het gebouwbeheersysteem
1C.Toepassing met ruimtethermostaat 1DToepassing met gebouwbeheersysteem
CODE | OMSCHRIJVING |
Halton | Geleverd door Halton |
OEM | Geleverd door een andere fabrikant |
ACD | UKV |
1 ( ^ ) | Nulleider VAC-systeem |
2 (~) | Fase 24 VCA |
3 (Y) | 2 tot 10 of 0 tot 10 VDC-stuursignaalinputdebietinstelling |
5 (U5) | 2 tot 10 of 0 tot 10 VDC-signaaloutput debietterugkoppeling |
RC | Ruimtethermostaat |
PLC | Gebouwbeheersysteem |
C (AO) | Stuursignaal luchtdebietinstelling |
F (AI) | Terugkoppelinput actueel gemeten luchtdebiet (terugkoppelsignaal) |
1E.Voorbeeld:UKV;EK/EE(NMV-D2-MP/MFHI)–parallelle regeling van het luchtdebiet door een gebouwbeheersysteem
1E.Parallelle regeling van het luchtdebiet d.m.v. het gebouwbeheersysteem
CODE | OMSCHRIJVING |
Halton | Geleverd door Halton |
OEM | Geleverd door een andere fabrikant |
ACD1 ACD2 | UKV voor toevoer UKVvoor afvoer |
1 ( ^ ) | Nulleider VAC-systeem |
2 (~) | Fase 24 VCA |
3 (Y) | 2 tot 10 of 0 tot 10 VDC-stuursignaalinput debietinstelling |
5 (U5) | 2 tot 10 of 0 tot 10 VDC-signaaloutput debietterugkoppeling |
PLC | Gebouwbeheersysteem |
C (AO) | Stuursignaal luchtdebietinstelling |
F (AI) | Terugkoppelinput actueel gemeten debiet (terugkoppelsignaal) |
3A&3B.UKV;CU = EG(GLB181.1E/3)–typetoepassingmet variabel debiet(VAV) en met constant debiet
3A.VAV-toepassing 3B.Constant luchtdebiet
CODE | OMSCHRIJVING |
Halton | Geleverd door Halton |
OEM | Geleverd door een andere fabrikant |
ACD | UKV |
2 (G0) | Nulleider VAC-systeem |
1 (G) | Fase 24 VCA |
8 (YC) | 2 tot 10 of 0 tot 10 VDC-signaalinput debietinstelling |
9 (U) | 2 tot 10 of 0 tot 10 VDC-signaaloutput debietterugkoppeling |
6 (Y1) | Input tijdelijke opheffing |
7 (Y2) | Input tijdelijke opheffing |
Constant debiet | A | B |
Gesloten | Off | ON |
Min.debiet | Off | Off |
Max.debiet | ON | ON |
Open | ON | Off |
5A&5B.UKV;CU = ESofCU = ER–drukregeling in het luchtkanaal
5A&B.Drukregeling in het kanaal 5C.Sturing met tijdelijke opheffing
CODE | OMSCHRIJVING |
Halton | Geleverd door Halton |
OEM | Geleverd door een andere fabrikant |
ACD | UKV |
1 (^) | Nulleider VAC-systeem |
2 (~) | Fase 24 VCA |
3 (W1) | 2 tot 10 of 0 tot 10 VDC-signaalinput debietinstelling |
5 (U5) | 2 tot 10 of 0 tot 10 VDC-signaaloutput debietterugkoppeling |
6 (y) | Actuatorsignaal |
7 (Z) | Input tijdelijke opheffing |
*) | Diode1N 4007 |
**) | Jumper 2-4voor sturing door een potentiometer wordt in de fabriek aangebracht; hij moet worden verwijderd bij gebruik van 2tot 10 VDC-input W1. |
Minimaleveiligheidsafstand tussen de regelaar en de drukmeetnippel: 5 x D.
Tijdelijke opheffing | A | B |
Gesloten | Off | ON |
Drukregeling | Off | Off |
Open | ON | Off |
De drukregelaar is uitgerust met een potentiometer voor de aanpassing van het drukinstelpunt.
Ingebruikname ▲
Debietregeling
Onderstaande tabel geeft de nominale debieten van de Halton UKV weer:
l/s | W | |||||||
H | 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 |
200 | 516 | 1033 | 1549 | 2065 | 2582 | 3098 | 3614 | 4131 |
300 | 775 | 1549 | 2324 | 3098 | 3873 | 4647 | 5422 | 6196 |
400 | 1033 | 2065 | 3098 | 4131 | 5164 | 6196 | 7229 | 8262 |
500 | 1291 | 2582 | 3873 | 5164 | 6454 | 7745 | 9036 | 10327 |
600 | 1549 | 3098 | 4647 | 6196 | 7745 | 9294 | 10843 | 12392 |
700 | 1807 | 3614 | 5422 | 7229 | 9036 | 10843 | 12651 | 14458 |
800 | 2065 | 4131 | 6196 | 8262 | 10327 | 12392 | 14458 | 16523 |
900 | 2324 | 4647 | 6971 | 9294 | 11618 | 13942 | 16265 | 18589 |
1000 | 2582 | 5164 | 7745 | 10327 | 12909 | 15491 | 18072 | 20654 |
m3/h | W | |||||||
H | 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 |
200 | 1859 | 3718 | 5577 | 7435 | 9294 | 11153 | 13012 | 14871 |
300 | 2788 | 5577 | 8365 | 11153 | 13942 | 16730 | 19518 | 22306 |
400 | 3718 | 7436 | 11153 | 14871 | 18598 | 22306 | 26024 | 29742 |
500 | 4647 | 9294 | 13942 | 18589 | 23236 | 27883 | 32530 | 37177 |
600 | 5577 | 11153 | 16730 | 22306 | 27883 | 33460 | 39036 | 44613 |
700 | 6506 | 13012 | 19518 | 26024 | 32530 | 39036 | 45542 | 52048 |
800 | 7435 | 14871 | 22306 | 29742 | 37177 | 44613 | 52048 | 59484 |
900 | 8365 | 16730 | 25095 | 33460 | 41825 | 50189 | 58554 | 66919 |
1000 | 9294 | 18589 | 27883 | 37177 | 46472 | 55766 | 65060 | 74355 |
W Breedtevan de module (mm)
H Hoogte van de module (mm)
Het actuele gemeten luchtdebiet (qv) kan worden bepaald door het terugkoppelsignaal van de regelaar (UofU5)en de nominale waarde van het regeldebiet (qv_nom).
Signaal | Formule | Regelaartypeen -modus | Aanskuiting nulleiderl | Terminal- signaal |
0...10 VDC | qv=qv_nom*U/10 | UKV;CU=EM, EK, EC fr EE (LMV-D3-MP/MF HI of NMV-D3-MP/MF HI), modus 0...10 V UKV;CU=EG (GLB181.1E/3) | 1 (GND) 2(G0) | 5 (U5) 9(U) |
2...10 VDC | qv=qv_nom*(U-2)/8 | UKV;CU=EM, EK, EC of EE (LMV-D3-MP/MF HI of NMV-D3-MP/MF HI), modus 2...10 V UKV;CU=ED (VRD3+NM24A-V) | 1 (GND) 1 (^) | 5 (U5) 5 (U5) |
Het actuele luchtdebiet kan eveneens worden berekend op basis van de door de meetsensor gemeten verschildruk en de k-waarde van deze laatste. De juiste k-waardewordt vermeld in de bij het product geleverde documentatie:
qv Actueel luchtdebiet [l/s]
k k-waardevan het product,waarin k = W (mm) x H (mm) x 0,001054
Δpm Door de sensor gemeten verschildruk [Pa]
De regelaars EKen EE zijn uitgerust met een dynamische-drukverschilsensor waardoor een klein bypass-debiet stroomt. Bijgevolg kan er geen manuele differentiaalmanometer in parallel op de debietregelaar worden aangesloten. Het gebruik van een manuele manometer vereist de onderbreking van de voeding van de debietregelaar om bewegingen van de luchtklep tijdens het meten van het debiet door de drukverschilsensor te vermijden. De druk in het kanaal kan variëren tijdens de meting.*
De EG-debietregelaar is uitgerust met een statische-druksensor met membraan met automatische ijking, waardoor geen lucht stroomt. Bijgevolg kan er een manuele differentiaalmanometer parallel op de debietregelaar worden aangesloten (bijv.met behulp van T-stukken) en beide metingen kunnen gelijktijdig met continue regeling werken.
Wanneer er bij de bestelling van de UKVgeen in te stellen luchtdebieten worden gespecificeerd, wordt het minimumluchtdebiet ingesteld op 0 en stemt het maximumluchtdebiet overeen met het nominale luchtdebiet.
Drukregeling ▲
DRUKREGELING
Het actuele gemeten luchtdebiet kan worden bepaald door het terugkoppelsignaal van de regelaar en de nominale waarde van het regeldebiet.
SIGNAAL | FORMULE | REGELAARTYPEEN-MODUS | AANSLUITING NULLEIDER | |
2 à 10 VCC | Pst = 100 Pa * (U2)/8 | UKV;CU=ES (VRP-STP+VFP-100) UKV;CU=ES (VRP-STP+VFP-100) | 1 ( ^ ) 1 ( ^ ) | 5 (u5) 5(U5) |
De actuele statische druk kan eveneens worden afgelezen van onderstaande tabel:
Beschrijving ▲
De VAV-regelaar met drukonafhankelijke werking is vervaardigd uit gegalvaniseerd staal en uitgerust met een debietmeetsonde uit aluminium.
De dichtheid van de klep in gesloten stand voldoet aan de EN 1751 /1 en die van de behuizing aan de eisen voor klasse B van de EN 1751.
Het gedeelte voor het beheer van de luchtklep bestaat uit een meetkruis, een debietregelaar en een actuator voor de sturing van de klep.
De grenzen van het luchtdebietbereik worden in de fabriek gekalibreerd.
Het instelpunt kan ter plaatse worden aangepast met behulp van een pc of een draagbaar toestel.
De debietregelaar werkt met een stuursignaalinput van 0 tot 10VDC of van 2 tot 10VDC en een output van 0 tot 10VDC voor de debietterugkoppeling.
De voedingsspanning bedraagt 24VAC.
Downloads & Media
Halton UKV - fr | Type Datasheet | Taal Frans (Frankrijk) | Grote 1,8 MB |
Halton UKV - se | Type Datasheet | Taal Zweeds (Zweden) | Grote 599,2 kB |